Low-Voltage Fan Coil Room Controller & Zone Controller: BACnet MS/TP, RH sensor & control, White Case/Fascia

LOW-VOLTAGE FAN COIL ROOM CONT

SQDSE8350U0B11 SE8350U0B11 3606480770067
1165.91 / EA
http://schema.org/OutOfStock
  • Depth: 25 mm
  • Height: 120 mm
  • Input Voltage: ...10 V
  • Line Rated Current: 4 A
  • Net Weight: 340 g
  • Output Voltage: ...10 V, 24 V
  • Standard: EN/IEC 60730-1, ETSI EN 300 328, ETSI EN 301 489-1:v1.9.2, ETSI EN 301 489-17:v2.2.1, 2012, FCC Part 15 Subpart B, FCC Part 15 Subpart C, ICES-003, UL 60730-2-9
  • Storage Temperature: -30-50 °C
  • Width: 86 mm
SE8300 Series room controllers are used for Low Voltage Fan Coil Unit control. The room controllers rated supply voltage range is 24 to 28V AC at 50 or 60Hz +/-15%. The rated current is 4A. The device consumption is up to 12VA. The room controller is colored white and is equiped with a communication port that uses BACnet MS/TP protocol and a PIR sensor. Its Room and Outdoor Air Temperature Display Range is between -40 and 50 oC. The measurement accuracy is +/- 0.5%. The temperature setting range is 12 to 37.5oC for cooling and 4.5 to 32 oC for heating. The room controller is equiped with 2 digital inputs, 5 analog inputs (5 to 10V), 4 analog outputs, and 5 digital outputs. The analog output voltage is 0 to 10V DC at < 5mA into > 2 kOhm resistance. The digital output rating is 28V AC 50 or 60 Hz, 0.3A, 1.5A inrush current. The product follows the following standards: IEC 61326-1: 2005, FCC part 15 subpart C, RSS 210 issue 8, FCC part 15 subpart B, ICES-003, EN 60950-1: 2006/A2, EN 60950-1: 2013, ETSI EN 301 489-1: v1.9.2. The product follows the directives: 2014/30/EU - electromagnetic compatibility, 2014/35/EU - low voltage directive, 2014/53/EU - radio equipment directive. The ambient air temperature for operation is between 0 and 50oC. The relative humidity for operating or storage is between 0 and 75% non condensing. The humidity reading range is 10 to 90% RH non-condensing.
QTY
  • Product Description
  • Specifications
SE8300 Series room controllers are used for Low Voltage Fan Coil Unit control. The room controllers rated supply voltage range is 24 to 28V AC at 50 or 60Hz +/-15%. The rated current is 4A. The device consumption is up to 12VA. The room controller is colored white and is equiped with a communication port that uses BACnet MS/TP protocol and a PIR sensor. Its Room and Outdoor Air Temperature Display Range is between -40 and 50 oC. The measurement accuracy is +/- 0.5%. The temperature setting range is 12 to 37.5oC for cooling and 4.5 to 32 oC for heating. The room controller is equiped with 2 digital inputs, 5 analog inputs (5 to 10V), 4 analog outputs, and 5 digital outputs. The analog output voltage is 0 to 10V DC at < 5mA into > 2 kOhm resistance. The digital output rating is 28V AC 50 or 60 Hz, 0.3A, 1.5A inrush current. The product follows the following standards: IEC 61326-1: 2005, FCC part 15 subpart C, RSS 210 issue 8, FCC part 15 subpart B, ICES-003, EN 60950-1: 2006/A2, EN 60950-1: 2013, ETSI EN 301 489-1: v1.9.2. The product follows the directives: 2014/30/EU - electromagnetic compatibility, 2014/35/EU - low voltage directive, 2014/53/EU - radio equipment directive. The ambient air temperature for operation is between 0 and 50oC. The relative humidity for operating or storage is between 0 and 75% non condensing. The humidity reading range is 10 to 90% RH non-condensing.
  • Specifications
    • Housing Colour : white
    • Ambient Air Temperature For Operation : 0-50 °C
    • Height : 120 mm
    • Calibration Certificate : 1 Pt
    • Standards : EN/IEC 60730-1 || FCC part 15 Subpart B || ICES-003 || ETSI EN 300 328 || ETSI EN 301 489-1:v1.9.2 || FCC part 15 Subpart C || UL 60730-2-9 || ETSI EN 301 489-17:v2.2.1, 2012
    • Output Voltage : 24 V AC relay output || 0...10 V DC analog output
    • Targeted Region : North America.
    • Product Or Component Type : room controller
    • Output Type : 5 xrelay output || 4 xuniversal
    • Humidity Measurement Drift : Less Than 1 % Yearly
    • Product Name : SE8000 Series
    • Net Weight : 340 g
    • Range : EcoStruxure Building Expert
    • Input Type : dry contact 2 || analog 5
    • Communication Port Protocol : BACnet MS/TP || Modbus RTU
    • Directives : 2014/30/EU - electromagnetic compatibility || 2014/35/EU - low voltage directive || 2014/53/EU - radio equipment directive
    • Awg Gauge : AWG 24...AWG 18
    • Ambient Air Temperature For Storage : -30-50 °C
    • Output Current : 1 A relay output || 3 A relay output inrush) || 0.3 A universal output || 1.5 A universal output inrush)
    • Input Voltage : 0...10 V DC
    • Sensor Type : 10 kOhm T2 NTC thermistor Temperature || space RH sensor Humidity || bulk polymer Humidity
    • Relative Humidity : 0-95 %
    • Temperature Setting Range : 12-37.5 °C cooling || 4.5-32 °C heating
    • Line Rated Current : 4 A
    • Width : 86 mm
    • Humidity Setting Range : 30-95 %
    • Market Segment : Lodging/Hotel || small commercial || buildings || healthcare || non-critical buildings || office || residential || school
    • Temperature Resolution : 0.1 °C
    • Depth : 25 mm
    • Device Application : low voltage fan coil
    • Device Short Name : SE8300
  • Complementary
    • Surface Finish : Matte
    • Surface Treatment : untreated
  • Offer Sustainability
    • Rohs Exemption Information : Yes
    • Mercury Free : Yes
    • Reach Regulation : Reference contains Substances of Very High Concern above the threshold
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: LEAD, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
    • China Rohs Regulation : X
    • Eu Rohs Directive : Compliant with Exemptions