  • Connection Type: RJ45 On The Remote Graphic Terminal)Ethernet/Modbus TCP, RJ45 On The Remote Graphic Terminal)Modbus Serial
  • Country of Origin: USA
  • Depth: 297 mm
  • IsSustainable: Yes
  • Operating Position: Vertical +/- 10 Degree
This Altivar Process ATV600 variable speed drive can feed 3-phase synchronous and asynchronous power motors. This variable speed drive features an integrated EMC filter with 25m cable conforming to category C3. It works at a rated supply voltage from 500V to 690VAC. This drive provides up to 30% energy saving when on standby due to the innovative ‘‘Stop and Go’’operation without additional costs. It is suitable for motors with power rating up to 45kW/60HP (500V supply voltage) for applications requiring slight overload (up to 120%). It is suitable for motors with power rating up to 37kW/50HP (500V supply voltage) for applications requiring significant overload (up to 150%). Its dimensions are 331mm (width) x 297mm (depth) x 630mm (height). It weighs 53kg. This drive is focused on fluids management processing and energy saving, it offers extensive flexibility in water and wastewater, mining, minerals and metals, oil and gas and food and beverage applications. This product is certified by CE, CSA and TUV. It meets UL 508C, EN/IEC 61800-3, EN/IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508 and IEC 13849-1 standards. Accessories (fan kit, graphic display terminal) and options (line chokes, dv/dt filter, sinus filter, EMC filter) are available with Altivar Process ATV600 drives, depending on the drive rating. It is designed to be mounted in vertical position (+/- 10 °) on a wall. This new concept of drives meets the major needs of process and utilities in terms of equipment efficiency and total cost of ownership by supporting the energy management, asset management and also the overall performance of the process.
QTY
  • Features
  • Specifications
  • Prop 65
    • WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
  • Assets
    • Cad : https://download.schneider-electric.com/files?p_Doc_Ref=MCADID0000988_3D-CAD
  • Communications & Management Attributes
    • Communication Port Protocol : Modbus serial, Ethernet, Modbus TCP
  • Conformance Attributes
    • Product Certifications : UL, TÜV, CSA
    • Standards : UL 508C, IEC 61800-3, EN/IEC 61800-3 environment 2 category C3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, UL 508C, IEC 61800-3, environment 2 category C3 IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, IEC 13849-1
  • Complementary Attributes
    • Maximum Horse Power Rating : 50 hp 690 V heavy duty, 50 hp 500 V normal duty, 40 hp 500 V heavy duty, 60 hp 690 V normal duty
    • Maximum Switching Current : relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 30 V DC, relay output R1, R2, R3 resistive, cos phi = 1 3 A 250 V AC, relay output R1, R2, R3 resistive, cos phi = 1 3 A 30 V DC, relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 250 V AC
    • Maximum Thdi : <48 % with external line choke IEC 61000-3-12, <48 % with external line choke IEC 61000-3-12, <48 % with external line choke IEC 61000-3-12, <48 % with external line choke IEC 61000-3-12, <48 % with external line choke IEC 61000-3-12, <48 % with external line choke IEC 61000-3-12
    • Maximum Transient Current : 60.5 A 60 s normal duty), 67.5 A 60 s heavy duty)
    • Ue Rated Operational Voltage : 690 V 37 kW 50 hp heavy duty, 500 V 37 kW 50 hp normal duty, 500 V 30 kW 40 hp heavy duty, 690 V 45 kW 60 hp normal duty
    • Us Rated Supply Voltage : 500...690 V, 500...690 V - 15...10 %
    • Brake Chopper Integrated : false
    • Maximum Associated Fuse Rating : 100.0 A
    • Maximum Input Current Per Phase : 55.6 A
    • Maximum Output Frequency : 500 kHz
    • Maximum Output Voltage : 690.0 V
    • Minimum Switching Current : relay output R1, R2, R3 5 mA 24 V DC
    • Maximum Acceleration Under Shock Impact During Operation : 150 m/s² at 11 ms
    • Maximum Acceleration Under Shock Load During Storage : 150 m/s² at 11 ms
    • Maximum Acceleration Under Shock Load During Transport : 150 m/s² at 11 ms
    • Maximum Acceleration Under Vibrational Stress During Operation : 10 m/s² at 13...200 Hz
    • Maximum Acceleration Under Vibratory Load During Storage : 10 m/s² at 13...200 Hz
    • Maximum Acceleration Under Vibratory Load During Transport : 10 m/s² at 13...200 Hz
    • Maximum Deflection Under Vibratory Load During Operation : 1.5 mm at 2...13 Hz
    • Maximum Deflection Under Vibratory Load During Storage : 1.5 mm at 2...13 Hz
    • Maximum Deflection Under Vibratory Load During Transport : 1.5 mm at 2...13 Hz
  • Important Information Attributes
    • Product Contributes To Saved And Avoided Emissions : YES_SSI2, Yes
    • Persona Type Ids : EU, OM, OM8, SI
    • Persona Type Names : End User, Original Equipment Manufacturer, OEM - Control Panelbuilder, System Integrator
    • Apparent Power : 65 kVA 690 V normal duty), 55.2 kVA 690 V heavy duty)
    • Asynchronous Motor Control Profile : constant torque standard, optimized torque mode, variable torque standard
    • Connector Type : RJ45 on the remote graphic terminal)Ethernet/Modbus TCP, RJ45 on the remote graphic terminal)Modbus serial
    • Electrical Connection : control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16, line side screw terminal 25...50 mm² AWG 4...AWG 1, motor screw terminal 25...50 mm² AWG 4...AWG 1
    • Electromagnetic Compatibility : electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2, radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3, electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4, 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5, conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
    • Frequency Resolution : display unit 0.1 Hz, analog input 0.012/50 Hz
    • Insulation Resistance : > 1 MOhm 500 V DC for 1 minute to earth, > 1 MOhm 500 V DC for 1 minute to earth, > 1 MOhm 500 V DC for 1 minute to earth, > 1 MOhm 500 V DC for 1 minute to earth
    • Line Current : 55.6 A 500 V normal duty), 54.4 A 690 V normal duty), 47.2 A 500 V heavy duty), 46.2 A 690 V heavy duty)
    • Linearity Error : AI1, AI2, AI3 +/- 0.15 % of maximum value analog input, AO1, AO2 +/- 0.2 % analog output
    • Local Signalling : 3 LEDs for local diagnostic, 3 LEDs (dual colour) for embedded communication status, 4 LEDs (dual colour) for communication module status, 1 LED (red) for presence of voltage
    • Motor Power Kw : 37 kW 690 V heavy duty), 37 kW 500 V normal duty), 30 kW 500 V heavy duty), 45 kW 690 V normal duty)
    • Motor Slip Compensation : adjustable, can be suppressed, not available in permanent magnet motor law, automatic whatever the load
    • Noise Level : 52 dB 86/188/EEC, 56 dB
    • Option Card : slot A communication module, Profibus DP V1, slot A communication module, PROFINET, slot A communication module, DeviceNet, slot A communication module, Modbus TCP/EtherNet/IP, slot A communication module, CANopen daisy chain RJ45, slot A communication module, CANopen SUB-D 9, slot A communication module, CANopen screw terminals, slot A/slot B digital and analog I/O extension module, slot A/slot B output relay extension module, slot A communication module, Ethernet IP/Modbus TCP/MD-Link, communication module, BACnet MS/TP, communication module, Ethernet Powerlink
    • Permissible Temporary Current Boost : 1.1 x In 60 s normal duty), 1.5 x In 60 s heavy duty)
    • Power Dissipation In W : natural convection 202 W 500 V 2.5 kHz, forced convection 700 W 500 V 2.5 kHz
    • Product Destination : asynchronous motors, synchronous motors
    • Protection Type : safe torque off drive, motor phase break drive, thermal protection motor, safe torque off motor, motor phase break motor, thermal protection drive, overheating drive, overcurrent between output phases and earth drive, overload of output voltage drive, short-circuit protection drive, overvoltages on the DC bus drive, line supply overvoltage drive, line supply undervoltage drive, line supply phase loss drive, overspeed drive, break on the control circuit drive
    • Sampling Duration : 2 ms +/- 0.5 ms DI1...DI4) - discrete input, 5 ms +/- 1 ms DI5, DI6) - discrete input, 5 ms +/- 0.1 ms AI1, AI2, AI3) - analog input, 10 ms +/- 1 ms AO1) - analog output
    • Supply : external supply for digital inputs 24 V DC 19-30 V), <1.25 mA overload and short-circuit protection, internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection, internal supply for digital inputs and STO 24 V DC 21-27 V), <200 mA overload and short-circuit protection
    • Switching Frequency : 1...4.9 kHz adjustable, 2.5...4.9 kHz with derating factor
    • Synchronous Motor Control Profile : permanent magnet motor, synchronous reluctance motor
    • Transmission Rate : 10, 100 Mbits, 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps
    • Vibration Resistance : 1.5 mm peak to peak (f= 2-13 Hz) conforming to IEC 60068-2-6, 1 gn (f= 13-200 Hz) conforming to IEC 60068-2-6
    • Environmental Class During Storage : class 1C3 according to EN 60721-3-1, class 1S2 according to EN 60721-3-1
    • Environmental Class During Transport : class 2C3 according to EN 60721-3-2, class 2S1 according to EN 60721-3-2
    • Carbon Footprint Of The Distribution Phase A4 : 10.32793868947881, 10 kg CO2 eq.
    • Carbon Footprint Of The End Of Life Phase C1 To C4 : 96.14185095767549, 96 kg CO2 eq.
    • Carbon Footprint Of The Installation Phase A5 : 15 kg CO2 eq., 14.655701481987794
    • Carbon Footprint Of The Manufacturing Phase A1 To A3 : 397 kg CO2 eq., 397.1879473962931
    • Carbon Footprint Of The Use Phase B2 B3 B4 B6 : 13 062 kg CO2 eq., 13061.997157712805
    • Medium Desc : variable speed drive, Altivar Process ATV600, ATV630, 45kW, 60hp, 500 to 690V, IP00
    • Local Data Status : Publishable
    • Local Publishable Date : 2026-01-12
    • Global Commercial Status : Commercialised
    • Return Indicator : Y
    • Stocking Flag : N
    • Device Type : Variable speed drive - VSD Compacts
    • Serviceability : Yes
    • Traceability : Yes
    • Field Service Division : IDIBS
    • Average Life Duration : 10 year(s)
    • Legacy Weee Scope : In
    • Scope Perimeter : At least in Europe
    • Eoli Availability Display : Yes
    • End Of Life Doc Ref : ENVEOLI1706016EN
    • Reach Full Compliance Status : Reference contains Substances of Very High Concern above the threshold
    • Reach Full Compliance Status Id : CONTAINS_SVHC
    • Reach Compliance Directive : Reference contains Substances of Very High Concern above the threshold
    • Rohs Eur In Scope : No
    • Rohs Eur Status : Compliant By Exemption
    • Rohs Eur Full Compliance Status : Compliant By Exemption
    • China Rohs In Scope : Yes
    • With Recycled Cardboard : Yes
    • Without Single Use Plastic : No
    • Dangerous Goods Code : LITHIUM METAL BATTERIES IN EQUIP. BUTTON CELL-BAT EXEMPT
    • Function Option Id : ADVANCED
    • Function Option : Advanced
    • Market Segmentation Id : INDUSTRIAL
    • Market Segmentation : Industrial
    • Product Kit Identifier : N
    • 1 Phase Low Current Possible : false
    • 4 Quadrant Operation Possible : false
    • Application In Domestic And Commercial Area Permitted : false
    • Base Load Current At High Overload : 45.0 A
    • Base Load Current At Low Overload : 55.0 A
    • Braking To Standstill : by DC injection
    • Capacity Of Dc Link : 2500.0 µF
    • Computer Port : true
    • Data Format : 8 bits, configurable odd, even or no parity
    • Design Of Frequency Changer : U converter
    • Device Short Name : ATV630
    • Emc Filter : integrated 25 m IEC 61800-3 category C3
    • Enclosure Mounting : wall mounted
    • Exchange Mode : half duplex, full duplex, autonegotiation Ethernet/Modbus TCP
    • Housing Material : sheet steel
    • Isolation : between power and control terminals
    • Marking : CE
    • Maximum Associated Fuse Rating : 100.0 A
    • Maximum Input Current Per Phase : 55.6 A
    • Method Of Access : slave Modbus TCP
    • Mounting Mode : wall mount
    • Network Frequency : 50-60 Hz
    • Nominal Switching Frequency : 2.5 kHz
    • Number Of Addresses : 1-247 Modbus serial
    • Operating Element Present : true
    • Operating Position : vertical +/- 10 degree
    • Optical Interface Present : false
    • Overvoltage Category : III
    • Phase : 3 phase
    • Power Loss Per Device Current Dependent : 842.0 W
    • Power Loss Static Current Independent : 58.0 W
    • Product Availability : Stock - Normally stocked in distribution facility
    • Product Or Component Type : variable speed drive
    • Product Specific Application : process and utilities
    • Prospective Line Isc : 70 kA
    • Range Of Product : Altivar Process ATV600
    • Refresh Time : relay output R1, R2, R3)5 ms +/- 0.5 ms)
    • Regulation Loop : adjustable PID regulator
    • Relative Symmetric Mains Voltage Tolerance : 10 %
    • Relative Symmetric Network Frequency Tolerance : 5 %
    • Returnability : Yes
    • Safety Function : STO (safe torque off) SIL 3
    • Shock Resistance : 15 gn 11 ms IEC 60068-2-27
    • Software Version : v6.1
    • Supply Frequency : 50...60 Hz - 5...5 %
    • Supporting Protocol For As Interface Safety At Work : false
    • Supporting Protocol For Asi : false
    • Supporting Protocol For Bacnet : false
    • Supporting Protocol For Can : true
    • Supporting Protocol For Data Highway : false
    • Supporting Protocol For Devicenet : false
    • Supporting Protocol For Devicenet Safety : false
    • Supporting Protocol For Ethernet Ip : true
    • Supporting Protocol For Foundation Fieldbus : false
    • Supporting Protocol For Interbus : false
    • Supporting Protocol For Knx : false
    • Supporting Protocol For Lon : false
    • Supporting Protocol For Modbus : true
    • Supporting Protocol For Other Bus Systems : false
    • Supporting Protocol For Profibus : true
    • Supporting Protocol For Profinet Cba : true
    • Supporting Protocol For Profinet Io : true
    • Supporting Protocol For Profisafe : false
    • Supporting Protocol For Safetybus P : false
    • Supporting Protocol For Sercos : false
    • Supporting Protocol For Suconet : false
    • Supporting Protocol For Tcp Ip : true
    • Sustainable Packaging : No
    • Total Lifecycle Carbon Footprint : 13 580 kg CO2 eq.
    • Transmission Frame : RTU
    • Type Of Cooling : forced convection
    • Type Of Polarization : no impedance
    • Volume Of Cooling Air : 406 m3/h
    • Weee Label : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • With Safety Function Safe Programmable Logic : false
    • Application In Industrial Area Permitted : true
    • Supporting Protocol For Interbus Safety : false
    • Emc Limit Value Complied : true
    • Permitted Relative Humidity During Transport : class 2K5 according to EN 60721-3
    • With Safety Function Safe Brake Management Sbc Sbt : false
    • With Safety Function Safe Direction Sdi : false
    • With Safety Function Safe Operating Stop Sos : false
    • With Safety Function Safe Position Sp : false
    • With Safety Function Safe Speed Monitor Ssm : false
    • With Safety Function Safe Stop 1 Ss1 : false
    • With Safety Function Safe Torque Off Sto : true
    • With Safety Function Safely Limited Position Slp : false
    • With Safety Function Safely Limited Speed Sls : false
    • With Sft Fct Safe Stop 2 Ss : false
    • Pep Code : ENVPEP1706016EN
    • Database Version : 2023-02
    • Pep Verification Date : 2024-11-01
    • Pcr Version : PCR-4-ed4-EN-2021 09 06
    • Psr Version : PSR-0005-ed3.1-EN-2023 12 08
    • Type Of Verification For The Pep : Independent external review
    • Data Source : extrapolated product
    • Functional Unit Description : To adapt the speed and torque of synchronous, asynchronous or reluctance motor to the machine's operating point for 75 kW for heavy duty electric motors for fluid management and industrial applications in IP20/UL type 1 conditions, at 600V rated 3-phases voltage supply. Calculation of the environmental impacts is based on 10 years of product service lifetime. The usage profile taken into account is 80% uptime in use phase at 75% loading rate and 20% uptime in stand by phase.
    • Functional Unit Unit : Unit
    • Energy Model Manufacturing A1 A3 2 : India, IN
    • Energy Model Installation A5 2 : Electricity Mix; Low voltage; 2018; Europe, EU-27
    • Energy Model Use B6 2 : Electricity Mix; Low voltage; 2018; Europe, EU-27
    • Energy Model End Of Life C1 C4 2 : Electricity Mix; Low voltage; 2018; Europe, EU-27
    • Height Nominal : 630 mm
    • Width Nominal : 331 mm
  • Environment Attributes Main
    • Ambient Air Temperature For Operation : -15-50 °C (without derating), -15-50 °C (without derating), -15-60 °C, -15-50 °C (without derating), -15-50 °C (without derating), 50-60 °C (with derating factor)
    • Ambient Air Transport Temperature : -40-70 °C, -40-70 °C
    • Ip Degree Of Protection : IP20 with kit VW3A9706)IEC 60529, IP21, IP00IEC 61800-5-1, IP00IEC 60529, IP20 with kit VW3A9706)IEC 61800-5-1
    • Operating Altitude : <= 3280.84 ft (1000 m) without derating, <= 3280.84 ft (1000 m) without derating, <= 3280.84 ft (1000 m) without derating, <= 3280.84 ft (1000 m) without derating, 1000...4800 m with current derating 1 % per 100 m
    • Environmental Class During Operation : class 3C3 according to IEC 60721-3-3, class 3S3 according to IEC 60721-3-3
    • Take Back : Nej
    • Recycled Metal Content At Cr Level : 0 %
    • China Rohs Regulation : X
    • Mercury Free : Yes
    • Carbon Footprint : 13580.310596238241
    • Ambient Air Temperature For Storage : -40-70 °C
    • Circularity Profile : ENVEOLI1706016EN
    • Environmental Disclosure : ENVPEP1706016EN
    • Eu Rohs Directive : Compliant By Exemption
    • Nema Degree Of Protection : NEMA 1
    • Packaging Made With Recycled Cardboard : Yes
    • Packaging Without Single Use Plastic : No
    • Reach Regulation : Reference contains Substances of Very High Concern above the threshold
    • Relative Humidity : 5-95 % without condensation IEC 60068-2-3
    • Permitted Relative Humidity During Operation : class 3K5 according to EN 60721-3
    • Permitted Relative Humidity During Storage : class 1K5 according to EN 60721-3
    • Pep Code : ENVPEP1706016EN
    • Pep Verification Date : 2024-11-01
    • Pcr Version : PCR-4-ed4-EN-2021 09 06
    • Psr Version : PSR-0005-ed3.1-EN-2023 12 08
    • Type Of Verification For The Pep : Independent external review
  • General Attributes
    • Phase : 3 phase
    • Product Or Component Type : variable speed drive
    • Range Of Product : Altivar Process ATV600
  • ETIM
    • ETIM 8 : EC001857
    • ETIM 9 : EC001857
  • Output Attributes
    • Analogue Output Type : software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits, software-configurable current AQ1, AQ2 0...20 mA 10 bits, software-configurable current DQ-, DQ+ 30 V DC, software-configurable current DQ-, DQ+ 100 mA
    • Continuous Output Current : 55 A 2.5 kHz normal duty, 45 A 2.5 kHz heavy duty
    • Discrete Output Type : relay outputs R2A, R2C 30 V DC 5000 mA, relay outputs R3A, R3C 30 V DC 5000 mA, relay outputs R1A, R1B, R1C 250 V AC 3000 mA, relay outputs R1A, R1B, R1C 30 V DC 3000 mA, relay outputs R2A, R2C 250 V AC 5000 mA, relay outputs R3A, R3C 250 V AC 5000 mA
    • Relay Output Type : configurable relay logic R1 fault relay NO/NC 100000 cycles, configurable relay logic R2 sequence relay NO 100000 cycles, configurable relay logic R3 sequence relay NO 100000 cycles
    • Analogue Output Number : 2
    • Discrete Output Number : 0
    • Maximum Output Frequency : 500 kHz
    • Maximum Output Voltage : 690.0 V
    • Nominal Output Current : 55.0 A
    • Nominal Output Power : 45.0 kW
    • Output Voltage : <= power supply voltage
    • Relay Output Number : 3
    • Speed Drive Output Frequency : 0.1-500 Hz
  • Surge Protection And Filtering Attributes
    • Emc Filter : integrated 25 m IEC 61800-3 category C3
  • Input Attributes
    • Analogue Input Type : AI1, AI2, AI3 software-configurable voltage 0...10 V DC 31.5 kOhm 12 bits, AI1, AI2, AI3 software-configurable current 0...20 mA 250 Ohm 12 bits, AI2 voltage analog input - 10...10 V DC 31.5 kOhm 12 bits
    • Discrete Input Logic : positive logic (source) DI1...DI8), < 5 V, > 11 V, negative logic (sink) DI1...DI8), > 16 V, < 10 V, 16 preset speeds
    • Input Compatibility : DI1...DI6 discrete input level 1 PLC IEC 61131-2, DI5, DI6 discrete input level 1 PLC IEC 65A-68, STOA, STOB discrete input level 1 PLC IEC 61131-2
    • Analogue Input Number : 3
    • Discrete Input Number : 8
    • Discrete Input Type : DI7, DI8 programmable as pulse input 0-30 kHz, 24 V DC <= 30 V)
    • Number Of Input Phases : 3
  • Specifications
    • Country of Origin : United States
    • Depth : 297 mm
  • Batteries & Runtime Attributes
    • Removable Battery : Yes