Schneider Electric at Mayer

Contactor, high power, TeSys Giga, advanced version, 3 pole/NO, AC-3 <=440V 115A, 200-500VAC/DC coil

CONTACTOR, HIGH POWER, TESYS G

SQDLC1G115LSEA LC1G115LSEA 3606481922427
725.22 / EA
http://schema.org/OutOfStock
  • Country of Origin: China
  • Depth: 193 mm
  • Height: 255 mm
  • Net Weight: 4.1 kg
  • Weight: 4.1 kg
  • Width: 108 mm
TeSys Giga high power contactor, 3 poles (3 NO) for category AC-3 applications up to 115A 75kW@440V. It provides a 200-500V AC/DC wide band low consumption electronic coil, PLC output control and embedded highly reliability 1NO+1NC auxiliary contact block (17V 1mA). Designed for demanding applications with maximum operating rates up to 600 cycles per hour and environments until 60°C. It procures high reliability and durability with 5 Mcycles mechanical durability. Local and Remote Contact Wear Diagnosis (CWD) as standard function, continuous monitoring with healthy and alarm indicators. It is possibility to replace switching module (main contacts), enhancement contactor life. Contactor can be fixed in all quadrants, maintenance without removing cables/busbars, and OLR could be directly mounted below contactor. To be used with power connection by bolted connection with cable memory kit and control connections by spring terminals, accessible from front for easy and quick replacement. It provides IP2x protection in Front face with shrouds conforming to IEC 60529 and VDE 0106. It can cover -25°C to 60°C operation ambient air temperature and directly mounted on plate, No derating up to 3000m altitude. The dimension is 255mm x 108mm x 175mm (H x W x D), compact size enables panel space savings. Multi standards certified (CE,CB,CCC,cULus,EAC,KC,RCM,Marine). Unique QR code provides quick access to complete product data.
QTY
  • Product Description
  • Features
  • Specifications
TeSys Giga high power contactor, 3 poles (3 NO) for category AC-3 applications up to 115A 75kW@440V. It provides a 200-500V AC/DC wide band low consumption electronic coil, PLC output control and embedded highly reliability 1NO+1NC auxiliary contact block (17V 1mA). Designed for demanding applications with maximum operating rates up to 600 cycles per hour and environments until 60°C. It procures high reliability and durability with 5 Mcycles mechanical durability. Local and Remote Contact Wear Diagnosis (CWD) as standard function, continuous monitoring with healthy and alarm indicators. It is possibility to replace switching module (main contacts), enhancement contactor life. Contactor can be fixed in all quadrants, maintenance without removing cables/busbars, and OLR could be directly mounted below contactor. To be used with power connection by bolted connection with cable memory kit and control connections by spring terminals, accessible from front for easy and quick replacement. It provides IP2x protection in Front face with shrouds conforming to IEC 60529 and VDE 0106. It can cover -25°C to 60°C operation ambient air temperature and directly mounted on plate, No derating up to 3000m altitude. The dimension is 255mm x 108mm x 175mm (H x W x D), compact size enables panel space savings. Multi standards certified (CE,CB,CCC,cULus,EAC,KC,RCM,Marine). Unique QR code provides quick access to complete product data.
  • Prop 65
    • WARNING: This product can expose you to chemicals including: Styrene, which is known to the State of California to cause cancer, and Bisphenol A (BPA), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
  • Environment
    • Ambient Air Temperature For Operation : -25-60 °C
    • Ambient Air Temperature For Storage : -60-80 °C
    • Protective Treatment : TH
    • Ip Degree Of Protection : IP2X front face with shrouds IEC 60529 || IP2X front face with shrouds VDE 0106
    • Mechanical Robustness : vibrations 5-300 Hz 2 gn contactor open || vibrations 5-300 Hz 4 gn contactor closed || shocks 10 gn 11 ms contactor open || shocks 15 gn 11 ms contactor closed
    • Color : dark grey
    • Permissible Ambient Air Temperature Around The Device : -40-70 °C at Uc
  • Complementary
    • Product Certifications : CB Scheme || CCC || cULus || EAC || CE || UKCA || EU-RO-MR by DNV-GL
    • Height : 255 mm
    • Power Dissipation Per Pole : 10 W AC-1 - Ith 250 A || 3 W AC-3 - Ith 115 A
    • Average Impedance : 0.00018 Ohm
    • Auxiliary Contact Composition : 1 NO + 1 NC
    • Connection Pitch : 35 mm
    • Mounting Support : plate
    • Standards : EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 || JIS C8201-5-1 || IEC 60335-1:Clause 30.2 || IEC 60335-2-40:Annex JJ || UL 60335-1 || UL 60335-2-40:Annex JJ
    • Safety Reliability Level : B10d = 400000 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1
    • Hold-In Power Consumption In W : 8.0-8.0 W
    • Rated Breaking Capacity : 1040 A at 440 V
    • Associated Fuse Rating : 125 A aM at <= 440 V for motor || 125 A aM at <= 690 V for motor || 315 A gG at <= 690 V
    • Net Weight : 4.1 kg
    • [Uimp] Rated Impulse Withstand Voltage : 8 kV
    • Inrush Power In Va : 295-295 VA
    • Pole Contact Composition : 3 NO
    • Connections - Terminals : power circuit: bar 2 - busbar cross section: 25 x 6 mm || power circuit: lugs-ring terminals 1 185-185 mm² || power circuit: bolted connection || control circuit: push-in 1 0.2-2.5 mm² - cable stiffness: solid stranded without cable end || control circuit: push-in 1 0.25-2.5 mm² - cable stiffness: flexible with cable end || control circuit: push-in 2 0.5-1.0 mm² with cable end || control circuit: push-in 0.75-2.5 mm² - cable stiffness: solid stranded without cable end || control circuit: push-in 0.75-2.5 mm² - cable stiffness: flexible with cable end
    • Coil Technology : built-in bidirectional peak limiting
    • Operating Time : 40...70 ms closing || 15...50 ms opening
    • Maximum Operating Rate : 600 cyc/h AC-3 || 600 cyc/h AC-3e || 300 cyc/h AC-1 || 150 cyc/h AC-4
    • Mechanical Durability : 8 Mcycles
    • Tightening Torque : 18 N.m
    • Compatibility Code : LC1G
    • Hold-In Power Consumption In Va : 13.0-13.0 VA
    • Width : 108 mm
    • Overvoltage Category : III
    • Depth : 193 mm
    • Maximum Horse Power Rating : 30 hp at 200/208 V 60 Hz || 40 hp at 230/240 V 60 Hz || 75 hp at 460/480 V 60 Hz || 100 hp at 575/600 V 60 Hz
    • Motor Power Kw : 30 kW at 230 V AC 50/60 Hz (AC-3e) || 55 kW at 400 V AC 50/60 Hz (AC-3e) || 55 kW at 415 V AC 50/60 Hz (AC-3e) || 75 kW at 440 V AC 50/60 Hz (AC-3e) || 75 kW at 500 V AC 50/60 Hz (AC-3e) || 75 kW at 690 V AC 50/60 Hz (AC-3e) || 30 kW at 230 V AC 50/60 Hz (AC-3) || 55 kW at 400 V AC 50/60 Hz (AC-3) || 55 kW at 415 V AC 50/60 Hz (AC-3) || 75 kW at 440 V AC 50/60 Hz (AC-3) || 75 kW at 500 V AC 50/60 Hz (AC-3) || 75 kW at 690 V AC 50/60 Hz (AC-3) || 30 kW at 230 V AC 50/60 Hz (AC-4) || 55 kW at 400 V AC 50/60 Hz (AC-4) || 55 kW at 415 V AC 50/60 Hz (AC-4) || 65 kW at 440 V AC 50/60 Hz (AC-4) || 65 kW at 500 V AC 50/60 Hz (AC-4) || 75 kW at 690 V AC 50/60 Hz (AC-4)
    • [Ui] Rated Insulation Voltage : 1000 V
    • Inrush Power In W : 215 W
    • [Icw] Rated Short-Time Withstand Current : 1.1 kA - 10 s || 0.64 kA - 30 s || 0.52 kA - 1 min || 0.4 kA - 3 min || 0.32 kA - 10 min
  • Environmental data
    • Packaging Made With Recycled Cardboard : Yes
    • Environmental Disclosure : ENVPEP2105013
    • Halogen Content Performance : Halogen free plastic parts product
    • Packaging Without Single Use Plastic : No
    • Scip Number : 6fbdad13-bb7c-47d4-a6d6-d82dd6f54349
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Styrene, which is known to the State of California to cause cancer, and Bisphenol A (BPA), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
    • Circularity Profile : ENVEOLI2105013
    • Take-Back : No
    • Pvc Free : Yes
    • Carbon Footprint (Kg Co2 Eq, Total Life Cycle) : 595.2815193725783
  • Specifications
    • Country of Origin : China
    • Width : 108 mm
    • Height : 255 mm
    • Weight : 4.1 kg
    • [Uc] Control Circuit Voltage : 200...500 V AC 50/60 Hz || 200...500 V DC
    • [Ue] Rated Operational Voltage : <= 1000 V AC 50/60 Hz || <= 460 V DC
    • Range Of Product : TeSys Giga
    • Control Circuit Voltage Limits : operational: 0.8 Uc Min...1.1 Uc Max (at <60 °C) || drop-out: 0.1 Uc Max...0.45 Uc Min (at <60 °C)
    • Contactor Application : power switching || motor control
    • Product Or Component Type : contactor
    • Range : TeSys
    • Utilisation Category : AC-1 || AC-3 || AC-3e || AC-4 || AC-5a || AC-5b || AC-6a || AC-6b || AC-8b || AC-8a || DC-1 || DC-3 || DC-5
    • [Ie] Rated Operational Current : 250 A (at <40 °C) at <= 1000 V AC-1 || 115 A (at <60 °C) at <= 440 V AC-3
    • Poles Description : 3P
    • Device Short Name : LC1G