Schneider Electric at Mayer

switch disconnector, Compact INS400, 400A, standard version with black rotary handle, 4 poles

CIRCUIT BREAKER INS400 4P

SQD31111 31111 3303430311119
1177.77 / EA
http://schema.org/OutOfStock
  • Country of Origin: USA
  • Depth: 120 mm
  • Handle Color: Black
  • Height: 205 mm
  • Net Weight: 4.9 kg
  • Warranty Length: 18 mth
  • Weight: 4.9 kg
  • Width: 185 mm
This Compact INS400 is a 4 poles non-automatic switch-disconnector with black rotary handle. It is suitable for isolation with positive contact indication, as defined by IEC 60947-1 and IEC60947-3 standards. The operational current is 400A at 415VAC in categories AC22A and AC23A. The rated voltage is 690VAC 50/60Hz or 250VDC. The black rotary handle is designed to offer easy operation and high performance in interruption of currents. Compact INS400 is a class II insulation level front-face device as per IEC 60664 standard.
QTY
  • Product Description
  • Features
  • Specifications
This Compact INS400 is a 4 poles non-automatic switch-disconnector with black rotary handle. It is suitable for isolation with positive contact indication, as defined by IEC 60947-1 and IEC60947-3 standards. The operational current is 400A at 415VAC in categories AC22A and AC23A. The rated voltage is 690VAC 50/60Hz or 250VDC. The black rotary handle is designed to offer easy operation and high performance in interruption of currents. Compact INS400 is a class II insulation level front-face device as per IEC 60664 standard.
  • Prop 65
    • WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
  • Environment
    • Product Certifications : KEMA-KEUR || CCC
    • Ik Degree Of Protection : IK07 conforming to EN 50102
    • Ambient Air Temperature For Operation : -25-70 °C
    • Standards : IEC 60947-1 || IEC 60947-3
    • Ip Degree Of Protection : IP40 conforming to IEC 60529
    • Ambient Air Temperature For Storage : -50-85 °C
  • Contractual warranty
    • Warranty : 18 months
  • Environmental data
    • Packaging Made With Recycled Cardboard : Yes
    • Environmental Disclosure : ENVPEP1304025
    • Packaging Without Single Use Plastic : No
    • Scip Number : bbc62998-8aa6-42dc-8088-17a5c936153d
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Circularity Profile : ENVEOLI1304025
    • Take-Back : No
    • Carbon Footprint (Kg Co2 Eq, Total Life Cycle) : 483.5351550764628
  • Complementary
    • Height : 205 mm
    • Connection Pitch : 45 mm
    • Mounting Support : rail || plate
    • Downside Connection : front
    • Handle Colour : black
    • Net Weight : 4.9 kg
    • Control Type : direct front rotary handle
    • Upside Connection : front
    • Mounting Mode : fixed
    • Electrical Durability : AC-22A 1500 cycles 440 V AC 50/60 Hz || AC-22A 1500 cycles 500 V AC 50/60 Hz || AC-22A 1500 cycles 690 V AC 50/60 Hz || AC-23A 1500 cycles 440 V AC 50/60 Hz || AC-23A 1500 cycles 500 V AC 50/60 Hz || AC-23A 1500 cycles 690 V AC 50/60 Hz || DC-23A 1000 cycles 250 V DC 4 poles in series
    • Mechanical Durability : 10000 cycles
    • Width : 185 mm
    • Depth : 120 mm
    • [Icw] Rated Short-Time Withstand Current : 11.5 kA 3 s IEC 60947-3 || 20 kA 1 s IEC 60947-3 || 4 kA 30 s IEC 60947-3 || 4.9 kA 20 s IEC 60947-3
    • Rated Duty : uninterrupted
    • Maximum Power : AC-23 110 kW 220/240 V AC 50/60 Hz || AC-23 110 kW 230 V AC 50/60 Hz NEMA) || AC-23 200 kW 380/415 V AC 50/60 Hz || AC-23 220 kW 440 V AC 50/60 Hz || AC-23 220 kW 480 V AC 50/60 Hz NEMA) || AC-23 250 kW 500/525 V AC 50/60 Hz || AC-23 400 kW 660/690 V AC 50/60 Hz
  • Specifications
    • Country of Origin : United States
    • Width : 185 mm
    • Height : 205 mm
    • Weight : 4.9 kg
    • Network Frequency : 50/60 Hz
    • [Ith] Conventional Free Air Thermal Current : 400 A 60 °C
    • [Ue] Rated Operational Voltage : 250 V DC || 690 V AC 50/60 Hz
    • Contact Position Indicator : yes
    • Network Type : DC || AC
    • Visible Break : no
    • Product Or Component Type : switch disconnector
    • Product Name : ComPacT INS
    • Range : ComPact
    • Pollution Degree : 3
    • [Icm] Rated Short-Circuit Making Capacity : 330 kA with upstream protection circuit breaker 690 V AC 50/60 Hz || 50 kA switch-disconnector alone 690 V AC 50/60 Hz
    • [Ui] Rated Insulation Voltage : 800 V AC 50/60 Hz
    • Suitability For Isolation : yes
    • [Ie] Rated Operational Current : AC-22A 400 A AC 50/60 Hz 220/240 V || AC-22A 400 A AC 50/60 Hz 380/415 V || AC-22A 400 A AC 50/60 Hz 440/480 V || AC-22A 400 A AC 50/60 Hz 480 V NEMA || AC-22A 400 A AC 50/60 Hz 500/525 V || AC-22A 400 A AC 50/60 Hz 660/690 V || AC-23A 400 A AC 50/60 Hz 220/240 V || AC-23A 400 A AC 50/60 Hz 380/415 V || AC-23A 400 A AC 50/60 Hz 440/480 V || AC-23A 400 A AC 50/60 Hz 480 V NEMA || AC-23A 400 A AC 50/60 Hz 500/525 V || AC-23A 400 A AC 50/60 Hz 660/690 V || DC-22A 400 A DC 125 V 2 poles in series || DC-22A 400 A DC 250 V 4 poles in series || DC-23A 400 A DC 125 V 2 poles in series || DC-23A 400 A DC 250 V 4 poles in series
    • Poles Description : 4P
    • [Uimp] Rated Impulse Withstand Voltage : 8 kV || 8 kVIEC 60947-3