SQUARE D

Circuit breaker, PowerPacT L, 450A, 3 pole, 500VDC, 20kA, lugs, thermal magnetic, 80%

CIRCUIT BREAKER, POWERPACT L,

SQDLGL37045D31 LGL37045D31 SQDLGL37045D31
16453.24 / EA
http://schema.org/OutOfStock
  • Certifications: CSA, NOM, UL
  • Depth: 110 mm
  • Height: 340 mm
  • Line Rated Current: 450-450 A
  • Mounting Type: Unit Mount Lug)
  • Net Weight: 6.2 kg
  • Standard: CSA, IEC 60947-2, NEMA, NOM-003-SCFI-2000, UL
  • Storage Temperature: -50-85 °C
  • Strip Length: 31 mm, 61 mm
  • Trip Point: 1125-2250 A
  • Warranty Length: 18 mth
  • Width: 140 mm
PowerPacT L-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT L-Frame circuit breakers are available with electronic trip units. All PowerPacT L-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT L circuit breakers are available in 3 and 4-pole unit mount, I-Line, and drawout constructions. This PowerPacT L, 450A, 3 pole, circuit breaker has an interrupting rating of 20kA at 500VDC. This circuit breaker has a fixed long time electronic trip unit. This unit has lugs on both the line and load sides. This circuit breaker has a continuous current rating of 80%. PowerPacT L circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
QTY
  • Product Description
  • Specifications
PowerPacT L-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT L-Frame circuit breakers are available with electronic trip units. All PowerPacT L-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT L circuit breakers are available in 3 and 4-pole unit mount, I-Line, and drawout constructions. This PowerPacT L, 450A, 3 pole, circuit breaker has an interrupting rating of 20kA at 500VDC. This circuit breaker has a fixed long time electronic trip unit. This unit has lugs on both the line and load sides. This circuit breaker has a continuous current rating of 80%. PowerPacT L circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
  • Environment
    • Ambient Air Temperature For Operation : -2-70 °C
    • Pollution Degree : 3 IEC 60947-1
    • Ambient Air Temperature For Storage : -50-85 °C
    • Standards : UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
    • Product Certifications : UL || CSA || NOM
    • Operating Altitude : < 6561.68 ft (2000 m) without derating || 5000 m with derating
    • Ip Degree Of Protection : front cover IP40
  • Contractual warranty
    • Warranty : 18 months
  • Offer Sustainability
    • China Rohs Regulation : Product out of China RoHS scope. Substance declaration for your information.
    • Circularity Profile : ENVEOLI1406010EN
    • Rohs Exemption Information : Yes
    • Mercury Free : Yes
    • Environmental Disclosure : ENVPEP1406010EN
    • Sustainable Offer Status : Green Premium product
    • Pvc Free : Yes
    • Eu Rohs Directive : Compliant with Exemptions
    • Reach Regulation : Reference contains Substances of Very High Concern above the threshold
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
  • Complementary
    • Circuit Breaker Application : HACR rated
    • Mounting Mode : unit mount lug)
    • Network Frequency : 50/60 Hz
    • Wire Stripping Length : 31 mm || 61 mm
    • Terminal Identifier : AL600LS52K3
    • Line Rated Current : 450-450 A
    • Utilisation Category : category A
    • [Ics] Rated Service Breaking Capacity : 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
    • Trip Unit Technology : thermal-magnetic
    • Height : 340 mm
    • Breaking Capacity : 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
    • [Ui] Rated Insulation Voltage : 750 V IEC 60947-2
    • Suitability For Isolation : yes IEC 60947-2
    • Communication Interface : Modbus || Ethernet
    • [Ue] Rated Operational Voltage : 600 V AC 50/60 Hz IEC 60947-3
    • Tightening Torque : 50-50 N.m 70-240 mm² (AWG 2/0...500 kcmil)
    • Mounting Support : lug
    • Breaking Capacity Code : G
    • Magnetic Tripping Current : 1125-2250 A
    • Poles Description : 3P
    • Local Signalling : switched off (OFF) 1 trip indicator green)
    • Awg Gauge : 2 x AWG 2/0...500 kcmil aluminium/copper
    • Color : Black
    • Width : 140 mm
    • Protection Technology : current limiter
    • Electrical Connection : lugs, line || lugs, load
    • Depth : 110 mm
    • Net Weight : 6.2 kg
    • [Uimp] Rated Impulse Withstand Voltage : 8 kV IEC 60947-2
    • Control Type : toggle
  • Specifications
    • Product Or Component Type : circuit breaker
    • Product Name : PowerPact L
    • Device Application : distribution
    • Device Short Name : L-Frame
    • Range : PowerPact