Schneider Electric at Mayer

Multi9 - C60H - MCB - 1P - 10 A - C Curve - 240 V - 15 kA

10A 1P CB

SQDM9F14110 M9F14110 785901512479
124.60 / EA
  • Amperage: 10 A
  • Certifications: CCC, EAC
  • Country of Origin: France
  • Depth: 2.83 in, 72 mm
  • Height: 3.19 in, 81 mm
  • Mounting Type: Clip-On
  • Standard: EN/IEC 60947-2
  • Strip Length: 0.55 in, 14 mm
  • Voltage: 240 V, 415 V, 72 V
  • Weight: 0.12 kg, 0.26 lb
  • Width: 0.71 in, 18 mm
This Multi9 C60H is a low voltage miniature circuit breaker (MCB). It is a 1P circuit breaker with 1 protected pole, 10A rated current and C tripping curve. The rated short circuit breaking capacity goes up to 3kA at 415VAC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. Its fast closing mechanism, overvolatge resistance and high performance limitation improve its service life. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The operating frequency is 50Hz or 60Hz. The product can be clipped on a DIN rail. Its width is 2 pitches of 9mm. Pollution degree is 3. Overvoltage category is IV. The product colour is light grey (RAL7035). The dimensions are (W) 18mm x (H) 81mm x (D) 72mm. The weight is 0.12kg. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 80°C.
  • Product Description
  • Specifications
This Multi9 C60H is a low voltage miniature circuit breaker (MCB). It is a 1P circuit breaker with 1 protected pole, 10A rated current and C tripping curve. The rated short circuit breaking capacity goes up to 3kA at 415VAC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. Its fast closing mechanism, overvolatge resistance and high performance limitation improve its service life. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The operating frequency is 50Hz or 60Hz. The product can be clipped on a DIN rail. Its width is 2 pitches of 9mm. Pollution degree is 3. Overvoltage category is IV. The product colour is light grey (RAL7035). The dimensions are (W) 18mm x (H) 81mm x (D) 72mm. The weight is 0.12kg. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 80°C.
  • Offer Sustainability
    • WEEE : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Green Premium Status : Green Premium product
    • Mercury Free : Yes
    • Halogen Content Performance : Halogen free plastic parts & cables product
    • EU RoHs Directive : Compliant
  • Main
    • Curve Code : C
    • Device Application : Distribution
    • Suitability For ISOlation : Yes conforming to EN/IEC 60947-2
    • In Rated Current : 10 A 122 °F (50 °C) EN/IEC 60947-2
    • Network Type : AC || DC
    • Poles Description : 1P
    • Product Name : Multi 9 C60
    • Utilisation Category : Category A EN/IEC 60947-2
    • Trip Unit Technology : Thermal-magnetic
    • Device Short Name : C60H
    • Breaking Capacity : 20 kA Icu <= 72 V DC EN/IEC 60947-2 || 3 kA Icu 415 V AC 50/60 Hz between phase and neutral EN/IEC 60947-2 || 15 kA Icu 240 V AC 50/60 Hz between phase and neutral EN/IEC 60947-2
    • Standards : EN/IEC 60947-2
    • Product Certifications : EAC || CCC
    • Number Of Protected Poles : 1
    • Range : Multi 9
    • Product Or Component Type : Miniature circuit-breaker
  • Ordering And Shipping Details
    • GTIN : 00785901512479
    • Nbr. Of Units In Pkg. : 1
    • Discount Schedule : DE2
    • Returnability : No
    • Category : 00908 - C60N SUPPLEMENTARY PROTECTORS
    • Country Of Origin : FR
  • Environment
    • Relative Humidity : 95 % 131 °F (55 °C)
    • Tropicalisation : 2 conforming to IEC 60068-1
    • Ambient Air Temp For Storage : -40…176 °F (-40…80 °C)
    • Pollution Degree : 3 EN/IEC 60947-2
    • Overvoltage Category : IV
    • Heat Dissipation : 1.8 W 240 V - 10 A
    • Ambient Air Temp For Op : -22…158 °F (-30…70 °C)
    • IP Degree Of Protection : IP20 conforming to IEC 60529 || IP40 (modular enclosure) conforming to IEC 60529
  • Complementary
    • Earth-Leakage Protection : Separate block
    • Ue Rated Operational Voltage : 240 V AC 50/60 Hz between phase and neutral || 415 V AC 50/60 Hz between phase and neutral || <= 72 V DC
    • Mounting Mode : Clip-on
    • Local Signalling : ON/OFF indication
    • Height : 3.19 in (81 mm)
    • Provision For Padlocking : Padlockable
    • Tightening Torque : 17.70 lbf.in (2 N.m) top or bottom
    • Wire Stripping Length : 0.55 in (14 mm) top or bottom
    • Network Frequency : 50/60 Hz
    • Ui Rated Insulation Voltage : 500 V AC 50/60 Hz EN/IEC 60947-2
    • Width : 0.71 in (18 mm)
    • Contact Position Indicator : Yes
    • Control Type : Toggle
    • Uimp Rated Imp Wstd Voltage : 6 kVEN/IEC 60947-2
    • Colour : Gray
    • Electrical Durability : 10000 cycles
    • Mechanical Durability : 20000 cycles
    • 9 mm Pitches : 2
    • Magnetic Tripping Limit : 8.5 x In +/- 20 % AC || 12 x In +/- 20 % DC
    • Mounting Support : DIN rail
    • Product Weight : 0.26 lb(US) (0.12 kg)
    • Depth : 2.83 in (72 mm)
    • Ics Rated Service Breaking Cap : 7.5 kA 50 % EN/IEC 60947-2 - 240 V AC 50/60 Hz || 1.5 kA 50 % EN/IEC 60947-2 - 415 V AC 50/60 Hz || 20 kA 100 % EN/IEC 60947-2 - <= 72 V DC
    • Connections - Terminals : Tunnel type terminal top or bottom) 0.00…0.04 in² (1…25 mm²) - rigid || Tunnel type terminal top or bottom) 0.00…0.04 in² (1…25 mm²) - flexible || Tunnel type terminal top or bottom) 0.00…0.04 in² (1…25 mm²) - flexible with ferrule