Multi 9 - C60BPR - MCB - 2P - 30 A - D Curve - 480Y/277 V - 10 kA - UL 489

Multi 9 - C60BPR - MCB - 2P - 30 A - D Curve - 480Y/277 V - 10 kA - UL 489

SQDM9F53230 M9F53230 785901135654
153.66 / EA
  • Amperage: 30 A
  • Certifications: CCC, CSA, IEC, UL
  • Country of Origin: France
  • Depth: 2.83 in, 72 mm
  • Height: 127 mm, 5 in
  • Mounting Type: Clip-On
  • Standard: CSA C22.2 No 5, EN/IEC 60947-2, GB 14048.2, UL 489
  • Voltage: 240 V, 415 V, 440 V
  • Width: 1.42 in, 36 mm
This Multi9 C60BPR is a low voltage miniature circuit breaker (MCB). It is a 2P circuit breaker with 2 protected poles, 30A rated current and D tripping curve. The rated short circuit breaking capacity goes up to 10kA at 415VAC conforming to EN/IEC 60947-2 standard and 10kA at 415VAC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The product can be clipped on a DIN rail. Its width is 4 pitches of 9mm. Pollution degree is 3. The product colour is light grey (RAL7035). The dimensions are (W) 36mm x (H) 127mm x (D) 72mm. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 80°C.
  • Product Description
  • Specifications
This Multi9 C60BPR is a low voltage miniature circuit breaker (MCB). It is a 2P circuit breaker with 2 protected poles, 30A rated current and D tripping curve. The rated short circuit breaking capacity goes up to 10kA at 415VAC conforming to EN/IEC 60947-2 standard and 10kA at 415VAC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The product can be clipped on a DIN rail. Its width is 4 pitches of 9mm. Pollution degree is 3. The product colour is light grey (RAL7035). The dimensions are (W) 36mm x (H) 127mm x (D) 72mm. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 80°C.
  • Ordering And Shipping Details
    • Discount Schedule : DE2
    • GTIN : 00785901135654
    • Country Of Origin : FR
    • Returnability : Yes
    • Nbr. Of Units In Pkg. : 1
    • Category : 00949 - M9 GEN 2 CB UL489
  • Offer Sustainability
    • Green Premium Status : Green Premium product
    • Halogen Content Performance : Halogen free product
    • EU RoHs Directive : Compliant
    • Mercury Free : Yes
    • WEEE : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
  • Environment
    • Ambient Air Temp For Op : -22…158 °F (-30…70 °C)
    • Tropicalisation : 2 IEC 60068-1
    • Pollution Degree : 3 EN/IEC 60947-2
    • IP Degree Of Protection : IP20 conforming to IEC 60529 || IP40 modular enclosure)IEC 60529
    • Ambient Air Temp For Storage : -40…176 °F (-40…80 °C)
    • Operating Altitude : 0...6561.68 ft (0...2000 m)
    • Relative Humidity : 95 % 131 °F (55 °C)
  • Main
    • Device Short Name : C60BPR
    • Poles Description : 2P
    • Product Certifications : IEC || CCC || CSA || UL
    • In Rated Current : 30 A 77 °F (25 °C) EN/IEC 60947-2
    • Trip Unit Technology : Thermal-magnetic
    • Device Application : Distribution
    • Range : Multi 9
    • Network Type : AC || DC
    • Curve Code : D
    • Breaking Capacity : 6 kA Icu 440 V AC EN/IEC 60947-2 || 10 kA Icu 415 V AC EN/IEC 60947-2 || 20 kA Icu 240 V AC EN/IEC 60947-2 || 6 kA Icu 440 V AC GB 14048.2 || 10 kA Icu 415 V AC GB 14048.2 || 20 kA Icu 240 V AC GB 14048.2 || 14 kA AIR 240 V AC UL 489 || 10 kA AIR 125 V DC UL 489 || 10 kA AIR 480Y/277 V AC UL 489 || 14 kA AIR 240 V AC CSA C22.2 No 5 || 10 kA AIR 480Y/277 V AC CSA C22.2 No 5 || 10 kA AIR 125 V DC CSA C22.2 No 5
    • Product Name : Multi 9 C60
    • Number Of Protected Poles : 2
    • Suitability For ISOlation : Yes EN/IEC 60947-2
    • Standards : EN/IEC 60947-2 || GB 14048.2 || UL 489 || CSA C22.2 No 5
    • Product Or Component Type : Miniature circuit-breaker
  • Complementary
    • Control Type : Toggle
    • Local Signalling : ON/OFF indication
    • Depth : 2.83 in (72 mm)
    • Ui Rated Insulation Voltage : 500 V AC EN/IEC 60947-2
    • Ics Rated Service Breaking Cap : 4.5 kA 75 % GB 14048.2 - 240 V AC || 7.5 kA 75 % GB 14048.2 || 15 kA 75 % GB 14048.2 || 4.5 kA 75 % EN/IEC 60947-2 - 125 V DC || 7.5 kA 75 % EN/IEC 60947-2 - 440 V AC || 15 kA 75 % EN/IEC 60947-2 - 415 V AC
    • Contact Position Indicator : Yes
    • Mounting Mode : Clip-on
    • Earth-Leakage Protection : Without
    • Mechanical Durability : 20000 cycles
    • Colour : Gray
    • Tightening Torque : 17.70 lbf.in (2 N.m) top or bottom
    • Height : 5.00 in (127 mm)
    • Width : 1.42 in (36 mm)
    • Provision For Padlocking : Padlockable
    • Electrical Durability : 10000 cycles
    • Mounting Support : DIN rail
    • Uimp Rated Imp Wstd Voltage : 6 kVEN/IEC 60947-2
    • Connections - Terminals : Ring terminal top or bottom)
    • 9 mm Pitches : 4
    • Magnetic Tripping Limit : 12 x In +/- 20 % AC || 17 x In +/- 20 % DC
    • Ue Rated Operational Voltage : 240 V AC 50/60 Hz || 415 V AC 50/60 Hz || 440 V AC 50/60 Hz