Schneider Electric at Mayer

Multi 9 - C60BPR - MCB - 3P - 50 A - C Curve - 240 V - 10 kA - UL 489

Multi9 C60BPR 3P C 50A MCB

SQDM9F52350 M9F52350 785901133063
222.33 / EA
  • Certifications: CCC, CSA, IEC, UL
  • Depth: 72 mm
  • Height: 127 mm
  • Line Rated Current: 25 °C, 50 A
  • Mounting Type: Clip-On
  • Operating Temperature: -30-70 °C
  • Standard: CSA C22.2 No 5, EN/IEC 60947-2, GB 14048.2, UL 489
  • Storage Temperature: -40-80 °C
  • Width: 54 mm
This Multi9 C60BPR is a low voltage miniature circuit breaker (MCB). It is a 3P circuit breaker with 3 protected poles, 50A rated current and C tripping curve. The rated short circuit breaking capacity goes up to 10kA at 415VAC conforming to EN/IEC 60947-2 standard and 10kA at 415VAC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The product can be clipped on a DIN rail. Its width is 6 pitches of 9mm. Pollution degree is 3. The product colour is light grey (RAL7035). The dimensions are (W) 54mm x (H) 127mm x (D) 72mm. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 80°C.
  • Product Description
  • Specifications
This Multi9 C60BPR is a low voltage miniature circuit breaker (MCB). It is a 3P circuit breaker with 3 protected poles, 50A rated current and C tripping curve. The rated short circuit breaking capacity goes up to 10kA at 415VAC conforming to EN/IEC 60947-2 standard and 10kA at 415VAC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The product can be clipped on a DIN rail. Its width is 6 pitches of 9mm. Pollution degree is 3. The product colour is light grey (RAL7035). The dimensions are (W) 54mm x (H) 127mm x (D) 72mm. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 80°C.
  • Suitability For Isolation : yes EN/IEC 60947-2
  • Color : Gray
  • Control Type : toggle
  • Line Rated Current : 50 A 25 °C EN/IEC 60947-2
  • [Ics] Rated Service Breaking Capacity : 4.5 kA 75 % EN/IEC 60947-2 - 440 V AC || 7.5 kA 75 % EN/IEC 60947-2 - 415 V AC || 15 kA 75 % EN/IEC 60947-2 - 240 V AC || 4.5 kA 75 % GB 14048.2 - 440 V AC || 7.5 kA 75 % GB 14048.2 - 415 V AC || 15 kA 75 % GB 14048.2 - 240 V AC
  • Curve Code : C
  • Mounting Support : DIN rail
  • Operating Altitude : 0...6561.68 ft (0...2000 m)
  • Standards : EN/IEC 60947-2 || GB 14048.2 || UL 489 || CSA C22.2 No 5
  • Trip Unit Technology : thermal-magnetic
  • Product Certifications : IEC || CCC || CSA || UL
  • Provision For Padlocking : padlockable
  • Product Or Component Type : miniature circuit-breaker
  • Ip Degree Of Protection : IP20IEC 60529 || IP40 modular enclosure)IEC 60529
  • [Ui] Rated Insulation Voltage : 500 V AC EN/IEC 60947-2
  • Tightening Torque : 2-2 N.m top or bottom
  • Magnetic Tripping Limit : 8.5 x In +/- 20 % AC
  • Electrical Durability : 10000 cycles
  • Number Of Protected Poles : 3
  • Device Application : distribution
  • [Uimp] Rated Impulse Withstand Voltage : 6 kVEN/IEC 60947-2
  • Local Signalling : ON/OFF indication
  • Ambient Air Temperature For Storage : -40-80 °C
  • Maximum Depth : 72 mm
  • Maximum Width : 54 mm
  • Mechanical Durability : 20000 cycles
  • Relative Humidity : 95-95 % 55-55 °C
  • Product Name : Multi 9 C60
  • Network Type : AC
  • Tropicalisation : 2 IEC 60068-1
  • Pollution Degree : 3 EN/IEC 60947-2
  • Earth-Leakage Protection : without
  • Connections - Terminals : ring terminal top or bottom)
  • Device Short Name : C60BPR
  • [Ue] Rated Operational Voltage : 240 V AC 50/60 Hz || 415 V AC 50/60 Hz || 440 V AC 50/60 Hz
  • Overvoltage Category : IV
  • Breaking Capacity : 6 kA Icu 440 V AC EN/IEC 60947-2 || 10 kA Icu 415 V AC EN/IEC 60947-2 || 20 kA Icu 240 V AC EN/IEC 60947-2 || 6 kA Icu 440 V AC GB 14048.2 || 10 kA Icu 415 V AC GB 14048.2 || 20 kA Icu 240 V AC GB 14048.2 || 10 kA AIR 240 V AC UL 489 || 10 kA AIR 240 V AC CSA C22.2 No 5
  • Contact Position Indicator : yes
  • Maximum Height : 127 mm
  • Range : Multi 9
  • Mounting Mode : clip-on
  • Range Of Product : Multi 9
  • Ambient Air Temperature For Operation : -30-70 °C
  • 9 Mm Pitches : 6
  • Poles Description : 3P