Schneider Electric at Mayer

dual function relay, Harmony Timer Relays, 8A, 1CO, 1s..100h, on delay, 24V DC or 24...240V AC DC

ON-DELAY TIMER W/CONTROL SIGNA

SQDRE17RAMU RE17RAMU 3606480552670
61.58 / EA
http://schema.org/OutOfStock
  • Country of Origin: Indonesia
  • Depth: 72 mm
  • Dielectric Strength: 1 mA, 2.5 kV, 50 Hz
  • Height: 90 mm
  • Input Voltage: 10 V
  • Net Weight: 0.07 kg
  • Weight: 0.07 kg
  • Width: 17.5 mm
This Harmony RE17R timing relay can be set between 0.1 seconds and 100 hours, has an output rating of 8A, is 17.5mm wide and can be supplied with 24 V DC, 24 to 240 V AC. It also has 1 changeover contact SPDT (single pole double throw). It has one of market slimmest form-factors, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 1-pole DIN device. It also offers a sealable cover, simple and precise settings with rotary trimmers. This timer offers pause and summation control signals. Single function timer for a simple integration in hard-wired logic schematics, ideal for refurbishment of old installations without using a PLC. 0 0 0 0 0 0 0 0 0 0 0 0 0
QTY
  • Product Description
  • Features
  • Specifications
This Harmony RE17R timing relay can be set between 0.1 seconds and 100 hours, has an output rating of 8A, is 17.5mm wide and can be supplied with 24 V DC, 24 to 240 V AC. It also has 1 changeover contact SPDT (single pole double throw). It has one of market slimmest form-factors, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 1-pole DIN device. It also offers a sealable cover, simple and precise settings with rotary trimmers. This timer offers pause and summation control signals. Single function timer for a simple integration in hard-wired logic schematics, ideal for refurbishment of old installations without using a PLC. 0 0 0 0 0 0 0 0 0 0 0 0 0
  • Prop 65
    • WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
  • Complementary
    • Number Of Functions : 2
    • Creepage Distance : 4 kV/3 IEC 60664-1
    • Maximum Power Consumption In W : 0.6 W 24 V DC
    • Maximum Switching Current : 8 A AC/DC
    • Dielectric Strength : 2.5 kV 1 mA/1 minute 50 Hz IEC 61812-1
    • Function Available : A- Power on-delay relay-1 C/O || At- Power on-delay relay w/ pause/summation (Y1)-1 C/O
    • Reset Time : 120 ms on de-energisation typical
    • Operating Rate In Hz : 10 Hz
    • Net Weight : 0.07 kg
    • Mounting Position : any position in relation to normal vertical mounting plane
    • Voltage Drift : +/- 0.2 %/V
    • Connections - Terminals : screw terminals, 1 x 0.5...1 x 3.3 mm² AWG 20...AWG 12) solid without cable end || screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end || screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 14) flexible with cable end || screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end
    • Contacts Type And Composition : 1 C/O
    • Local Signalling : LED indicator on steady: relay energised, no timing in progress || LED indicator 80 % ON and 20 % OFF flashing: timing in progress || LED indicator 5 % ON and 95 % OFF pulsing: relay de-energised, no timing in progress (except function Di-D, Li-L)
    • Input Voltage : 10 V
    • Mounting Support : 35 mm DIN rail conforming to IEC 60715
    • Breaking Capacity : 2000 VA
    • Housing Material : self-extinguishing
    • Impulse Duration : 100 ms with load in parallel typical || 30 ms typical
    • Time Delay Type : A, At
    • Depth : 72 mm
    • Supply Frequency : 50...60 Hz +/- 5 %
    • Repeat Accuracy : +/- 0.5 % IEC 61812-1
    • Safety Reliability Data : B10d = 270000 || MTTFd = 296.8 years
    • Setting Accuracy Of Time Delay : +/- 10 % of full scale 25 °C IEC 61812-1
    • Height : 90 mm
    • Maximum Delay Response : 100 ms
    • Insulation Resistance : 100 MOhm 500 V DC IEC 60664-1
    • Contacts Material : cadmium free
    • Power Consumption In Va : 0-32 VA 240 V AC
    • Marking : CE
    • Voltage Range : 0.85...1.1 Us
    • Control Type : without test button
    • Maximum Switching Voltage : 250 V AC
    • Functionality : on-delay timing
    • [Us] Rated Supply Voltage : 24...240 V AC 50/60 Hz || 24 V DC
    • Temperature Drift : +/- 0.05 %/°C
    • Minimum Switching Current : 10 mA 5 V DC
    • Electrical Durability : 100000 cycles resistive 8 A 250 V AC
    • Mechanical Durability : 10000000 cycles
    • Compatibility Code : RE17
    • On-Load Factor : 100 %
    • [Uimp] Rated Impulse Withstand Voltage : 5 kV 1.2/50 µs
    • Tightening Torque : 0.6-1 N.m IEC 60947-1
  • Environment
    • Product Certifications : CSA || cULus || GL
    • Standards : 2006/95/EC || 2004/108/EC || IEC 61812-1 || IEC 61000-6-3 || IEC 61000-6-1 || IEC 61000-6-4 || IEC 61000-6-2
    • Shock Resistance : 15 gn 11 ms IEC 60068-2-27
    • Vibration Resistance : 20 m/s² (f= 10-150 Hz) conforming to IEC 60068-2-6
    • Ambient Air Temperature For Operation : -20-60 °C
    • Immunity To Microbreaks : 20 ms
    • Electromagnetic Compatibility : electrostatic discharge immunity test 6 kV in contact) level 3 IEC 61000-4-2 || electrostatic discharge immunity test 8 kV in air) level 3 IEC 61000-4-2 || susceptibility to electromagnetic fields 10 V/m 80 MHz to 1 GHz) level 3 IEC 61000-4-3 || electrical fast transient/burst immunity test 1 kV capacitive connecting clip) level 3 IEC 61000-4-4 || electrical fast transient/burst immunity test 2 kV direct) level 3 IEC 61000-4-4 || 1.2/50 µs shock waves immunity test 1 kV differential mode) level 3 IEC 61000-4-5 || 1.2/50 µs shock waves immunity test 2 kV common mode) level 3 IEC 61000-4-5 || conducted RF disturbances 10 V 0.15...80 MHz) level 3 IEC 61000-4-6 || voltage dips and interruptions immunity test 0 % 1 cycle) IEC 61000-4-11 || voltage dips and interruptions immunity test 70 % 25/30 cycles) IEC 61000-4-11 || conducted and radiated emissionsclass B EN 55022
    • Ip Degree Of Protection : IP20 IEC 60529 terminal block) || IP40 IEC 60529 housing) || IP50 IEC 60529 front panel)
    • Ambient Air Temperature For Storage : -30-60 °C
    • Relative Humidity : 93-93 % without condensation IEC 60068-2-30
  • Specifications
    • Country of Origin : Indonesia
    • Height : 90 mm
    • Weight : 0.07 kg
    • Product Or Component Type : modular timing relay
    • Time Delay Range : 1...10 min || 10...100 h || 0.1...1 s || 6...60 s || 6...60 min || 1...10 s || 1...10 h
    • Nominal Output Current : 8 A
    • Width : 17.5 mm
    • Discrete Output Type : relay
    • Range Of Product : Harmony Timer Relays
    • Time Delay Type : power on-delay
    • Device Short Name : RE17R
  • Environmental data
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Minimum Percentage Of Recycled Plastic Content : 0
    • Take-Back : No
    • Carbon Footprint (Kg Co2 Eq, Total Life Cycle) : 15.3703536024
    • Packaging Made With Recycled Cardboard : Yes
    • Environmental Disclosure : ENVPEP121117EN
    • Packaging Without Single Use Plastic : Yes
    • Scip Number : 7bdc2711-0ad2-427c-8ece-532c5e9f09d7
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
    • Circularity Profile : ENVEOLI121113EN