SQUARE D

Motor circuit protector, PowerPacT H, 50A, 3 pole, 600VAC, 100kA, lugs, thermal magnetic, 80%

Motor circuit protector, Power

SQDHRL36050M72 HRL36050M72 3606486282991
1682.86 / EA
http://schema.org/OutOfStock
  • Country of Origin: USA
  • Depth: 86 mm
  • Height: 163 mm
  • Length: 16 mm
  • Net Weight: 2.2 kg
  • Weight: 2.2 kg
  • Width: 104 mm
PowerPacT H-Frame motor circuit protectors (MCP) are instantaneous-trip circuit breakers designed to offer short circuit protection for motors. The unique design of the PowerPacT MCPs accommodates transient motor inrush current without nuisance tripping. This PowerPacT H, 50A, 3 pole, motor protector has a breaking capacity of 100kA at 600VAC. This unit has lugs on both the line and load side. These motor protectors accept the same accessories and terminals as PowerPacT H circuit breakers. This breaker has a continuous current rating of 80%. PowerPacT H motor circuit protectors comply to UL, CSA, and IEC standards and are CE marked.
QTY
  • Product Description
  • Features
  • Specifications
PowerPacT H-Frame motor circuit protectors (MCP) are instantaneous-trip circuit breakers designed to offer short circuit protection for motors. The unique design of the PowerPacT MCPs accommodates transient motor inrush current without nuisance tripping. This PowerPacT H, 50A, 3 pole, motor protector has a breaking capacity of 100kA at 600VAC. This unit has lugs on both the line and load side. These motor protectors accept the same accessories and terminals as PowerPacT H circuit breakers. This breaker has a continuous current rating of 80%. PowerPacT H motor circuit protectors comply to UL, CSA, and IEC standards and are CE marked.
  • Prop 65
    • WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
  • Specifications
    • Country of Origin : United States
    • Length : 16 mm
    • Width : 104 mm
    • Height : 163 mm
    • Weight : 2.2 kg
    • Product Or Component Type : Motor Circuit Protector
    • Product Name : PowerPact H
    • Range : PowerPact
    • Device Application : distribution
  • Environmental data
    • Rohs Exemption Information : Yes
    • Mercury Free : Yes
    • Environmental Disclosure : ENVPEP2206028EN
    • Reach Regulation : Reference contains Substances of Very High Concern above the threshold
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • China Rohs Regulation : Product out of China RoHS scope. Substance declaration for your information.
    • Circularity Profile : ENVEOLI2206028EN
    • Take-Back : No
    • Pvc Free : Yes
    • Global Warming ; Total Life Cycle​ : 455 kg CO2 eq.
    • Eu Rohs Directive : Compliant with Exemptions
    • Carbon Footprint (Kg Co2 Eq, Total Life Cycle) : 455.357767105
  • Complementary
    • Mounting Mode : unit mount lug)
    • Network Frequency : 50/60 Hz
    • Terminal Identifier : AL150HD
    • [Ics] Rated Service Breaking Capacity : 150 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 125 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 75 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 690 V AC 50/60 Hz IEC 60947-2
    • [Ith] Conventional Free Air Thermal Current : 14-42 A
    • Trip Unit Technology : thermal-magnetic
    • Height : 163 mm
    • [Ue] Rated Operational Voltage : 690 V AC 50/60 Hz IEC 60947-3
    • Tightening Torque : 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
    • Mounting Support : lug
    • Breaking Capacity Code : R
    • Magnetic Tripping Current : 84-546 A
    • Protected Poles Description : 3t
    • Number Of Slots : 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
    • Electrical Connection : lugs, line || lugs, load
    • Net Weight : 2.2 kg
    • [Uimp] Rated Impulse Withstand Voltage : 8 kV IEC 60947-2
    • Control Type : toggle
    • Wire Stripping Length : 16 mm
    • Line Rated Current : 50-50 A
    • Utilisation Category : category A
    • Continuous Current Rating : 80 %
    • Breaking Capacity : 200 kA 240 V AC 50/60 Hz UL 489 || 200 kA 480 V AC 50/60 Hz UL 489 || 100 kA 600 V AC 50/60 Hz UL 489
    • [Ui] Rated Insulation Voltage : 750 V IEC 60947-2
    • Suitability For Isolation : yes IEC 60947-2
    • Communication Interface : Modbus || Ethernet
    • Poles Description : 3P
    • Quantity Per Set : 1
    • Awg Gauge : AWG 14...AWG 3/0 aluminium/copper terminal
    • Color : Black
    • Width : 104 mm
    • Depth : 86 mm
  • Environment
    • Ambient Air Temperature For Operation : -25-70 °C
    • Standards : UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
    • Product Certifications : UL || CSA || NOM
    • Ip Degree Of Protection : front cover IP40 IEC 60529
    • Pollution Degree : 3 IEC 60947-1
    • Ambient Air Temperature For Storage : -50-85 °C
    • Quality Labels : CE
    • Operating Altitude : < 6561.68 ft (2000 m) without derating || 5000 m with derating