SQUARE D

module XPSABV - stop and switch monitoring - 24 V AC/DC

MODULE XPSABV - STOP AND SWITC

SQDXPSABV1133C 3389118376090
315.70 / EA
http://schema.org/OutOfStock
  • Certifications: BG, CSA, UL
  • Net Weight: 0.275 kg
  • Operating Temperature: -25-55 °C
  • Standard: EN 1088/ISO 14119, EN/IEC 60204-1, EN/IEC 60947-5-1, EN/ISO 13850
  • Storage Temperature: -25-75 °C
  • Warranty Length: 18 mth
This XPSABV safety module monitors emergency shutdown pushbuttons and limit switches. It meets the requirements of PL e/Category 4 (instantaneous safety outputs), PL d/Category 3 (time delayed safety outputs) conforming to EN/ISO 13849-1. It meets also the requirements of SILCL3 (instantaneous safety outputs) and SILCL2 (time delayed safety outputs) conforming to EN/IEC 61508 and EN/IEC 62061. It can be used for monitoring Emergency stop circuits conforming to EN/ISO 13850 and EN/IEC 60204-1 standards, and electrical monitoring of switches in protection devices conforming to EN/ISO 14119 standard. It has removable terminals for easier and better control wires tightening, thus improving installation reliability. It has spring terminals for fast and reliable wiring of safety circuits.
QTY
  • Product Description
  • Specifications
This XPSABV safety module monitors emergency shutdown pushbuttons and limit switches. It meets the requirements of PL e/Category 4 (instantaneous safety outputs), PL d/Category 3 (time delayed safety outputs) conforming to EN/ISO 13849-1. It meets also the requirements of SILCL3 (instantaneous safety outputs) and SILCL2 (time delayed safety outputs) conforming to EN/IEC 61508 and EN/IEC 62061. It can be used for monitoring Emergency stop circuits conforming to EN/ISO 13850 and EN/IEC 60204-1 standards, and electrical monitoring of switches in protection devices conforming to EN/ISO 14119 standard. It has removable terminals for easier and better control wires tightening, thus improving installation reliability. It has spring terminals for fast and reliable wiring of safety circuits.
  • Environment
    • Product Certifications : UL || BG || CSA
    • Ambient Air Temperature For Operation : -25-55 °C
    • Standards : EN/IEC 60947-5-1 || EN 1088/ISO 14119 || EN/IEC 60204-1 || EN/ISO 13850
    • Ip Degree Of Protection : IP20EN/IEC 60529 || IP40EN/IEC 60529
    • Ambient Air Temperature For Storage : -25-75 °C
  • Contractual warranty
    • Warranty : 18 months
  • Offer Sustainability
    • Rohs Exemption Information : Yes
    • Mercury Free : Yes
    • Environmental Disclosure : ENVPEP1406024EN
    • Sustainable Offer Status : Green Premium product
    • Pvc Free : Yes
    • Toxic Heavy Metal Free : Yes
    • Reach Regulation : Reference contains Substances of Very High Concern above the threshold
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • China Rohs Regulation : X
    • Circularity Profile : ENVEOLI1406024EN
    • Eu Rohs Directive : Pro-active compliance (Product out of EU RoHS legal scope)
  • Complementary
    • [Uc] Control Circuit Voltage : 24 V DC
    • Mounting Support : 35 mm symmetrical DIN rail
    • Output Thermal Current : 6 A instantaneous and time delay outputs
    • Minimum Output Voltage : 17 V relay output
    • Minimum Output Current : 10 mA relay output
    • [Ith] Conventional Free Air Thermal Current : 12 A
    • Associated Fuse Rating : 6 A gG instantaneous and time delay outputs
    • [Uimp] Rated Impulse Withstand Voltage : 4 kV III IEC 60947-5-1 || 4 kV III DIN VDE 0110 part 1
    • Net Weight : 0.275 kg
    • Time Delay Range : 0.15...3 s || 1.5...30 s
    • [Ui] Rated Insulation Voltage : 300 V 2)IEC 60947-5-1 || 300 V 2)DIN VDE 0110 part 1
    • Local Signalling : 3 LEDs
    • Input Protection Type : internal, electronic
    • Synchronisation Time Between Inputs : < 0.5 s
    • Breaking Capacity : 1.5 A 24 V DC-13)50 ms relay output
    • Maximum Power Consumption In W : 3 W
    • Maximum Response Time On Input Open : 200 ms
    • Breaking Capacity : 3600 VA inrush AC-15 B300 || 360 VA holding AC-15 B300
  • Specifications
    • [Us] Rated Supply Voltage : 24 V DC - 15...10 %
    • Range Of Product : Preventa Safety automation
    • Product Or Component Type : Preventa safety module
    • Safety Module Name : XPSABV
    • Output Type : relay instantaneous opening, 2 NO, volt-free || relay time delay opening, 1 NO, volt-free
    • Connections - Terminals : spring terminals, removable terminal block, 1 x 0.2...1 x 2.5 mm² solid without cable end || spring terminals, removable terminal block, 1 x 0.2...1 x 2.5 mm² flexible without cable end || spring terminals, removable terminal block, 1 x 0.25...1 x 2.5 mm² flexible with cable end, without bezel || spring terminals, removable terminal block, 1 x 0.25...1 x 2.5 mm² flexible with cable end, with bezel || spring terminals, removable terminal block, 2 x 0.5...2 x 1 mm² flexible with cable end, with double bezel || spring terminals, removable terminal block
    • Number Of Additional Circuits : 0
    • Safety Module Application : for emergency stop and switch monitoring
    • Safety Reliability Data : MTTFd = 53 years instantaneous safety outputs EN/ISO 13849-1 || MTTFd = 53 years time delay safety outputs EN/ISO 13849-1 || DC > 99 % instantaneous safety outputs EN/ISO 13849-1 || DC = 60...90 % time delay safety outputs EN/ISO 13849-1 || PFHd = 3E-8 1/h instantaneous safety outputs EN/IEC 62061 || PFHd = 2E-7 1/h time delay safety outputs EN/IEC 62061
    • Safety Level : can reach PL d/category 3 time delay safety outputs EN/ISO 13849-1 || can reach PL e/category 4 instantaneous safety outputs EN/ISO 13849-1 || can reach SILCL 3 instantaneous safety outputs EN/IEC 62061 || can reach SILCL 2 time delay safety outputs EN/IEC 62061