BTV Self-Regulating Heating Cable, 240 V, 5 W/ft at 50F, CT-Jacket

CABLE � HEATING 5W 250V

CHM5BTV2CT 5BTV2CT CHM5BTV2CT
19.21 / EA
http://schema.org/OutOfStock
  • Voltage: 208
  • Weight: 0.11 kg
Freeze protection and continuous operation up to 150°F/65°C. Maximum exposure 185°F/85°C. Safe and hazardous area. 240 V, 5 W/ft at 50°F (230 V, 16 W/m at 10°C), Fluoropolymer jacket.
QTY
  • Product Description
  • Features
  • Specifications
Freeze protection and continuous operation up to 150°F/65°C. Maximum exposure 185°F/85°C. Safe and hazardous area. 240 V, 5 W/ft at 50°F (230 V, 16 W/m at 10°C), Fluoropolymer jacket.
  • Features
    • Simplified design in hazardous area: unconditional T6 class
    • Fast installation: cut-to-length, multiple overlaps allowed, meter markings, user-friendly connections kits
    • Safe and efficient in operation: no overheating, uniform pipe temperatures, energy saving technology
    • Reliable during long life: 10 year product warranty available, maintenance free
  • Specifications
    • Length : 1000.00 millimetre
    • Width : 10.50 millimetre
    • Height : 5.50 millimetre
    • Weight : 0.11 kilogram
    • Heating Cable Technology : Self-Regulating
    • Supply Voltage (volt) : 200-277.00
    • Nominal Voltage (volt) : 208
    • Area Classification : Non-Hazardous
    • Conductor Material : Nickel-Plated Copper
    • Ground Path Type : Braid
    • Color : Black
    • Outer Jacket Material : Fluoropolymer
    • Max Circuit Length (metre) : 160
    • Max Circuit Length (foot) : 550
    • Nominal Width (millimetre) : 10.5
    • Nominal Width (inch) : 0.46
    • Nominal Height (millimetre) : 5.5
    • Nominal Height (inch) : 0.25
    • Nominal Thickness (millimetre) : 5.5
    • Nominal Thickness (inch) : 0.25
    • Conductor Quantity : 2
    • Nominal Cable Weight (gram per metre) : 110
    • Nominal Cable Weight (pound per foot) : 0.07
    • Max Maintain or Continuous Exposure Temperature, Power On/Off (degree Celsius) : 65
    • Max Maintain or Continuous Exposure Temperature, Power On/Off (degree Fahrenheit) : 150
    • Max Intermittent Exposure Temperature, Power On/Off (degree Celsius) : 85
    • Max Intermittent Exposure Temperature, Power On/Off (degree Fahrenheit) : 185
    • Max Cumulative Hours for Intermittent Exposure (hour) : 1,000
    • Min Bending Radius @ 20°C (millimetre) : 13
    • Min Bending Radius @ 68°F (inch) : 0.5
    • Min Bending Radius @ -60°C (millimetre) : 35
    • Min Bending Radius @ -76°F (inch) : 1.38
    • Nominal Power Output @ 10°C, 230V (watt per metre) : 16
    • Nominal Power Output @ 50°F, 240V (watt per foot) : 5
    • Min Installation Temperature (degree Fahrenheit) : -40
    • Min Installation Temperature (degree Celsius) : -60
    • Hazardous Area : Yes
    • Max Exposure Temperature (degree Celsius) : 85
    • Max Exposure Temperature (degree Fahrenheit) : 185
    • Sub Brand : RAYCHEM
    • Core : Self-regulating conductive core
    • Number of Conductors : 2
    • Voltage Rating : 240
    • Wattage : 5
    • Temperature Rating : 150
    • Jacket Material : Fluoropolymer