PowerLogic EM3500 DIN rail meter - BACnet - flexible transducer

POWERLOGIC EM3500 DIN RAIL MET

SQDMETSEEM3560A METSEEM3560A SQDMETSEEM3560A
1040.47 / EA
http://schema.org/OutOfStock
  • Depth: 59 mm
  • Display Type: Backlit LCD
  • IsSustainable: Yes
  • Number of Outputs: 1 Alarm Output
The EM3500 series offer a three-phases DIN rail-mounted energy meters fitted for accurate cost allocation and sub-metering. EM35xxA models are designed for use exclusively with Rogowski coil CTs where integrator and power supply for the CTs are built into the meter. Not recommanded for high harmonic application. Current input from 20A to 5000A with the Rogowski coil, ANSI C12.20 0.5% accuracy, IEC 62053-22 class 0.5S. The data logging capability protects data in the event of a power failure. Native BACnet and phase alarms are all provided to suit a wide variety of applications. Additional pulse input provide an easy way to incorporate simple WAGES sensors using a BACnet system. Suitable for a 230V AC network, with a supply voltage range of 90V AC to 300V AC at 50Hz or 60Hz. Compliant with UL508, CSA 22.2 number 14-05 and EN 61010-1. Product dimensions are as follows: width 107 mm, depth 59 mm, height 91 mm and product weight 280 g.
QTY
  • Product Description
  • Features
  • Specifications
The EM3500 series offer a three-phases DIN rail-mounted energy meters fitted for accurate cost allocation and sub-metering. EM35xxA models are designed for use exclusively with Rogowski coil CTs where integrator and power supply for the CTs are built into the meter. Not recommanded for high harmonic application. Current input from 20A to 5000A with the Rogowski coil, ANSI C12.20 0.5% accuracy, IEC 62053-22 class 0.5S. The data logging capability protects data in the event of a power failure. Native BACnet and phase alarms are all provided to suit a wide variety of applications. Additional pulse input provide an easy way to incorporate simple WAGES sensors using a BACnet system. Suitable for a 230V AC network, with a supply voltage range of 90V AC to 300V AC at 50Hz or 60Hz. Compliant with UL508, CSA 22.2 number 14-05 and EN 61010-1. Product dimensions are as follows: width 107 mm, depth 59 mm, height 91 mm and product weight 280 g.
  • Prop 65
    • WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
  • Communications & Management Attributes
    • Communication Service : total cumulated energy, total cumulated active energy
    • Communication Port Protocol : BACnet MS/TP 9600 bauds...115200 bauds (automatic detection) - 2-wire
    • Communication Port Support : screw terminal block RS485
  • Physical Attributes
    • Buffer Size : 32-bit 3
    • Color : dark grey
  • Conformance Attributes
    • Product Certifications : CE conforming to IEC 61010, cULus conforming to UL 508
    • Standards : IEC 61010-1, UL 508, CSA C22.2 No 14-05
  • Complementary Attributes
    • Ue Rated Operational Voltage : 90...347 V AC 50/60 Hz between phase and neutral UL, 156...600 V AC 50/60 Hz between phases UL, 90...300 V AC 50/60 Hz between phase and neutral CE, 125...300 V DC
    • Rated Voltage : 90-347 V
  • Important Information Attributes
    • Device Application : sub billing, partial meter
    • Function Available : external synchronisation to communication, fixed or rolling block
    • Information Displayed : status and alert, communication with system, input/output status, error, Tx activity, Rx activity, instant power per usage
    • Local Signalling : Red LED threshold reached, Green flashing LED output signal
    • Measurement Accuracy : power +/- 0.5 %, energy +/- 0.5 %
    • Metering Type : peak demand power PM, QM, SM, current I1, I2, I3, Iavg, demand power P, Q, S, voltage U21, U32, U13, V1, V2, V3
    • Mounting Mode : by screws, clip-on
    • Network Frequency : 50 Hz, 60 Hz
    • Power Consumption In Va : 5-5 VA 347 V AC between phase and neutral), 5-5 VA 600 V AC between phases)
    • Type Of Measurement : apparent power per phase, power factor per phase, active and reactive power total, active and reactive power per phase, apparent power total, power factor total, peak demand power, current, voltage, frequency
    • Carbon Footprint Of The Distribution Phase A4 : 0, 0 kg CO2 eq.
    • Carbon Footprint Of The End Of Life Phase C1 To C4 : 0.9 kg CO2 eq., 0.8889475602366841
    • Carbon Footprint Of The Installation Phase A5 : 0.007375080016090249, 0 kg CO2 eq.
    • Carbon Footprint Of The Manufacturing Phase A1 To A3 : 11 kg CO2 eq., 10.83731303937071
    • Carbon Footprint Of The Use Phase B2 B3 B4 B6 : 0 kg CO2 eq., 0
    • Local Data Status : Publishable
    • Local Publishable Date : 2025-07-09
    • Global Commercial Status : Commercialised
    • Return Indicator : Y
    • Stocking Flag : Y
    • Stock Policy : 2
    • Device Type : Relay, Control & Measurement - measuring, monitoring device
    • Serviceability : No
    • Traceability : Yes
    • Field Service Division : DPIBS
    • Average Life Duration : 15 year(s)
    • Legacy Weee Scope : In
    • Weee Product Category : 5
    • Scope Perimeter : Outside of Europe
    • Eoli Availability Display : Yes
    • End Of Life Doc Ref : ENVEOLI2509001EN
    • Reach Full Compliance Status : Reference contains Substances of Very High Concern above the threshold
    • Reach Full Compliance Status Id : CONTAINS_SVHC
    • Reach Compliance Directive : Reference contains Substances of Very High Concern above the threshold
    • Rohs Eur In Scope : Yes
    • Rohs Eur Status : Compliant By Exemption
    • Rohs Eur Conformity Date : 2031
    • Rohs Eur Full Compliance Status : Compliant By Exemption
    • China Rohs In Scope : No
    • With Recycled Cardboard : No
    • Without Single Use Plastic : No
    • Product Contributes To Saved And Avoided Emissions : No
    • Product Kit Identifier : N
    • Data Recording : energy consumption logs
    • Device Short Name : EM3560A
    • Display Digits : 5
    • Display Type : Backlit LCD
    • Energy Efficiency Optimized : False
    • Measurement Current : 20-5000 A
    • Mounting Support : DIN rail
    • Poles Description : 3P + N
    • Power Consumption In W : 3 W 300-300 V
    • Product Availability : Non-Stock - Not normally stocked in distribution facility
    • Product Name : PowerLogic EM3500
    • Product Or Component Type : energy meter
    • Range : PowerLogic
    • Returnability : Yes
    • Ride Through Time : 100 ms 120 V AC
    • Software Version : v6.2.4
    • Sustainable Packaging : No
    • Tamperproof Of Settings : protected by access code
    • Technology Type : electronic
    • Total Lifecycle Carbon Footprint : 12 kg CO2 eq.
    • Warranty In Months : 18
    • Pep Code : ENVPEP2509001EN
    • Database Version : 2024-01
    • Pep Verification Date : 2025-10-29
    • Pcr Version : PEP-PCR-ed4-2021 09 06
    • Psr Version : PSR-0005-ed3-2023 06 06
    • Type Of Verification For The Pep : Independent internal review
    • Data Source : extrapolated product
    • Functional Unit Description : Other switchgear and controlgear solutions mentioned in the scope (e.g. fuses TC32, all-or-nothing relays TC94, Measuring relays and protection equipment TC95), apply the general rules of PCR and mention in the accompanying report the functional unit, the reference product characteristics, the reference lifetime and the use scenario which are applied consistently with the relevant IEC technical standards.
    • Functional Unit Quantity : 1
    • Functional Unit Unit : unit
    • Product Weight In G2 : 410
    • Reference Lifetime In Y2 : 10
    • Energy Consumption On Product Lifetime In Kwh : 148.044
    • Energy Model Manufacturing A1 A3 2 : Electricity Mix; Low voltage; 2020; United States, US
    • Energy Model Installation A5 2 : No energy used
    • Energy Model Use B6 2 : Electricity Mix; Low voltage; 2020; United States, US
    • Energy Model End Of Life C1 C4 2 : Global, European and French datasets are used.
    • Offer Owner Code : 190781
    • Height Nominal : 91 mm
    • Width Nominal : 107 mm
  • Environment Attributes Main
    • China Rohs Regulation : Product out of China RoHS scope , Product out of China RoHS scope. Substance declaration for your information.
    • Ambient Air Temperature For Operation : -30-70 °C, -30-70 °C
    • Take Back : Nej
    • Recycled Metal Content At Cr Level : 0 %
    • Mercury Free : Yes
    • Carbon Footprint : 11.733635679623482
    • 9 Mm Pitches : 12
    • Ambient Air Temperature For Storage : -40-85 °C
    • Circularity Profile : ENVEOLI2509001EN
    • Environmental Disclosure : ENVPEP2509001EN
    • Eu Rohs Directive : Compliant By Exemption
    • Packaging Made With Recycled Cardboard : No
    • Packaging Without Single Use Plastic : No
    • Reach Regulation : Reference contains Substances of Very High Concern above the threshold
    • Relative Humidity : 0-95 %
    • Pep Code : ENVPEP2509001EN
    • Pep Verification Date : 2025-10-29
    • Pcr Version : PEP-PCR-ed4-2021 09 06
    • Psr Version : PSR-0005-ed3-2023 06 06
    • Type Of Verification For The Pep : Independent internal review
  • General Attributes
    • Product Or Component Type : energy meter
  • ETIM
    • ETIM 8 : EC001506
    • ETIM 9 : EC001506
  • Output Attributes
    • Number Of Outputs : 1 alarm output
  • Input Attributes
    • Analogue Input Type : Rogowski coil 50...5000 A
    • Number Of Inputs : 1 pulse
  • Specifications
    • Depth : 59 mm