Schneider Electric at Mayer

contactor, TeSys F, 3P(3NO), AC-3,<=440V 400 A, coil 550...600V AC

CONTACTOR 600VAC 400AMP IEC +O

SQDLC1F400X7 LC1F400X7 3389110876437
2121.76 / EA
http://schema.org/OutOfStock
  • Certifications: ABS, BV, CB, CCC, DNV, LROS (Lloyds Register Of Shipping), RINA, RMRoS, UKCA, UL
  • Contact Configuration: 3 NO
  • Depth: 219 mm
  • Height: 206 mm
  • Impedance: 0.26 MOhm - Ith 500 A 50 Hz
  • Net Weight: 9.1 kg
  • Standard: EN 60947-1, EN 60947-4-1, IEC 60947-1, IEC 60947-4-1, JIS C8201-4-1
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 213 mm
QTY
  • Specifications
  • Environment
    • Ambient Air Temperature For Operation : -5-55 °C
    • Height : 206 mm
    • Net Weight : 9.1 kg
    • Ambient Air Temperature For Storage : -60-80 °C
    • Protective Treatment : TH
    • Ip Degree Of Protection : IP20 front face with shrouds IEC 60529 || IP20 front face with shrouds VDE 0106
    • Operating Altitude : 9842.52 ft (3000 m) without derating
    • Width : 213 mm
    • Depth : 219 mm
    • Permissible Ambient Air Temperature Around The Device : -40-70 °C
  • Contractual warranty
    • Warranty : 18 months
  • Offer Sustainability
    • Rohs Exemption Information : Yes
    • Mercury Free : Yes
    • Environmental Disclosure : ENVPEP1505009EN
    • Sustainable Offer Status : Green Premium product
    • Reach Regulation : Reference contains Substances of Very High Concern above the threshold
    • California Proposition 65 : WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • China Rohs Regulation : Product out of China RoHS scope. Substance declaration for your information.
    • Circularity Profile : ENVEOLI1505009EN
    • Eu Rohs Directive : Compliant with Exemptions
  • Complementary
    • Product Certifications : CCC || BV || RINA || ABS || DNV || RMRoS || UL || LROS (Lloyds register of shipping) || CB || UKCA
    • Power Dissipation Per Pole : 65 W AC-1 || 42 W AC-3
    • Average Impedance : 0.26 mOhm - Ith 500 A 50 Hz
    • [Ith] Conventional Free Air Thermal Current : 500 A (at 40 °C)
    • Control Circuit Voltage Limits : operational 0.85...1.1 Uc 40...400 Hz 55 °C) || drop-out 0.3...0.5 Uc 40...400 Hz 55 °C)
    • Standards : EN 60947-1 || IEC 60947-4-1 || JIS C8201-4-1 || EN 60947-4-1 || IEC 60947-1
    • Mounting Support : plate
    • Control Circuit Type : AC 40...400 Hz
    • Rated Breaking Capacity : 3200 A conforming to IEC 60947-4-1
    • Associated Fuse Rating : 400 A aM at <= 440 V || 500 A gG at <= 440 V
    • [Uimp] Rated Impulse Withstand Voltage : 8 kV
    • Inrush Power In Va : 1075-1075 VA, 40...400 Hz 0.9 20 °C)
    • Connections - Terminals : control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit bar 2 30 x 5 mm || power circuit lugs-ring terminals 2 150-150 mm² || power circuit bolted connection
    • Pole Contact Composition : 3 NO
    • Operating Time : 40...65 ms closing || 100...170 ms opening
    • Maximum Operating Rate : 2400 cyc/h 55 °C
    • Mechanical Durability : 10 Mcycles
    • Tightening Torque : control circuit 1.2 N.m || power circuit 35 N.m
    • Compatibility Code : LC1F
    • Hold-In Power Consumption In Va : 15-15 VA, 40...400 Hz 0.9 20 °C)
    • Overvoltage Category : III
    • Motor Power Kw : 75 kW at 400 V AC 50/60 Hz (AC-4) || 200 kW at 380...400 V AC 50/60 Hz (AC-3) || 220 kW at 415 V AC 50/60 Hz (AC-3) || 250 kW at 440 V AC 50/60 Hz (AC-3) || 257 kW at 500 V AC 50/60 Hz (AC-3) || 280 kW at 660...690 V AC 50/60 Hz (AC-3) || 185 kW at 1000 V AC 50/60 Hz (AC-3) || 110 kW at 220...230 V AC 50/60 Hz (AC-3)
    • [Ui] Rated Insulation Voltage : 1000 V IEC 60947-4-1 || 1500 V VDE 0110 group C
    • [Icw] Rated Short-Time Withstand Current : 3600 A 40 °C - 10 s || 2400 A 40 °C - 30 s || 1700 A 40 °C - 1 min || 1200 A 40 °C - 3 min || 1000 A 40 °C - 10 min
    • Heat Dissipation : 14-14 W
  • Specifications
    • [Uc] Control Circuit Voltage : 550...600 V AC 40...400 Hz
    • Range Of Product : TeSys F
    • [Ue] Rated Operational Voltage : <= 1000 V AC 50/60 Hz || <= 460 V DC
    • Contactor Application : resistive load || motor control
    • Product Or Component Type : contactor
    • Range : TeSys
    • Utilisation Category : AC-3 || AC-4 || AC-1
    • [Ie] Rated Operational Current : 500 A (at <40 °C) at <= 440 V AC AC-1 || 400 A (at <55 °C) at <= 440 V AC AC-3
    • Poles Description : 3P
    • Device Short Name : LC1F