Schneider Electric at Mayer

Multi 9 - C60BP - MCB - 3P - 20 A - C Curve - 480Y/277 V - 10 kA - UL 489

MULTI9 C60BP 3P C 20A MCB

SQDM9F42320 M9F42320 785901692119
200.37 / EA
  • Certifications: CCC, CSA, IEC, UL
  • Depth: 72 mm
  • Height: 103 mm
  • Line Rated Current: 20 A, 25 °C
  • Mounting Type: Clip-On
  • Operating Temperature: -30-70 °C
  • Standard: CSA C22.2 No 5, EN/IEC 60947-2, GB 14048.2, UL 489
  • Storage Temperature: -40-80 °C
  • Strip Length: 14 mm
  • Width: 54 mm
This Multi9 C60BP is a low voltage miniature circuit breaker (MCB). It is a 3P circuit breaker with 3 protected poles, 20A rated current and C tripping curve. The rated short circuit breaking capacity goes up to 10kA at 415VAC conforming to EN/IEC 60947-2 standard and 10kA at 415VAC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The product can be clipped on a DIN rail. Its width is 6 pitches of 9mm. Pollution degree is 3. The product colour is light grey (RAL7035). The dimensions are (W) 54mm x (H) 103mm x (D) 72mm. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 80°C.
  • Product Description
  • Specifications
This Multi9 C60BP is a low voltage miniature circuit breaker (MCB). It is a 3P circuit breaker with 3 protected poles, 20A rated current and C tripping curve. The rated short circuit breaking capacity goes up to 10kA at 415VAC conforming to EN/IEC 60947-2 standard and 10kA at 415VAC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The product can be clipped on a DIN rail. Its width is 6 pitches of 9mm. Pollution degree is 3. The product colour is light grey (RAL7035). The dimensions are (W) 54mm x (H) 103mm x (D) 72mm. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 80°C.
  • Product Name : Multi 9 C60
  • Product Certifications : IEC || CCC || CSA || UL
  • Line Rated Current : 20 A 25 °C EN/IEC 60947-2
  • Ambient Air Temperature For Operation : -30-70 °C
  • Breaking Capacity : 6 kA Icu 440 V AC EN/IEC 60947-2 || 10 kA Icu 415 V AC EN/IEC 60947-2 || 20 kA Icu 240 V AC EN/IEC 60947-2 || 6 kA Icu 440 V AC GB 14048.2 || 10 kA Icu 415 V AC GB 14048.2 || 20 kA Icu 240 V AC GB 14048.2 || 14 kA AIR 240 V AC UL 489 || 10 kA AIR 480Y/277 V AC UL 489 || 14 kA AIR 240 V AC CSA C22.2 No 5 || 10 kA AIR 480Y/277 V AC CSA C22.2 No 5
  • Tropicalisation : 2 IEC 60068-1
  • Electrical Durability : 10000 cycles
  • Mechanical Durability : 20000 cycles
  • Wire Stripping Length : 14 mm top or bottom
  • Number Of Protected Poles : 3
  • Control Type : toggle
  • Color : Gray
  • Device Short Name : C60BP
  • Pollution Degree : 3 EN/IEC 60947-2
  • [Uimp] Rated Impulse Withstand Voltage : 6 kVEN/IEC 60947-2
  • Local Signalling : ON/OFF indication
  • Maximum Depth : 72 mm
  • Product Or Component Type : miniature circuit-breaker
  • Device Application : distribution
  • [Ics] Rated Service Breaking Capacity : 4.5 kA 75 % EN/IEC 60947-2 - 440 V AC || 7.5 kA 75 % EN/IEC 60947-2 - 415 V AC || 15 kA 75 % EN/IEC 60947-2 - 240 V AC || 4.5 kA 75 % GB 14048.2 - 440 V AC || 7.5 kA 75 % GB 14048.2 - 415 V AC || 15 kA 75 % GB 14048.2 - 240 V AC
  • Trip Unit Technology : thermal-magnetic
  • Standards : EN/IEC 60947-2 || GB 14048.2 || UL 489 || CSA C22.2 No 5
  • [Ue] Rated Operational Voltage : 240 V AC 50/60 Hz || 415 V AC 50/60 Hz || 440 V AC 50/60 Hz
  • Network Type : AC
  • Relative Humidity : 95-95 % 55-55 °C
  • Curve Code : C
  • Ip Degree Of Protection : IP20IEC 60529 || IP40 modular enclosure)IEC 60529
  • Range Of Product : Multi 9
  • Connections - Terminals : tunnel type terminal top or bottom) 1-25 mm² AWG 18...AWG 8) - rigid || tunnel type terminal top or bottom) 1-16 mm² AWG 18...AWG 8) - flexible with ferrule || tunnel type terminal top or bottom) 1-16 mm² AWG 18...AWG 8) - flexible
  • Ambient Air Temperature For Storage : -40-80 °C
  • Suitability For Isolation : yes EN/IEC 60947-2
  • [Ui] Rated Insulation Voltage : 500 V AC EN/IEC 60947-2
  • Magnetic Tripping Limit : 8.5 x In +/- 20 % AC
  • Poles Description : 3P
  • Contact Position Indicator : yes
  • Mounting Support : DIN rail
  • Maximum Width : 54 mm
  • Range : Multi 9
  • 9 Mm Pitches : 6
  • Tightening Torque : 2.5-2.5 N.m top or bottom
  • Maximum Height : 103 mm
  • Operating Altitude : 0...6561.68 ft (0...2000 m)
  • Mounting Mode : clip-on
  • Provision For Padlocking : padlockable
  • Earth-Leakage Protection : without