Schneider Electric at Mayer

Multi 9 - C60BPR - MCB - 1P - 20 A - D Curve - 277 V - 10 kA - UL 489

Multi9 C60BPR 1P D 20A MCB

SQDM9F53120 M9F53120 785901134190
68.67 / EA
  • Certifications: CCC, CSA, IEC, UL
  • Depth: 72 mm
  • Height: 127 mm
  • Line Rated Current: 20 A, 25 °C
  • Mounting Type: Clip-On
  • Operating Temperature: -30-70 °C
  • Standard: CSA C22.2 No 5, EN/IEC 60947-2, GB 14048.2, UL 489
  • Storage Temperature: -40-80 °C
  • Width: 18 mm
This Multi9 C60BPR is a low voltage miniature circuit breaker (MCB). It is a 1P circuit breaker with 1 protected pole, 20A rated current and D tripping curve. The rated short circuit breaking capacity goes up to 3kA at 415VAC conforming to EN/IEC 60947-2 standard and 3kA at 415VAC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The product can be clipped on a DIN rail. Its width is 2 pitches of 9mm. Pollution degree is 3. The product colour is light grey (RAL7035). The dimensions are (W) 18mm x (H) 127mm x (D) 72mm. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 80°C.
  • Product Description
  • Specifications
This Multi9 C60BPR is a low voltage miniature circuit breaker (MCB). It is a 1P circuit breaker with 1 protected pole, 20A rated current and D tripping curve. The rated short circuit breaking capacity goes up to 3kA at 415VAC conforming to EN/IEC 60947-2 standard and 3kA at 415VAC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The product can be clipped on a DIN rail. Its width is 2 pitches of 9mm. Pollution degree is 3. The product colour is light grey (RAL7035). The dimensions are (W) 18mm x (H) 127mm x (D) 72mm. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 80°C.
  • [Uimp] Rated Impulse Withstand Voltage : 6 kVEN/IEC 60947-2
  • Earth-Leakage Protection : without
  • Breaking Capacity : 3 kA Icu 415 V AC EN/IEC 60947-2 || 10 kA Icu 240 V AC EN/IEC 60947-2 || 20 kA Icu 60 V DC EN/IEC 60947-2 || 3 kA Icu 415 V AC GB 14048.2 || 10 kA Icu 240 V AC GB 14048.2 || 20 kA Icu 60 V DC GB 14048.2 || 10 kA AIR 277 V AC UL 489 || 14 kA AIR 240 V AC UL 489 || 14 kA AIR 120 V AC UL 489 || 10 kA AIR 60 V DC UL 489 || 10 kA AIR 277 V AC CSA C22.2 No 5 || 14 kA AIR 240 V AC CSA C22.2 No 5 || 14 kA AIR 120 V AC CSA C22.2 No 5 || 10 kA AIR 60 V DC CSA C22.2 No 5
  • [Ui] Rated Insulation Voltage : 500 V AC EN/IEC 60947-2
  • Ip Degree Of Protection : IP20IEC 60529 || IP40 modular enclosure)IEC 60529
  • Overvoltage Category : IV
  • Range : Multi 9
  • [Ue] Rated Operational Voltage : 240 V AC 50/60 Hz || 415 V AC 50/60 Hz || 60 V DC
  • Control Type : toggle
  • Poles Description : 1P
  • Product Name : Multi 9 C60
  • Trip Unit Technology : thermal-magnetic
  • Product Or Component Type : miniature circuit-breaker
  • Magnetic Tripping Limit : 12 x In +/- 20 % AC || 17 x In +/- 20 % DC
  • Range Of Product : Multi 9
  • Device Short Name : C60BPR
  • Number Of Protected Poles : 1
  • Maximum Width : 18 mm
  • Line Rated Current : 20 A 25 °C EN/IEC 60947-2
  • Curve Code : D
  • [Ics] Rated Service Breaking Capacity : 2.25 kA 75 % EN/IEC 60947-2 - 415 V AC || 7.5 kA 75 % EN/IEC 60947-2 - 240 V AC || 2.25 kA 75 % GB 14048.2 - 415 V AC || 7.5 kA 75 % GB 14048.2 - 240 V AC || 15 kA 75 % GB 14048.2 - 60 V DC || 15 kA 75 % EN/IEC 60947-2 - 60 V DC
  • Network Type : AC || DC
  • Contact Position Indicator : yes
  • Relative Humidity : 95-95 % 55-55 °C
  • Local Signalling : ON/OFF indication
  • Color : Gray
  • Provision For Padlocking : padlockable
  • Tropicalisation : 2 IEC 60068-1
  • Maximum Height : 127 mm
  • Suitability For Isolation : yes EN/IEC 60947-2
  • Mounting Mode : clip-on
  • Product Certifications : IEC || CCC || CSA || UL
  • Tightening Torque : 2-2 N.m top or bottom
  • 9 Mm Pitches : 2
  • Mechanical Durability : 20000 cycles
  • Pollution Degree : 3 EN/IEC 60947-2
  • Maximum Depth : 72 mm
  • Standards : EN/IEC 60947-2 || GB 14048.2 || UL 489 || CSA C22.2 No 5
  • Connections - Terminals : ring terminal top or bottom)
  • Ambient Air Temperature For Operation : -30-70 °C
  • Ambient Air Temperature For Storage : -40-80 °C
  • Device Application : distribution
  • Electrical Durability : 10000 cycles
  • Mounting Support : DIN rail
  • Operating Altitude : 0...6561.68 ft (0...2000 m)