Multi9 - C60L - MCB - 2P - 3 A - C Curve - 415 V - 25 kA

Multi9 - C60L - MCB - 2P - 3 A - C Curve - 415 V - 25 kA

SQDM9F17203 M9F17203 360648057801
0.00 / EA
  • Certifications: CCC, EAC
  • Depth: 72 mm
  • Height: 81 mm
  • Line Rated Current: 3 A, 50 °C
  • Mounting Type: Clip-On
  • Net Weight: 0.24 kg
  • Operating Temperature: -30-70 °C
  • Standard: EN/IEC 60947-2
  • Storage Temperature: -40-80 °C
  • Strip Length: 14 mm
  • Width: 36 mm
This Multi9 C60L is a low voltage miniature circuit breaker (MCB). It is a 2P circuit breaker with 2 protected poles, 3A rated current and C tripping curve. The rated short circuit breaking capacity goes up to 25kA at 415VAC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. Its fast closing mechanism, overvolatge resistance and high performance limitation improve its service life. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The operating frequency is 50Hz or 60Hz. The product can be clipped on a DIN rail. Pollution degree is 3. Overvoltage category is IV. The product colour is light grey (RAL7035). The dimensions are (W) 36mm x (H) 81mm x (D) 72mm. The weight is 0.24kg. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 80°C.
  • Product Description
  • Specifications
This Multi9 C60L is a low voltage miniature circuit breaker (MCB). It is a 2P circuit breaker with 2 protected poles, 3A rated current and C tripping curve. The rated short circuit breaking capacity goes up to 25kA at 415VAC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. Its fast closing mechanism, overvolatge resistance and high performance limitation improve its service life. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The operating frequency is 50Hz or 60Hz. The product can be clipped on a DIN rail. Pollution degree is 3. Overvoltage category is IV. The product colour is light grey (RAL7035). The dimensions are (W) 36mm x (H) 81mm x (D) 72mm. The weight is 0.24kg. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 80°C.
  • [Ue] Rated Operational Voltage : 240 V AC 50/60 Hz between phases || 415 V AC 50/60 Hz between phases || 440 V AC 50/60 Hz between phases || <= 125 V DC
  • Device Application : distribution
  • Connections - Terminals : tunnel type terminal top or bottom) 1-25 mm² - rigid || tunnel type terminal top or bottom) 1-25 mm² - flexible || tunnel type terminal top or bottom) 1-25 mm² - flexible with ferrule
  • Ambient Air Temperature For Storage : -40-80 °C
  • Tropicalisation : 2 IEC 60068-1
  • Breaking Capacity Code : L
  • Product Or Component Type : miniature circuit-breaker
  • Tightening Torque : 2-2 N.m top or bottom
  • [Uimp] Rated Impulse Withstand Voltage : 6 kVEN/IEC 60947-2
  • Limitation Class : 3
  • Range Of Product : Multi 9
  • Control Type : toggle
  • Product Name : Multi 9 C60
  • Line Rated Current : 3 A 50 °C EN/IEC 60947-2
  • Trip Unit Technology : thermal-magnetic
  • Mounting Support : DIN rail
  • Earth-Leakage Protection : separate block
  • Color : Gray
  • Maximum Height : 81 mm
  • Relative Humidity : 95-95 % 55-55 °C
  • Maximum Width : 36 mm
  • Utilisation Category : category A EN/IEC 60947-2
  • Local Signalling : ON/OFF indication
  • Poles Description : 2P
  • Pollution Degree : 3 EN/IEC 60947-2
  • Electrical Durability : 10000 cycles
  • [Ics] Rated Service Breaking Capacity : 25 kA 50 % EN/IEC 60947-2 - 240 V AC 50/60 Hz || 12.5 kA 50 % EN/IEC 60947-2 - 415 V AC 50/60 Hz || 10 kA 50 % EN/IEC 60947-2 - 440 V AC 50/60 Hz || 30 kA 100 % EN/IEC 60947-2 - <= 125 V DC
  • [Ui] Rated Insulation Voltage : 500 V AC 50/60 Hz EN/IEC 60947-2
  • Network Frequency : 50/60 Hz
  • Wire Stripping Length : 14 mm top or bottom
  • Range : Multi 9
  • 9 Mm Pitches : 4
  • Suitability For Isolation : yes EN/IEC 60947-2
  • Network Type : AC || DC
  • Contact Position Indicator : yes
  • Magnetic Tripping Limit : 8.5 x In +/- 20 % AC || 12 x In +/- 20 % DC
  • Device Short Name : C60L
  • Overvoltage Category : IV
  • Mounting Mode : clip-on
  • Product Certifications : EAC || CCC
  • Mechanical Durability : 20000 cycles
  • Number Of Protected Poles : 2
  • Standards : EN/IEC 60947-2
  • Ambient Air Temperature For Operation : -30-70 °C
  • Curve Code : C
  • Maximum Depth : 72 mm
  • Net Weight : 0.24 kg
  • Breaking Capacity : 50 kA Icu 240 V AC 50/60 Hz between phases EN/IEC 60947-2 || 25 kA Icu 415 V AC 50/60 Hz between phases EN/IEC 60947-2 || 20 kA Icu 440 V AC 50/60 Hz between phases EN/IEC 60947-2 || 30 kA Icu <= 125 V DC 50/60 Hz EN/IEC 60947-2
  • Provision For Padlocking : padlockable
  • Heat Dissipation : 4.4-4.4 W 415 V - 3 A
  • Ip Degree Of Protection : IP20IEC 60529 || IP40 modular enclosure)IEC 60529