Reversing ultra compact starter, TeSys Hybrid, 3P, 500VAC, 0.75kW at 400V, 24VDC, Spring terminal

Compact Starter_Rev 2.4A STD S

SQDLZ2H2X43BD LZ2H2X43BD 3606485421063
337.99 / EA
http://schema.org/OutOfStock
  • Country of Origin: Germany
  • Depth: 114.5 mm
  • Height: 99 mm
  • Net Weight: 212 g
  • Weight: 212 g
  • Width: 22.5 mm
TeSys H ultra compact reverse starter, 3 poles, 2.4A/500V AC-53, for control and protection of 3-phase motors up to 0.75kW@400V (1HP@480V). The hybrid technology used for power contacts procures ultra compactness (22.5mm width) as well as an extended electrical durability up to 30 million cycles AC-53. It provides control for 2 directions of rotation, an adjustable motor current 0.18-2.4A, class 10A thermal overload protection with auto/manual/remote reset, phase loss and phase unbalanced protection, stall and jam motor protection. To be supplied with 24V DC, it provides logic inputs for FW/RV motor direction and remote reset after thermal tripping, 1C/O contact relay for fault indication, LED status on front face for indication of tripping and motor running. DIN rail mounting, spring terminals for control and power, it can be used without derating for ambient temperatures from -25 to 70°C. Multi standards certified (IEC, UL, CCC).
QTY
  • Product Description
  • Features
  • Specifications
TeSys H ultra compact reverse starter, 3 poles, 2.4A/500V AC-53, for control and protection of 3-phase motors up to 0.75kW@400V (1HP@480V). The hybrid technology used for power contacts procures ultra compactness (22.5mm width) as well as an extended electrical durability up to 30 million cycles AC-53. It provides control for 2 directions of rotation, an adjustable motor current 0.18-2.4A, class 10A thermal overload protection with auto/manual/remote reset, phase loss and phase unbalanced protection, stall and jam motor protection. To be supplied with 24V DC, it provides logic inputs for FW/RV motor direction and remote reset after thermal tripping, 1C/O contact relay for fault indication, LED status on front face for indication of tripping and motor running. DIN rail mounting, spring terminals for control and power, it can be used without derating for ambient temperatures from -25 to 70°C. Multi standards certified (IEC, UL, CCC).
  • Prop 65
    • WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
  • Specifications
    • Country of Origin : Germany
    • Width : 22.5 mm
    • Height : 99 mm
    • Weight : 212 g
    • [Uc] Control Circuit Voltage : 24 V DC
    • [Ue] Rated Operational Voltage : 500 V AC
    • Thermal Protection Adjustment Range : 0.18-2.4 A
    • Product Or Component Type : reversing ultra-compact starter
    • Product Name : TeSys Hybrid
    • Thermal Overload Class : class 10A IEC 60947-4-2
    • Motor Power Kw : 0.37 kW 220 V AC 0.65 || 0.37 kW 230 V AC 0.65 || 0.75 kW 380 V AC 0.65 || 0.75 kW 400 V AC 0.65 || 0.75 kW 415 V AC 0.65 || 0.75 kW 440 V AC 0.65 || 1.1 kW 500 V AC 0.65
    • Range : TeSys
    • Motor Starter Type : direct on line
    • [Ie] Rated Operational Current : 2.4 A 500 V AC-51 || 2.4 A 500 V AC-53A || 2.4 A 500 V AC-51 mounting side by side || 2.4 A 500 V AC-53A mounting side by side
    • Poles Description : 3P
    • Maximum Horse Power Rating : 0.5 hp 200 V AC || 0.5 hp 230 V AC || 1 hp 460 V AC
    • Device Short Name : LZ2H
  • Complementary
    • Height : 99 mm
    • Reset : manual || automatic reset || electrical reset
    • Standards : IEC 60947-4-2 || UL 60947-4-1
    • Mounting Support : DIN rail
    • Pollution Degree : 2
    • Net Weight : 212 g
    • [Uimp] Rated Impulse Withstand Voltage : 6 kV
    • Connections - Terminals : spring clamp terminals 1 0.2-2.5 mm² rigid || spring clamp terminals 1 0.25-2.5 mm² flexible - with cable end || spring clamp terminals 1 0.2-2.5 mm² flexible - without cable end
    • Current Consumption : <= 40 mA 24 V DC
    • [Ui] Rated Insulation Voltage : 500 V AC 50/60 Hz
    • Mounting Mode : by clips
    • Maximum Operating Rate : 120 cyc/mn AC-51 50 % || 6 cyc/mn AC-53A 50 %
    • Auxiliary Contact Composition : 1 C/O fault signalling
    • Control Circuit Voltage Limits : 19.2...30 V DC
    • Certifications : CE || cULus
    • Width : 22.5 mm
    • Depth : 114.5 mm
    • Electrical Durability : 30 Mcycles
  • Environmental data
    • Rohs Exemption Information : Yes
    • Packaging Made With Recycled Cardboard : Yes
    • Mercury Free : Yes
    • Packaging Without Single Use Plastic : No
    • Weee Label : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Toxic Heavy Metal Free : Yes
    • California Proposition 65 : WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
    • Reach Free Of Svhc : Yes
    • Take-Back : No
    • Sustainable Packaging : No
    • Eu Rohs Directive : Compliant
  • Environment
    • Ambient Air Temperature For Operation : -25-70 °C without derating
    • Ambient Air Temperature For Storage : -40-80 °C
    • Protective Treatment : TC
    • Ip Degree Of Protection : IP20