TeSys Deca thermal overload relays - 9...13 A - class 20

FLOOR MOUNTING BRACKET

SQD7400FMB 7400FMB 785901812401
132.02 / EA
http://schema.org/OutOfStock
  • Certifications: ATEX INERIS, CCC, CSA, DNV-GL, EAC, EU-RO MR, IEC, LROS (Lloyds Register Of Shipping), RMRS, UKCA, UL
  • Contact Configuration: 1 NO + 1 NC
  • Depth: 123 mm
  • Height: 70 mm
  • Net Weight: 0.375 kg
  • Standard: CSA C22.2 No 60947-4-1, CSA C22.2 No 60947-5-1, EN 50495, EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, UL 60947-5-1
  • Storage Temperature: -60-70 °C
  • Warranty Length: 18 mth
  • Width: 55 mm
LRD313L is a TeSys LRD thermal overload relay from Schneider Electric to be used with a TeSys D contactor. It protects motors 5.5kW@400V thanks to a thermal range 9-13A, a tripping class 20 and phase unbalance protection. LRD313L is a TeSys LRD thermal overload relay from Schneider Electric for direct mounting on TeSys D contactors. With a thermal setting range 9-13A, a tripping class 20 and phase unbalance detection, it protects motors 5.5kW@400V. It provides manual test & reset buttons, automatic reset, trip auxiliary contact and flag indicator. Available worldwide, it is multi-standards certified (IEC, UL, CSA, CCC, EAC, Marine) and Green Premium compliant (RoHs/Reach). Thermal overload protection relay, bimetallic type, with phase unbalance protection (differential). Direct mounting on the bottom terminals of a Tesys contactor LC1D40A-D65A to form a compact starter. Light and compact, 55mm wide. Temperature compensated for a good accuracy of the protection. Manual control with test & reset buttons, manual / automatic reset selector. Trip signaling with 1NO+1NC auxiliary contacts and trip flag indicator. Can be completed with terminal blocks for separate mounting (LAD7B, LAD96) and remote control devices (LAD703, LA7D03).
QTY
  • Product Description
  • Specifications
LRD313L is a TeSys LRD thermal overload relay from Schneider Electric to be used with a TeSys D contactor. It protects motors 5.5kW@400V thanks to a thermal range 9-13A, a tripping class 20 and phase unbalance protection. LRD313L is a TeSys LRD thermal overload relay from Schneider Electric for direct mounting on TeSys D contactors. With a thermal setting range 9-13A, a tripping class 20 and phase unbalance detection, it protects motors 5.5kW@400V. It provides manual test & reset buttons, automatic reset, trip auxiliary contact and flag indicator. Available worldwide, it is multi-standards certified (IEC, UL, CSA, CCC, EAC, Marine) and Green Premium compliant (RoHs/Reach). Thermal overload protection relay, bimetallic type, with phase unbalance protection (differential). Direct mounting on the bottom terminals of a Tesys contactor LC1D40A-D65A to form a compact starter. Light and compact, 55mm wide. Temperature compensated for a good accuracy of the protection. Manual control with test & reset buttons, manual / automatic reset selector. Trip signaling with 1NO+1NC auxiliary contacts and trip flag indicator. Can be completed with terminal blocks for separate mounting (LAD7B, LAD96) and remote control devices (LAD703, LA7D03).
  • Environment
    • Product Certifications : IEC || UL || CSA || CCC || EAC || DNV-GL || RMRS || EU-RO MR || LROS (Lloyds register of shipping) || ATEX INERIS || UKCA
    • Mechanical Robustness : shocks15 Gn for 11 ms IEC 60068-2-7 || vibrations4 gn IEC 60068-2-6
    • Standards : EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-4-1 || CSA C22.2 No 60947-5-1 || EN 50495
    • Climatic Withstand : IACS E10
    • Ambient Air Temperature For Operation : -20-60 °C without derating IEC 60947-4-1
    • Dielectric Strength : 1.89 kV 50 Hz IEC 60947-1
    • Ip Degree Of Protection : IP20 conforming to IEC 60529
    • Flame Retardance : V1 conforming to UL 94
    • Ambient Air Temperature For Storage : -60-70 °C
  • Contractual warranty
    • Warranty : 18 months
  • Offer Sustainability
    • Rohs Exemption Information : Yes
    • Mercury Free : Yes
    • Environmental Disclosure : ENVPEP080405EN
    • Sustainable Offer Status : Green Premium product
    • Toxic Heavy Metal Free : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Reach Free Of Svhc : Yes
    • China Rohs Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Circularity Profile : ENVEOLI0804005_V1
    • Eu Rohs Directive : Compliant
  • Complementary
    • Network Frequency : 0...400 Hz
    • Height : 70 mm
    • [Ith] Conventional Free Air Thermal Current : 5 A signalling circuit
    • Auxiliary Contact Composition : 1 NO + 1 NC
    • Connections - Terminals : control circuit screw clamp terminals 2 1-2.5 mm² flexible without cable end || control circuit screw clamp terminals 2 1-2.5 mm² flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm² solid without cable end || power circuit EverLink BTR screw connectors 1 1-35 mm² flexible without cable end || power circuit EverLink BTR screw connectors 1 1-35 mm² flexible with cable end || power circuit EverLink BTR screw connectors 1 1-35 mm² solid without cable end
    • Phase Failure Sensitivity : tripping current 130 % of Ir on two phase, the last one at 0
    • [Ue] Rated Operational Voltage : 690 V AC 0...400 Hz power circuit IEC 60947-4-1
    • Associated Fuse Rating : 4 A gG for signalling circuit || 4 A BS for signalling circuit
    • Net Weight : 0.375 kg
    • [Uimp] Rated Impulse Withstand Voltage : 6 kV
    • Permissible Current : 3 A 120 V AC-15 signalling circuit || 0.22 A 125 V DC-13 signalling circuit
    • Tripping Threshold : 1.14 +/- 0.06 Ir IEC 60947-4-1
    • Tightening Torque : control circuit 1.7 N.m screw clamp terminals || power circuit 5 N.m EverLink BTR screw connectors
    • Control Type : Red push-button stop || Blue push-button reset
    • Mounting Support : plate, with specific accessories || rail, with specific accessories || under contactor
    • Width : 55 mm
    • Depth : 123 mm
    • Temperature Compensation : -20-60 °C
  • Specifications
    • Network Type : DC || AC
    • Thermal Protection Adjustment Range : 9-13 A
    • Relay Application : motor protection
    • Product Or Component Type : differential thermal overload relay
    • Product Name : TeSys LRD || TeSys Deca
    • Thermal Overload Class : class 20 IEC 60947-4-1
    • Range : TeSys || TeSys Deca
    • [Ui] Rated Insulation Voltage : power circuit 600 V CSA || power circuit 600 V UL || power circuit 690 V IEC 60947-4-1
    • Product Compatibility : LC1D40A || LC1D65A || LC1D50A
    • Device Short Name : LRD