Auxiliary contact block, TeSys Deca, 2NC, side mounting, screw clamp terminals

CONTACTOR AUXILIARY CONTACT BL

SQDLAD8N02 LAD8N02 3389110384499
29.64 / EA
http://schema.org/OutOfStock
  • Country of Origin: Indonesia
  • Depth: 76 mm
  • Height: 76 mm
  • Warranty Length: 18 mth
  • Width: 12.5 mm
TeSys Deca instantaneous auxiliary contact block, for LC.D contactors and CAD control relays with AC coils only. It provides 2NC contacts (NC mirror certified) rated up to 10A 690V AC, connection by screw clamp terminals. Clip-on side mounting, it procures high reliability and durability. Multi standards certified (IEC, UL, CSA, CCC, EAC).
QTY
  • Product Description
  • Features
  • Specifications
TeSys Deca instantaneous auxiliary contact block, for LC.D contactors and CAD control relays with AC coils only. It provides 2NC contacts (NC mirror certified) rated up to 10A 690V AC, connection by screw clamp terminals. Clip-on side mounting, it procures high reliability and durability. Multi standards certified (IEC, UL, CSA, CCC, EAC).
  • Prop 65
    • WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
  • Environment
    • Ambient Air Temperature For Operation : -5-60 °C
    • Ip Degree Of Protection : IP20 conforming to IEC 60529
    • Ambient Air Temperature For Storage : -60-80 °C
    • Environmental Characteristic : normal environment
    • Protective Treatment : TH IEC 60068
    • Operating Altitude : 9842.52 ft (3000 m)
  • Contractual warranty
    • Warranty : 18 months
  • Environmental data
    • Packaging Made With Recycled Cardboard : Yes
    • Environmental Disclosure : ENVPEP110807EN_V3
    • Packaging Without Single Use Plastic : No
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Circularity Profile : N/A
    • Take-Back : No
    • Carbon Footprint (Kg Co2 Eq, Total Life Cycle) : 3.8092894548534253
  • Complementary
    • Non-Overlap Time : 1.5 ms on de-energisation no overlap between NC and NO contact || 1.5 ms on energisation no overlap between NC and NO contact
    • Permissible Short-Time Rating : 100 A 1 s || 120 A 500 ms || 140 A 100 ms
    • Minimum Switching Current : 5 mA
    • Height : 76 mm
    • Protection Type : gG fuse 10 A
    • Insulation Resistance : > 10 MOhm
    • Irms Rated Making Capacity : 140 A AC conforming to IEC 60947-5-1 || 250 A DC conforming to IEC 60947-5-1
    • Connections - Terminals : screw clamp terminals 1 1-4 mm²flexible with cable end || screw clamp terminals 1 1-4 mm²flexible without cable end || screw clamp terminals 2 1-2.5 mm²flexible with cable end || screw clamp terminals 2 1-4 mm²flexible without cable end || screw clamp terminals 1 1-4 mm²rigid without cable end || screw clamp terminals 2 1-4 mm²rigid without cable end
    • Minimum Switching Voltage : 17 V
    • Tightening Torque : 1.7 N.m flat Ø 6 mm || 1.7 N.m Philips No 2 || 1.7 N.m pozidriv No 2
    • Mechanical Durability : 30 Mcycles
    • Width : 12.5 mm
    • Depth : 76 mm
  • Specifications
    • Country of Origin : Indonesia
    • Width : 12.5 mm
    • Height : 76 mm
    • Product Certifications : CB Scheme || UL || CSA || CCC || EAC || UKCA
    • [Ith] Conventional Free Air Thermal Current : 10 A (at 60 °C)
    • [Ue] Rated Operational Voltage : 690 V AC 25...400 Hz
    • Standards : EN/IEC 60947-5-1 || UL 60947-5-1 || CSA C22.2 No 60947-5-1 || IEC 60335-1:Clause 30.2 || IEC 60335-2-40:Annex JJ || UL 60335-2-40:Annex JJ
    • Range Compatibility : TeSys Deca LC1D09…95 AC coil || TeSys Deca LC1D40A…80A AC Coil || TeSys Deca LC1D115/150 || TeSys Deca CAD AC coil || TeSys F LC1F
    • Product Or Component Type : auxiliary contact block
    • Product Name : TeSys Deca
    • Range : TeSys
    • Mounting Location : side
    • Pole Contact Composition : 2 NC
    • [Ui] Rated Insulation Voltage : 690 V IEC 60947-5-1 || 600 V UL || 600 V CSA
    • [Ie] Rated Operational Current : 6 A at 120 V AC-15 || 1.04 A at 690 V AC-15 || 0.55 A at 125 V DC-13 || 0.1 A at 600 V DC-13
    • Product Compatibility : LC1D80...D95
    • Auxiliary Contacts Operation : instantaneous