Motor controller, TeSys T, Motor Management, Profibus DP, 6 logic inputs, 3 logic outputs, 5 to 100A, 100 to 240VAC

MTR Management CTRLler - Profi

SQDLTMR100PFM LTMR100PFM 3389119404853
953.01 / EA
http://schema.org/OutOfStock
  • Certifications: ABS, ATEX, BV, CCC, CSA, C-tick, DNV, EAC, GL, KERI, LROS (Lloyds Register Of Shipping), NOM, RINA, RMRoS, UL
  • Current: 8-62.8 mA
  • Depth: 122.5 mm
  • Height: 61 mm
  • Net Weight: 0.53 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, IACS E10, IEC 60947-4-1, UL 508
  • Storage Temperature: -40-80 °C
  • Warranty Length: 18 mth
  • Width: 91 mm
QTY
  • Specifications
  • Environment
    • Product Certifications : KERI || RMRoS || ABS || UL || ATEX || NOM || RINA || BV || CCC || GL || DNV || CSA || LROS (Lloyds register of shipping) || EAC || C-tick
    • Mechanical Robustness : vibrations mounted on symmetrical rail1 Gn, 5...300 Hz EN/IEC 60068-2-6 || vibrations plate mounted4 Gn, 5...300 Hz EN/IEC 60068-2-6 || shocks half sine wave acceleration15 Gn for 11 ms EN/IEC 60068-2-27
    • Ambient Air Temperature For Operation : -20-60 °C
    • Standards : EN 60947-4-1 || IACS E10 || CSA C22.2 No 14 || UL 508 || IEC 60947-4-1
    • Ambient Air Temperature For Storage : -40-80 °C
    • Protective Treatment : 12 x 24 hour cycles EN/IEC 60068-2-30 || 48 h EN/IEC 60070-2-11 || TH EN/IEC 60068
    • Operating Altitude : <= 6561.68 ft (2000 m) without derating
    • Fire Resistance : 650 °C EN/IEC 60695-2-12 || 960 °C UL 94
    • Ip Degree Of Protection : IP20
  • Contractual warranty
    • Warranty : 18 months
  • Offer Sustainability
    • Rohs Exemption Information : Yes
    • Mercury Free : Yes
    • Environmental Disclosure : ENVPEP060308EN_V2
    • Sustainable Offer Status : Green Premium product
    • Pvc Free : Yes
    • Reach Regulation : Reference contains Substances of Very High Concern above the threshold
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • China Rohs Regulation : Product out of China RoHS scope. Substance declaration for your information.
    • Circularity Profile : ENVEOLI100411EN_V2
    • Eu Rohs Directive : Compliant with Exemptions
    • Halogen Content Performance : Halogen free plastic parts product
  • Complementary
    • Contacts Type And Composition : 1 NO + 1 NC fault signal || 3 NO
    • Height : 61 mm
    • Connection Pitch : 5.08 mm
    • Permissible Power : 480 VA AC-15), Ie = 2 A, 500000 cycles output) || 30 W DC-13), Ie = 1.25 A, 500000 cycles output)
    • Network And Machine Diagnosis Type : starting current and time || trip history information || running hours counter/operating time || phase fault and earth fault trip counters || trip context information || event recording || remaining operating time before overload tripping || motor control command recording || waiting time after overload tripping || fault recording
    • Pollution Degree : 3
    • Logic Input Number : 6
    • Maximum Operating Rate : 1800 cyc/h
    • Connections - Terminals : control circuit connector 1 0.25-2.5 mm² AWG 24...AWG 14)flexible with cable end || control circuit connector 1 0.2-2.5 mm² AWG 24...AWG 14)flexible without cable end || control circuit connector 1 0.25-2.5 mm² AWG 24...AWG 14)flexible without cable end || control circuit connector 1 0.2-2.5 mm² AWG 24...AWG 14)solid without cable end || control circuit connector 2 0.2-1 mm² AWG 24...AWG 14)flexible with cable end || control circuit connector 2 0.2-1.5 mm² AWG 24...AWG 14)flexible without cable end || control circuit connector 2 0.5-1.5 mm² AWG 24...AWG 14)flexible without cable end || control circuit connector 2 0.2-1 mm² AWG 24...AWG 14)solid without cable end
    • Input Current : 3.1 mA 100 V || 7.5 mA 240 V
    • Current State 1 Guaranteed : logic input 79...264 V >= 2 mA 25 ms
    • Net Weight : 0.53 kg
    • [Uimp] Rated Impulse Withstand Voltage : 4 kV supply, inputs and outputs EN/IEC 60947-4-1 || 6 kV current or voltage measurement circuit EN/IEC 60947-4-1 || 0.8 kV communication circuit EN/IEC 60947-4-1
    • Associated Fuse Rating : 4 A gG output || 0.5 A gG control circuit
    • Electromagnetic Compatibility : electrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 || communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 || relay outputs and supply: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5 || relay outputs and supply: surges (common mode), 4 kV, conforming to EN/IEC 61000-4-5 || control circuit: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 || radiated RF fields, 3, 10 V/m, conforming to EN/IEC 61000-4-3 || fast transients immunity test (other circuits), level 3, 2 kV, conforming to EN/IEC 61000-4-4 || fast transients immunity test (on supply and relay outputs), level 4, 4 kV, conforming to EN/IEC 61000-4-4 || voltage dips and interruptions immunity test, 70 %, 500 ms, conforming to EN/IEC 61000-4-11 || conducted RF disturbances, 10 V, conforming to EN/IEC 61000-4-6 || temperature sensor: surges (serial mode), 0.5 kV, conforming to EN/IEC 61000-4-5 || temperature sensor: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5 || control circuit: surges (serial mode), 1 kV, conforming to EN/IEC 61000-4-5
    • Measurement Accuracy : 5...15 % earth fault current internal measurement || 1 % voltage 100...830 V) || 3 % power factor || 5 % earth fault current external measurement || +/- 30 min/year internal clock || 0,02 Temperature || 5 % active and reactive power || 0,02 current
    • Current State 0 Guaranteed : logic input 0...40 V <= 15 mA 25 ms
    • [Ui] Rated Insulation Voltage : 690 V EN/IEC 60947-1 || 690 V CSA C22.2 No 14 || 690 V UL 508
    • Short-Circuit Withstand : 100 kA conforming to EN/IEC 60947-4-1
    • Compatibility Code : LTMR
    • Protection Type : thermal overload protection || power factor variation || overload || locked rotor || thermal protection || reverse polarity protection || phase unbalance || earth-leakage protection || phase failure || load fluctuation || overload (long time)
    • Web Services : web server
    • Width : 91 mm
    • Load Current : 5 A 250 V AC logic output || 5 A 30 V DC logic output
    • Tightening Torque : control circuit 0.5-0.6 N.m flat 3 mm
    • Overvoltage Category : III
    • Depth : 122.5 mm
    • Maximum Operating Frequency : 2 Hz
    • Metering Type : earth-fault current || phase current I1, I2, I3 RMS || temperature || imbalance current || average current Iavg
  • Specifications
    • Product Or Component Type : motor controller
    • Product Name : TeSys T
    • Measurement Current : 5-100 A
    • Range : TeSys
    • Current Consumption : 8...62.8 mA
    • [Us] Rated Supply Voltage : 100...240 V AC 50/60 Hz
    • Communication Port Protocol : Profibus DP
    • Bus Type : Profibus DP polarised 2-wire RS485 1...125 9.6 kbit/s...12 Mbit/s, SUB-D 9 2 shielded twisted pairs, type A || Profibus DP polarised 2-wire RS485 1...125 9.6 kbit/s...12 Mbit/s, terminal block 2 shielded twisted pairs, type A
    • Supply Voltage Limits : 93.5-264 V AC
    • Device Application : equipment monitoring and control
    • Device Short Name : LTMR