Certifications:
ATEX INERIS, CCC, CSA, DNV-GL, EAC, EU-RO MR, IEC, LROS (Lloyds Register Of Shipping), RMRS, UKCA, UL
-
Contact Configuration:
1 NO + 1 NC
-
Depth:
123 mm
-
Height:
70 mm
-
Net Weight:
0.375 kg
-
Standard:
CSA C22.2 No 60947-4-1, CSA C22.2 No 60947-5-1, EN 50495, EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, UL 60947-5-1
-
Storage Temperature:
-60-70 °C
-
Warranty Length:
18 mth
-
Width:
55 mm
LRD313L is a TeSys LRD thermal overload relay from Schneider Electric to be used with a TeSys D contactor. It protects motors 5.5kW@400V thanks to a thermal range 9-13A, a tripping class 20 and phase unbalance protection. LRD313L is a TeSys LRD thermal overload relay from Schneider Electric for direct mounting on TeSys D contactors. With a thermal setting range 9-13A, a tripping class 20 and phase unbalance detection, it protects motors 5.5kW@400V. It provides manual test & reset buttons, automatic reset, trip auxiliary contact and flag indicator. Available worldwide, it is multi-standards certified (IEC, UL, CSA, CCC, EAC, Marine) and Green Premium compliant (RoHs/Reach). Thermal overload protection relay, bimetallic type, with phase unbalance protection (differential). Direct mounting on the bottom terminals of a Tesys contactor LC1D40A-D65A to form a compact starter. Light and compact, 55mm wide. Temperature compensated for a good accuracy of the protection. Manual control with test & reset buttons, manual / automatic reset selector. Trip signaling with 1NO+1NC auxiliary contacts and trip flag indicator. Can be completed with terminal blocks for separate mounting (LAD7B, LAD96) and remote control devices (LAD703, LA7D03).