• Features
  • Specifications
  • Prop 65
    • "WARNING: This product can expose you to chemicals including: Nickel (Metallic), which is known to the State of California to cause cancer, and Bisphenol A (BPA), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov"
  • Specifications
    • Country of Origin : United States
    • Product Certifications : UL Listed
    • Primary Voltage : 480 V
    • Range Of Product : Mini Power-Zone
    • Secondary Voltage : 120/240 V
    • Circuit Breaker Application : FAL26060 primary main breaker 60 A || QOB280 secondary main breaker 80 A || QO/QOB feeder breaker 60 A
    • Board Name : NQ Panelboard interior
    • Temperature Rise : 115 °C
    • Number Of Tap-Offs : 2 5 % FCBN
    • Product Or Component Type : Sealed Transformer
    • Number Of Circuits : 28
    • Number Of Spaces : 28
    • Phase : 1 phase
    • Material : copper
    • Rated Power In Va : 15 kVA
    • Short-Circuit Current : 25 kA
    • Nema Degree Of Protection : NEMA 3R hot-rolled steel
    • Box Number : BB
    • Insulation Temperature : 185 °C
  • Contractual warranty
    • Warranty : 18 months
  • Environmental data
    • Packaging Made With Recycled Cardboard : Yes
    • Packaging Without Single Use Plastic : No
    • California Proposition 65 : "WARNING: This product can expose you to chemicals including: Nickel (Metallic), which is known to the State of California to cause cancer, and Bisphenol A (BPA), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov"
    • China Rohs Regulation : Product out of China RoHS scope. Substance declaration for your information.
    • Take-Back : No
    • Pvc Free : Yes