Schneider Electric at Mayer

transformer protection relay, PowerLogic P3T32 6CT 3Io ringlug 4VT 6DI 10DO 110-230V DI110V 3BIO 6ARC RS485 RJ45 ANSI

transformer protection relay, PowerLogic P3T32 6CT 3Io ringlug 4VT 6DI 10DO 110-230V DI110V 3BIO 6ARC RS485 RJ45 ANSI

SQDREL52131 REL52131 3606481465658
5824.23 / EA
http://schema.org/OutOfStock
  • Depth: 230 mm
  • Height: 176 mm
  • Mounting Type: Flush, Flush Mounting
  • Net Weight: 4.2 kg
  • Number of Outputs: 1, 10
  • Storage Temperature: -40-70 °C
  • Warranty Length: 10 yr, 2 yr
  • Width: 270 mm
QTY
  • Specifications
  • Specifications
    • Analogue Output Number : 0
    • Input Type : 6 1/5 A CT phase current || 2 5/1 A CT residual current || 1 1/0.2 A CT residual current || 4 100 V/110 V VT voltage
    • Range Of Product : PowerLogic P3
    • Connections - Terminals : screw removable (digital input/output) || ring lugs fixed (current transformer) || pin removable (voltage transformer)
    • Network And Machine Diagnosis Type : event recording || disturbance recording || tripping context
    • Device Mounting : flush
    • Number Of Outputs : 10 DO || 1 watchdog
    • Protection Type : overfluxing (V/Hz) 24 || synchro-check 25 || undervoltage 27 || directional active underpower 32 || negative sequence overcurrent 46 || thermal overload protection 49 || earth fault overcurrent 50N/51N || phase overcurrent 50/51 || breaker failure 50BF || switch ON to fault (SOTF) || capacitor bank unbalance 51C || capacitor overvoltage 59C || overvoltage 59 || earth fault overvoltage 59N || restricted earth fault 64REF || directional phase overcurrent 67 || directional earth fault 67N || magnetising inrush detection 68F2 || H5 detection 68H5 || underfrequency 81/81N || rate of change of frequency 81R || lockout relay 86 || two-winding transformer differential 87T || programmable stages 99 8-8 || programmable curve || cold load pick-up || CT supervision 60 || VT supervision 60FL
    • Relay Application : transformer
    • Communication Port Protocol : IEC 61850 ed. 1 || IEC 61850 ed. 2 || IEC 60870-5-101 || DNP3 TCP || Modbus TCP || EtherNet/IP || IEC 60870-5-103 || DNP3 || Modbus RTU || DeviceNet || SPAbus
    • Product Or Component Type : protection relay
    • Single Line Diagram : 3 controlled + 5 displayed
    • Mounting Case Size : 30TE
    • Monitoring Function : trip circuit supervision 74 || circuit breaker monitoring || relay self-monitoring
    • Analogue Input Number : 0
    • Relay Type : differential current relay
    • Mounting Mode : flush mounting
    • Control Type : switchgear control and monitoring || programmable switchgear interlocking || local control on single-line diagram || local control with I/O keys || local/remote control || 2 function keys || mobile application with Easergy SmartApp || web-server || programmable logic
    • Digital Input Number : 6
    • Setting : 4
    • Integrated Connection Type : front USB port 1 || rear RJ45 1 || rear RS485 1
    • Cybersecurity : password protection || port hardening
    • Number Of Sensors : 0 temperature sensor(s) || 0 arc sensor(s)
    • Switchgear Diagnosis Type : CT/VT supervision || trip circuit supervision TCS
    • Arc Flash Protection : yes
    • Type Of Measurement : current 3-phase || current zero sequence || current positive sequence || current negative sequence || current ratio of negative and positive || voltage phase to earth || voltage phase to phase || voltage zero sequence || voltage positive sequence || voltage negative sequence || voltage ratio of negative and positive || short circuit fault reactance || fault location current || earth fault reactance || frequency || active power || RMS active power || reactive power || RMS reactive power || apparent power || RMS apparent power || active energy || reactive energy || cos φ || tan φ || power angle || power factor || voltage phasor diagram view || current phasor diagram view || current 2nd, 15th harmonics with THD || voltage 2nd, 15th harmonics with THD || condition monitoring CB wear || voltage interruption
    • Device Short Name : P3T32-CBG1A-DA1FA-BBAAB
    • [Us] Rated Supply Voltage : 48...230 V AC/DC
  • Environment
    • Mechanical Robustness : vibrations class II) IEC 60255-21-1 || vibrationsFc IEC 60068-2-6 || shocks class II) IEC 60255-21-2 || shocksEa IEC 60068-2-27 || seismic tests method A class II) IEC 60255-21-3
    • Ambient Air Temperature For Operation : -40-65 °C
    • Environmental Characteristic : exposure to dry heat Bd EN/IEC 60068-2-2 || exposure to cold Ad EN/IEC 60068-2-1 || exposure to damp heat in service Db EN/IEC 60068-2-30 || exposure to damp heat in service Cab EN/IEC 60068-2-78
    • Ip Degree Of Protection : IP54 front IEC 60529
    • Electromagnetic Compatibility : emission tests IEC/EN 60255-26 ed. 3 || emission tests class A CISPR 11 || emission tests class A CISPR 22 || EMC immunity IEC/EN 60255-26 ed. 3 || EMC immunity EN/IEC 61000-4-18 || EMC immunity IEC 60255-22-1 || EMC immunity level 4 EN/IEC 61000-4-2 || EMC immunity IEC 60255-22-2 || EMC immunity level 3 EN/IEC 61000-4-3 || EMC immunity IEC 60255-22-3 || EMC immunity level 4 EN/IEC 61000-4-4 || EMC immunity IEC 60255-22-4 || EMC immunity level 3 EN/IEC 61000-4-5 || EMC immunity IEC 60255-22-5 || EMC immunity level 3 EN/IEC 61000-4-6 || EMC immunity IEC 60255-22-6 || EMC immunity EN/IEC 61000-4-8 || EMC immunity level 5 EN/IEC 61000-4-9 || EMC immunity EN/IEC 61000-4-29 || EMC immunity EN/IEC 61000-4-11 || EMC immunity EN/IEC 61000-4-17 || EMC immunity IEC 60255-27 || EMC immunity class III IEC 60255-5 || EMC immunity EN/IEC 60255-1
    • Ambient Air Temperature For Storage : -40-70 °C
    • Relative Humidity : 0-95 %, without condensation
    • Protective Treatment : conformal coating
    • Operating Altitude : 6561.68 ft (2000 m)
  • Complementary
    • Number Of Key : 2 customizable
    • Local Signalling : 2 LEDs || 16 LEDs programmable
    • Depth : 230 mm
    • Operating Threshold : 110 V AC/DC
    • Time Synchronisation Protocol : SNTP
    • Width : 270 mm
    • Height : 176 mm
    • Display Type : LCD 128 x 128 pixels with single line diagram || LCD 128 x 128 pixels with ANSI symbols
    • Net Weight : 4.2 kg maximum
    • Software Name : eSetup Easergy Pro virtual simulation test || Easergy SmartApp
    • Web Server : embedded HTTP server
  • Contractual warranty
    • Warranty : up to 10 years (Standard warranty 2 years. Please check with your local SE representative for extended warranty availability and conditions)