Surge protection device, Surgelogic, HR, 160kA, 600Y/347 VAC, 3 phase, 4 wire, SPD type 2

SURGE PROTECTION DEVICE, SURGE

SQDHR8IMA16C HR8IMA16C SQDHR8IMA16C
0.00 / EA
http://schema.org/OutOfStock
  • Cable Length: 483 mm
  • Country of Origin: USA
  • Depth: 142.1 mm
  • Height: 308.9 mm
  • Length: 483 mm
  • Number of Poles: 3
  • Width: 341.9 mm
Surgelogic™ Type IMA systems are internal surgical protection devices with a focus on service entrance and critical branch panel surge suppresion. With a surge current rating of 160,000 Amps and enhanced EMI/RFI filtering, this unit is retrofitted to be installed in a wide variety I-Line Branch units. Being modular in design, this unit is able to achieve superior surge suppression on the load side including at the branch panel. This unit uses the WYE system to allow two different voltages using three phase. This product is UL and CSA certified.
QTY
  • Product Description
  • Features
  • Specifications
Surgelogic™ Type IMA systems are internal surgical protection devices with a focus on service entrance and critical branch panel surge suppresion. With a surge current rating of 160,000 Amps and enhanced EMI/RFI filtering, this unit is retrofitted to be installed in a wide variety I-Line Branch units. Being modular in design, this unit is able to achieve superior surge suppression on the load side including at the branch panel. This unit uses the WYE system to allow two different voltages using three phase. This product is UL and CSA certified.
  • Prop 65
    • WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
  • Environmental data
    • Rohs Exemption Information : Yes
    • Packaging Made With Recycled Cardboard : No
    • Mercury Free : Yes
    • Packaging Without Single Use Plastic : No
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
    • Take-Back : No
    • Sustainable Packaging : No
    • Eu Rohs Directive : Compliant with Exemptions
  • Specifications
    • Country of Origin : United States
    • Length : 483 mm
    • Width : 341.9 mm
    • Height : 308.9 mm
    • Range Of Product : Surgelogic
    • Breaking Capacity Code : HR
    • Product Or Component Type : surge protection device
    • Device Short Name : IMA
  • Complementary
    • Height : 308.9 mm
    • Breaking Capacity : 100 kA
    • Connections - Terminals : I-Line line || lugs ground AWG 6 copper 4 N.m || lugs neutral AWG 6 copper 4 N.m
    • Mounting Support : panel mounting
    • Cable Length : 483 mm
    • Provided Equipment : alarm enable/disable switch || surge counter || circuit-breaker
    • Surge Current : 160 kA
    • Phase : 3 phase
    • Local Signalling : status LED green per phase normal operation || status LED red per phase fault
    • Short-Circuit Protection : 200 kA
    • [Uc] Maximum Continuous Operating Voltage : 420 V
    • Line Rated Current : 60 A
    • Width : 341.9 mm
    • Wiring Configuration : 4-wire
    • Depth : 142.1 mm
    • Trip Unit Technology : electronic
    • Number Of Poles : 3
    • [Ue] Rated Operational Voltage : 600Y/347 V AC
  • Environment
    • Standards : UL 1449:ed. 3 || UL 1283:ed. 5 || CSA C22.2 No 8:1986 || UL 96A:ed. 12 || UL 489:ed. 11 || CSA C22.2 No 5-09
    • Nema Degree Of Protection : NEMA 2