Multi 9 - C60BPR - MCB - 1P - 4 A - D Curve - 277 V - 10 kA - UL 489

Multi 9 - C60BPR - MCB - 1P - 4 A - D Curve - 277 V - 10 kA - UL 489

SQDM9F53104 M9F53104 785901134046
73.73 / EA
  • Amperage: 4 A
  • Certifications: CCC, CSA, IEC, UL
  • Country of Origin: France
  • Depth: 2.83 in, 72 mm
  • Height: 127 mm, 5 in
  • Mounting Type: Clip-On
  • Standard: CSA C22.2 No 5, EN/IEC 60947-2, GB 14048.2, UL 489
  • Voltage: 240 V, 415 V, 60 V
  • Width: 0.71 in, 18 mm
This Multi9 C60BPR is a low voltage miniature circuit breaker (MCB). It is a 1P circuit breaker with 1 protected pole, 4A rated current and D tripping curve. The rated short circuit breaking capacity goes up to 3kA at 415VAC conforming to EN/IEC 60947-2 standard and 3kA at 415VAC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The product can be clipped on a DIN rail. Its width is 2 pitches of 9mm. Pollution degree is 3. The product colour is light grey (RAL7035). The dimensions are (W) 18mm x (H) 127mm x (D) 72mm. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 80°C.
  • Product Description
  • Specifications
This Multi9 C60BPR is a low voltage miniature circuit breaker (MCB). It is a 1P circuit breaker with 1 protected pole, 4A rated current and D tripping curve. The rated short circuit breaking capacity goes up to 3kA at 415VAC conforming to EN/IEC 60947-2 standard and 3kA at 415VAC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The product can be clipped on a DIN rail. Its width is 2 pitches of 9mm. Pollution degree is 3. The product colour is light grey (RAL7035). The dimensions are (W) 18mm x (H) 127mm x (D) 72mm. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 80°C.
  • Ordering And Shipping Details
    • Category : 00949 - M9 GEN 2 CB UL489
    • Country Of Origin : FR
    • Discount Schedule : DE2
    • Nbr. Of Units In Pkg. : 1
    • Returnability : Yes
    • GTIN : 00785901134046
  • Complementary
    • Depth : 2.83 in (72 mm)
    • Uimp Rated Imp Wstd Voltage : 6 kVEN/IEC 60947-2
    • Width : 0.71 in (18 mm)
    • Mounting Mode : Clip-on
    • 9 mm Pitches : 2
    • Height : 5.00 in (127 mm)
    • Ics Rated Service Breaking Cap : 2.25 kA 75 % EN/IEC 60947-2 - 415 V AC || 7.5 kA 75 % EN/IEC 60947-2 - 240 V AC || 2.25 kA 75 % GB 14048.2 - 415 V AC || 7.5 kA 75 % GB 14048.2 - 240 V AC || 15 kA 75 % GB 14048.2 - 60 V DC || 15 kA 75 % EN/IEC 60947-2 - 60 V DC
    • Earth-Leakage Protection : Without
    • Ui Rated Insulation Voltage : 500 V AC EN/IEC 60947-2
    • Mechanical Durability : 20000 cycles
    • Connections - Terminals : Ring terminal top or bottom)
    • Mounting Support : DIN rail
    • Provision For Padlocking : Padlockable
    • Tightening Torque : 17.70 lbf.in (2 N.m) top or bottom
    • Contact Position Indicator : Yes
    • Electrical Durability : 10000 cycles
    • Ue Rated Operational Voltage : 240 V AC 50/60 Hz || 415 V AC 50/60 Hz || 60 V DC
    • Control Type : Toggle
    • Colour : Gray
    • Magnetic Tripping Limit : 12 x In +/- 20 % AC || 17 x In +/- 20 % DC
    • Local Signalling : ON/OFF indication
  • Offer Sustainability
    • WEEE : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Halogen Content Performance : Halogen free product
    • EU RoHs Directive : Compliant
    • Green Premium Status : Green Premium product
    • Mercury Free : Yes
  • Environment
    • Ambient Air Temp For Op : -22…158 °F (-30…70 °C)
    • Operating Altitude : 0...6561.68 ft (0...2000 m)
    • Tropicalisation : 2 IEC 60068-1
    • Pollution Degree : 3 EN/IEC 60947-2
    • Ambient Air Temp For Storage : -40…176 °F (-40…80 °C)
    • Relative Humidity : 95 % 131 °F (55 °C)
    • IP Degree Of Protection : IP20 conforming to IEC 60529 || IP40 modular enclosure)IEC 60529
    • Overvoltage Category : IV
  • Main
    • Device Short Name : C60BPR
    • Product Or Component Type : Miniature circuit-breaker
    • Network Type : AC || DC
    • Device Application : Distribution
    • Number Of Protected Poles : 1
    • Poles Description : 1P
    • Suitability For ISOlation : Yes EN/IEC 60947-2
    • Product Certifications : IEC || CCC || CSA || UL
    • Trip Unit Technology : Thermal-magnetic
    • Standards : EN/IEC 60947-2 || GB 14048.2 || UL 489 || CSA C22.2 No 5
    • Range : Multi 9
    • In Rated Current : 4 A 77 °F (25 °C) EN/IEC 60947-2
    • Product Name : Multi 9 C60
    • Breaking Capacity : 3 kA Icu 415 V AC EN/IEC 60947-2 || 10 kA Icu 240 V AC EN/IEC 60947-2 || 20 kA Icu 60 V DC EN/IEC 60947-2 || 3 kA Icu 415 V AC GB 14048.2 || 10 kA Icu 240 V AC GB 14048.2 || 20 kA Icu 60 V DC GB 14048.2 || 10 kA AIR 277 V AC UL 489 || 14 kA AIR 240 V AC UL 489 || 14 kA AIR 120 V AC UL 489 || 10 kA AIR 60 V DC UL 489 || 10 kA AIR 277 V AC CSA C22.2 No 5 || 14 kA AIR 240 V AC CSA C22.2 No 5 || 14 kA AIR 120 V AC CSA C22.2 No 5 || 10 kA AIR 60 V DC CSA C22.2 No 5
    • Curve Code : D