• Specifications
  • Environment
    • Product Certifications : UL || CSA || TÜV
    • Ambient Air Temperature For Operation : -25-55 °C
    • Standards : EN/IEC 60947-5-1 || EN/IEC 60204-1
    • Ip Degree Of Protection : IP20 terminals)EN/IEC 60529 || IP40 enclosure)EN/IEC 60529
    • Ambient Air Temperature For Storage : -25-70 °C
  • Contractual warranty
    • Warranty : 18 months
  • Offer Sustainability
    • Rohs Exemption Information : Yes
    • Mercury Free : Yes
    • Environmental Disclosure : ENVPEP1406024EN
    • Sustainable Offer Status : Green Premium product
    • Pvc Free : Yes
    • Toxic Heavy Metal Free : Yes
    • Reach Regulation : Reference contains Substances of Very High Concern above the threshold
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • China Rohs Regulation : X
    • Circularity Profile : ENVEOLI1406024EN
    • Eu Rohs Directive : Pro-active compliance (Product out of EU RoHS legal scope)
  • Complementary
    • [Ith] Conventional Free Air Thermal Current : 24 A relay output
    • Mounting Support : 35 mm symmetrical DIN rail
    • Output Thermal Current : 6 A per relay relay output
    • Minimum Output Voltage : 5 V relay output
    • Minimum Output Current : 10 mA relay output
    • Associated Fuse Rating : 6 A gG relay output EN/IEC 60947-5-1, DIN VDE 0660 part 200
    • [Uimp] Rated Impulse Withstand Voltage : 4 kV III EN/IEC 60947-5-1, DIN VDE 0110 parts 1 & 2
    • Net Weight : 0.65 kg
    • Connections - Terminals : captive screw clamp terminals, 1 x 0.2...1 x 2.5 mm² solid without cable end || captive screw clamp terminals, 1 x 0.2...1 x 2.5 mm² flexible without cable end || captive screw clamp terminals, 1 x 0.25...1 x 2.5 mm² flexible with cable end, without bezel || captive screw clamp terminals, 1 x 0.25...1 x 1.5 mm² flexible with cable end, with bezel || captive screw clamp terminals, 2 x 0.2...2 x 1 mm² solid without cable end || captive screw clamp terminals, 2 x 0.2...2 x 1 mm² flexible without cable end || captive screw clamp terminals, 2 x 0.25...2 x 1 mm² flexible with cable end, without bezel || captive screw clamp terminals, 2 x 0.5...2 x 1.5 mm² flexible with cable end, with double bezel
    • [Ui] Rated Insulation Voltage : 300 V 2)EN/IEC 60947-5-1, DIN VDE 0110 parts 1 & 2
    • Power Consumption In Va : 6 VA
    • Local Signalling : 3 LEDs
    • Input Protection Type : internal, electronic
    • Breaking Capacity : 3 A 24 V DC-13)50 ms relay output || 20 mA 24 V solid state output circuit
    • Supply Frequency : 50/60 Hz
    • Maximum Response Time On Input Open : 10 ms
    • Breaking Capacity : 360 VA holding AC-15 B300 relay output || 3600 VA inrush AC-15 B300 relay output
  • Specifications
    • [Us] Rated Supply Voltage : 115...230 V AC - 15...10 %
    • Range Of Product : Preventa Safety automation
    • Product Or Component Type : Preventa safety module
    • Safety Module Name : XPSECPE
    • Number Of Additional Circuits : 2 NC + 1 solid state output
    • Output Type : relay, 8 NO, volt-free
    • Safety Module Application : increasing the number of safety contacts
    • Safety Reliability Data : MTTFd > 100 years EN/ISO 13849-1 || DC = 0...99 % EN/ISO 13849-1 || PFHd = 2.47E-8 1/h EN/IEC 62061
    • Function Of Module : increasing the number of safety contacts
    • Safety Level : can reach PL e/category 4 can reach the maximum safety level of module base EN/ISO 13849-1 || can reach SILCL 3 can reach the maximum safety level of module base EN/IEC 62061