Circuit breaker, PowerPacT L, 400A, 3 pole, 500VDC, 50kA, lugs, thermal magnetic, 80%

CIRCUIT BREAKER, POWERPACT L,

SQDLLL37040D30 LLL37040D30 3606486284100
11347.06 / EA
http://schema.org/OutOfStock
  • Depth: 110 mm
  • Warranty Length: 18 mth
PowerPacT L-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT L-Frame circuit breakers are available with electronic trip units. All PowerPacT L-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT L circuit breakers are available in 3 and 4-pole unit mount, I-Line, and drawout constructions. This PowerPacT L, 400A, 3 pole, circuit breaker has an interrupting rating of 50kA at 500VDC. This circuit breaker has a fixed long time electronic trip unit. This unit has lugs on both the line and load sides. This circuit breaker has a continuous current rating of 80%. PowerPacT L circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
QTY
  • Product Description
  • Features
  • Specifications
PowerPacT L-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT L-Frame circuit breakers are available with electronic trip units. All PowerPacT L-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT L circuit breakers are available in 3 and 4-pole unit mount, I-Line, and drawout constructions. This PowerPacT L, 400A, 3 pole, circuit breaker has an interrupting rating of 50kA at 500VDC. This circuit breaker has a fixed long time electronic trip unit. This unit has lugs on both the line and load sides. This circuit breaker has a continuous current rating of 80%. PowerPacT L circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
  • Features
    • Available in 3 or 4 pole design
    • Protection from overloads and short circuits
    • Common accessories across the range
    • Used as main panel disconnect for control panel
    • UL 489 Listed, CSA, NEMA, NMX, VDE, BS, CCC, IEC certified, and CE marked
    • The PowerPact L-frame circuit breaker is compliant with standards IEC 60947-2 and UL 508/CSA 22.3 N°14, with UL 489.
  • Prop 65
    • WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
  • Communications & Management Attributes
    • Communication Interface : Modbus, Ethernet
  • Physical Attributes
    • Wire Stripping Length : 31 mm, 61 mm
    • Color : Black
  • Conformance Attributes
    • Product Certifications : UL, CSA, NOM
    • Standards : UL, CSA, NEMA, NOM-003-SCFI-2000, IEC 60947-2
  • Important Information Attributes
    • Persona Type Ids : LC, OM, OM8, PB
    • Persona Type Names : Contractor, Original Equipment Manufacturer, OEM - Control Panelbuilder, Panel Builder
    • Market Segmentation Id : COMMERCIAL, INDUSTRIAL
    • Market Segmentation : Commercial, Industrial
    • Electrical Connection : lugs, line, lugs, load
    • Ics Rated Service Breaking Capacity2 : 125 kA 220/240 V AC 50/60 Hz IEC 60947-2, 100 kA 380/440/415 V AC 50/60 Hz IEC 60947-2, 50 kA 500/525 V AC 50/60 Hz IEC 60947-2, 20 kA 250 V DC IEC 60947-2, 20 kA 500 V DC IEC 60947-2
    • Carbon Footprint Of The Distribution Phase A4 : 1.966271580566898, 2 kg CO2 eq.
    • Carbon Footprint Of The End Of Life Phase C1 To C4 : 10 kg CO2 eq., 10.302971150240523
    • Carbon Footprint Of The Installation Phase A5 : 1.8967904693791804, 2 kg CO2 eq.
    • Carbon Footprint Of The Manufacturing Phase A1 To A3 : 44 kg CO2 eq., 43.82880551360121
    • Carbon Footprint Of The Use Phase B2 B3 B4 B6 : 1 005 kg CO2 eq., 1005.3828384868019
    • Ics Rated Service Breaking Capacity5 : 125 kA 220/240 V AC 50/60 Hz IEC 60947-2, 100 kA 380/440/415 V AC 50/60 Hz IEC 60947-2, 50 kA 500/525 V AC 50/60 Hz IEC 60947-2, 20 kA 250 V DC IEC 60947-2, 20 kA 500 V DC IEC 60947-2
    • Local Data Status : Publishable
    • Local Publishable Date : 2025-11-18
    • Device Type : LV equipment - Low voltage circuit breaker
    • Serviceability : No
    • Traceability : Yes
    • Field Service Division : PPIBS
    • Average Life Duration : 15 year(s)
    • Legacy WEEE Scope : In
    • Scope Perimeter : At least in Europe
    • EOLI Availability Display : Yes
    • End Of Life Doc Ref : ENVEOLI2206029_V2
    • Reach Full Compliance Status : Reference contains Substances of Very High Concern above the threshold
    • Reach Full Compliance Status Id : CONTAINS_SVHC
    • Reach Compliance Directive : Reference contains Substances of Very High Concern above the threshold
    • ROHS EUR In Scope : Yes
    • ROHS EUR Status : Compliant with Exemptions
    • ROHS EUR Full Compliance Status : Compliant with Exemptions
    • ROHS EUR Full Compliance Status Id : COMPLIANT_WITH_EXEMPTIONS
    • China ROHS In Scope : No
    • Green Premium Status For Reporting : Green Premium product
    • With Recycled Cardboard : Yes
    • Without Single Use Plastic : No
    • Product Contributes To Saved And Avoided Emissions : No
    • Return Indicator : Y
    • Function Option Id : STANDARD
    • Function Option : Standard
    • AWG Gauge : 2 x AWG 2/0...500 kcmil aluminium/copper
    • Circuit Breaker Application : HACR rated
    • Control Type : toggle
    • Device Application : distribution
    • Device Short Name : L-Frame
    • Energy Efficiency Optimized : False
    • Local Signalling : switched off (OFF) 1 trip indicator green)
    • Magnetic Tripping Current : 1000-2000 A
    • Mounting Mode : unit mount lug)
    • Mounting Support : lug
    • Package Weight Lbs : 6.804 kg
    • Poles Description : 3P
    • Product Availability : Stock - Normally stocked in distribution facility
    • Product Or Component Type : circuit breaker
    • Range : PowerPact
    • Returnability : Yes
    • Suitability For Isolation : yes IEC 60947-2
    • Sustainable Packaging : No
    • Terminal Identifier : AL600LS52K3
    • Tightening Torque : 50-50 N.m 70-240 mm² (2 x AWG 2/0...500 kcmil)
    • Total Lifecycle Carbon Footprint : 1 063 kg CO2 eq.
    • Trip Unit Technology : thermal-magnetic
    • Utilisation Category : category A
    • Weee Label : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Ue Rated Operational Voltage2 : 500 V DC
    • Ui Rated Insulation Voltage2 : 750 V IEC 60947-2
    • Uimp Rated Impulse Withstand Voltage2 : 8 kV IEC 60947-2
    • Medium Desc : Circuit breaker, PowerPacT L, 400A, 3 pole, 500VDC, 50kA, lugs, thermal magnetic, 80%
    • Stocking Flag : N
    • Product Kit Identifier : N
    • Pep Code : ENVPEP2206029EN
    • Database Version : 2024-01
    • Pep Verification Date : 2027-09-06
    • Pcr Version : PEP-PCR-ed4-2021 09 06
    • Psr Version : PSR-0005-ed3.1-EN-2023 12 08
    • Type Of Verification For The Pep : Independent external review
    • Data Source : extrapolated product
    • Functional Unit Description : Protect the installation from overloads and short circuits in a circuit with rated voltage Ue, rated current In, with Np poles, a rated breaking capacity Icu, and, if applicable, the specific specifications, in the Industrial application area, according to the appropriate use scenario, and during the reference service life of the product of 20 years.
    • Functional Unit Unit : unit
    • Energy Model Manufacturing A1 A3 2 : Electricity Mix; Low voltage; 2020; United States, US
    • Energy Model Installation A5 2 : No energy used
    • Energy Model Use B6 2 : Electricity Mix; Low voltage; 2020; United States, US
    • Energy Model End Of Life C1 C4 2 : Global, European and French datasets are used.
    • Global Commercial Status : Commercialised
    • Product Name : PowerPact L
    • Ue Rated Operational Voltage5 : 500 V DC
    • Ui Rated Insulation Voltage5 : 750 V IEC 60947-2
    • Uimp Rated Impulse Withstand Voltage5 : 8 kV IEC 60947-2
  • Environment Attributes Main
    • China ROHS Regulation : Product out of China RoHS scope , Product out of China RoHS scope. Substance declaration for your information.
    • EU ROHS Directive : Compliant By Exemption , Compliant with Exemptions
    • Operating Altitude : < 6561.68 ft (2000 m) without derating, < 6561.68 ft (2000 m) without derating, < 6561.68 ft (2000 m) without derating, < 6561.68 ft (2000 m) without derating, 5000 m with derating
    • ROHS Exemption Information : Yes
    • Take Back : No
    • Recycled Metal Content At Cr Level : 0 %
    • Mercury Free : Yes
    • Carbon Footprint : 1063.37767720059
    • Ambient Air Temperature For Operation : -25-70 °C
    • Ambient Air Temperature For Storage : -50-85 °C
    • Circularity Profile : ENVEOLI2206029_V2
    • Environmental Disclosure : ENVPEP2206029EN
    • IP Degree Of Protection : front cover IP40
    • Packaging Made With Recycled Cardboard : Yes
    • Packaging Without Single Use Plastic : No
    • Reach Regulation : Reference contains Substances of Very High Concern above the threshold
    • Pep Code : ENVPEP2206029EN
    • Pep Verification Date : 2027-09-06
    • Pcr Version : PEP-PCR-ed4-2021 09 06
    • Psr Version : PSR-0005-ed3.1-EN-2023 12 08
    • Type Of Verification For The Pep : Independent external review
  • General Attributes
    • Product Or Component Type : circuit breaker
  • Contractual Warranty Attributes
    • Warranty Period : 18 months
    • Warranty : 18 months
  • Specifications
    • Depth : 110 mm