EM4800 multi-circuit energy meter - 24 x 80 mA inputs, 120 V - 60 Hz

EM4800, 80MA CTS, 120V CP, 60

SQDMETSEEM488016 METSEEM488016 785901754497
8717.53 / EA
http://schema.org/OutOfStock
  • Certifications: UL
  • Depth: 5.5 cm
  • Height: 30.5 cm
  • Mounting Type: Wall Mounted, Wall-Mounted
  • Net Weight: 4 kg
  • Standard: ANSI/TIA-568-A, CSA C22.2 No 61010-1, EN 55022, FCC Part 15 Class B, ICES-003, IEC 61000-4-5, IEC 61010-1
  • Storage Temperature: -40-70 °C
  • Warranty Length: 18 mth
  • Width: 33.5 cm
This multi-circuit power meter is part of the PowerLogic EM4800 Series. This compact multi-circuit energy meter enables reliable metering of individual tenants with a low installation cost-per-point. It combine revenue-accurate electricity sub-metering with advanced communications technology. It is ideal for multi-tenant or departmental metering applications within office, condominiums, malls and other multi-user environments. This version monitor up to 24 tenants with a single device, combined with 80 mA solid core current transformers. Designed for 120 volts networks, working at 60 Hz. Measurement accuracy is plus or minus 0.5 %, compliant with ANSI C12.1 and C12.20 Class 0.5 ; IEC 62053-22 Class 0.5S. The printed board is installed in a Type 1 black enclosure, with an integrated backlit LCD display, 2 lines, on the door. Mechanical dimensions are 335 mm in width, 440 mm in height and 55 mm in depth ; for 5.4 kg.
QTY
  • Product Description
  • Specifications
This multi-circuit power meter is part of the PowerLogic EM4800 Series. This compact multi-circuit energy meter enables reliable metering of individual tenants with a low installation cost-per-point. It combine revenue-accurate electricity sub-metering with advanced communications technology. It is ideal for multi-tenant or departmental metering applications within office, condominiums, malls and other multi-user environments. This version monitor up to 24 tenants with a single device, combined with 80 mA solid core current transformers. Designed for 120 volts networks, working at 60 Hz. Measurement accuracy is plus or minus 0.5 %, compliant with ANSI C12.1 and C12.20 Class 0.5 ; IEC 62053-22 Class 0.5S. The printed board is installed in a Type 1 black enclosure, with an integrated backlit LCD display, 2 lines, on the door. Mechanical dimensions are 335 mm in width, 440 mm in height and 55 mm in depth ; for 5.4 kg.
  • Environment
    • Ambient Air Temperature For Operation : -40-70 °C
    • Height : 30.5 cm
    • Standards : ICES-003 || CSA C22.2 No 61010-1 || IEC 61000-4-5 || EN 55022 || FCC Part 15 class B || IEC 61010-1 || ANSI/TIA-568-A
    • Device Mounting : wall mounted
    • Product Certifications : UL
    • Net Weight : 4 kg
    • Type Of Installation : indoor installation || enclosed outdoor
    • Pollution Degree : 2
    • Mounting Mode : wall mount
    • Ambient Air Temperature For Storage : -40-70 °C
    • Relative Humidity : 90-90 % 40-40 °C
    • Width : 33.5 cm
    • Depth : 5.5 cm
    • Operating Altitude : <= 9842.52 ft (3000 m)
  • Contractual warranty
    • Warranty : 18 months
  • Offer Sustainability
    • Rohs Exemption Information : Yes
    • Mercury Free : Yes
    • Toxic Heavy Metal Free : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
    • Reach Free Of Svhc : Yes
    • China Rohs Regulation : Product out of China RoHS scope. Substance declaration for your information.
    • Eu Rohs Directive : Compliant
  • Complementary
    • Communication Port Support : RJ45 ETHERNET || RJ11 modem || SUB-D 9 RS232
    • Measurement Voltage : 80-480 V || 480-999000 V with external VT
    • Sampling Rate : 256 samples/cycle
    • Communication Port Protocol : BACnet IP || FTP || HTTP || Modbus TCP/IP || SNTP
    • Communication Of Data : positive reactive energy || positive active energy || voltage || apparent energy || negative reactive energy || negative active energy
    • Number Of Inputs : 2 pulse
    • Messages Display Capacity : 2 lines of 16 characters
    • Measurement Accuracy : +/- 0.5 % of the measuring range
    • Analogue Input Type : solid core CT 80 mA24 x single pole || solid core CT 80 mA12 x single phase || solid core CT 80 mA8 x three phase
    • Display Type : Backlit LCD
  • Specifications
    • Network Frequency : 60 Hz
    • Type Of Measurement : current per phase, rms || voltage per phase, rms || negative reactive energy || apparent energy || pulse count || positive active energy || positive reactive energy || negative active energy
    • Power Monitoring : basic instrumentation
    • Product Or Component Type : multi-circuit energy meter
    • Product Name : PowerLogic EM4800
    • Range : PowerLogic
    • Energy Management : sub billing and cost allocation || billing analysis
    • [Us] Rated Supply Voltage : 120 V AC 60 Hz
    • Device Application : sub billing
    • Device Short Name : EM4800