Schneider Electric at Mayer

discrete I/O module Modicon Quantum - 16 I - 115 V AC - 8 O solid state

DISCRETE AC IN/OUT 115VAC

SQD140DAM59000 140DAM59000 785901013952
1478.35 / EA
http://schema.org/OutOfStock
  • Certifications: CUL
  • Impedance: 14400 ohm
  • Net Weight: 0.45 kg
  • Standard: CSA C22.2 No 142, FM Class 1 Division 2, UL 508
  • Warranty Length: 18 mth
QTY
  • Specifications
  • Specifications
    • Range Of Product : Modicon Quantum automation platform
    • Product Or Component Type : mixed discrete I/O module
    • Discrete I/O Number : 24
  • Contractual warranty
    • Warranty : 18 months
  • Complementary
    • Power Dissipation : 5.5 W + (1.1 x total module load current)
    • Discrete Output Type : solid state
    • Maximum Load Current : <= 4 A per point || <= 8 A per group || <= 8 A per module
    • Discrete Input Voltage : 115 V AC
    • Maximum Voltage Drop : <1.5 V
    • Isolation Between Channels And Bus : 1780 Vrms for 1 minute
    • Discrete Output Number : 8 2 groups of 4
    • Current State 1 Guaranteed : <= 11 mA 50 Hz || <= 13.2 mA 60 Hz
    • Network Frequency Limits : 47-63 Hz
    • Marking : CE
    • Current State 0 Guaranteed : <= 0.5 mA
    • Response Time : 4.9...0.75 ms at state 0 to state 1 || 7.3...12.3 ms at state 1 to state 0
    • Input Voltage Limits : 156 V during 10 s || 200 V during one cycle || 132 V typical
    • Isolation Between Group : 1000 Vrms for 1 minute
    • Net Weight : 0.45 kg
    • Voltage State 0 Guaranteed : 0...20 V
    • Output Voltage Limits : 156 V AC during 10 s || 200 V AC during 1 cycle || 85...132 V typical AC typical
    • Maximum Leakage Current : 2.1 mA 115 V AC input circuit || 2 mA output circuit
    • External Power Requirement : 85...132 V AC for output circuit
    • Voltage State 1 Guaranteed : 79...132 V 60 Hz || 85...132 V 50 Hz
    • Discrete Output Voltage : 115 V
    • Absolute Maximum Output : 20 A 2 cycles per point || 26 A 3 cycles per group || 30 A 1 cycle per point || 30 A 2 cycles per group || 45 A 1 cycle per group || 10 A 3 cycles per point
    • Bus Current Requirement : 250 mA
    • Addressing Requirement : 1 input word || 0.5 output word
    • Fault Indication : loss of field power on output || blown fuse on output
    • Local Signalling : for bus communication is present (Active) 1 LED (green) || for no voltage in output and input (F) 1 LED (red) || for output is turned on 2 LEDs (green) || for fault detected on the input point 2 LEDs (red) || for fault detected on the output point 2 LEDs (red)
    • Dv/Dt : 400 V/µs
    • Protection Type : on output by RC filter || internal output protection by 5 A fuse per group
    • Minimum Load : 5 mA
    • Discrete Input Number : 16 2 groups of 8
    • Input Impedance : 14400 Ohm capacitive
    • Response Time On Output : <= 0.5 ms at state 0 to state 1 || <= 0.5 ms at state 1 to state 0
  • Offer Sustainability
    • Rohs Exemption Information : Yes
    • Mercury Free : Yes
    • Environmental Disclosure : ENVPEP071201EN
    • Sustainable Offer Status : Green Premium product
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
    • Reach Free Of Svhc : Yes
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • China Rohs Regulation : X
    • Circularity Profile : ENVEOLI0712001EN
    • Eu Rohs Directive : Pro-active compliance (Product out of EU RoHS legal scope)
  • Environment
    • Product Certifications : cUL
    • Ambient Air Temperature For Operation : 0-60 °C
    • Resistance To Electromagnetic Fields : 10 V/m 80-1000 MHz IEC 801-3
    • Standards : FM Class 1 Division 2 || UL 508 || CSA C22.2 No 142
    • Ambient Air Temperature For Storage : -40-85 °C
    • Relative Humidity : 95-95 % without condensation
    • Resistance To Electrostatic Discharge : 4 kV contact IEC 801-2 || 8 kV on air IEC 801-2
    • Operating Altitude : <= 16404.2 ft (5000 m)