Residual current protection relay, VigiPacT RH10P, 30mA, 220/240VAC 50/60Hz, front panel mounting

RESIDUAL CURRENT PROTECTION RE

SQD56230 56230 3303430562306
1577.23 / EA
http://schema.org/OutOfStock
  • Depth: 78 mm
  • Warranty Length: 18 mth
VigiPacT RH10P is a front panel mounting residual current protection relay. It protects against people direct or indirect contact, property fire hazards and motors. It measures the earth leakage current in an electrical installation via its associated toroid. It trips the associated circuit breaker when the set residual operation current is overrun. The operational supply voltage is 220/240VAC 50/60Hz. It is a type A earth-leakage protection class. The current sensitivity (IDn) is fixed to 30mA. The time delay (Dt) is instantaneous. It requires a local manual reset after a fault clearance. The monitored distribution system voltage is up to 1000VAC 50/60/400Hz. It is installed on a front panel switchboard and the protection degree is IP40. It must be associated with a compatible Schneider Electric type A toroid or rectangular sensor.
QTY
  • Product Description
  • Features
  • Specifications
VigiPacT RH10P is a front panel mounting residual current protection relay. It protects against people direct or indirect contact, property fire hazards and motors. It measures the earth leakage current in an electrical installation via its associated toroid. It trips the associated circuit breaker when the set residual operation current is overrun. The operational supply voltage is 220/240VAC 50/60Hz. It is a type A earth-leakage protection class. The current sensitivity (IDn) is fixed to 30mA. The time delay (Dt) is instantaneous. It requires a local manual reset after a fault clearance. The monitored distribution system voltage is up to 1000VAC 50/60/400Hz. It is installed on a front panel switchboard and the protection degree is IP40. It must be associated with a compatible Schneider Electric type A toroid or rectangular sensor.
  • Prop 65
    • WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
  • Physical Attributes
    • Wire Stripping Length : auxiliary power supply: 7 mm, fault: 7 mm, relay test and fault reset: 7 mm, sensor: 7 mm, voltage presence: 7 mm
  • Conformance Attributes
    • Standards : EN/IEC 60947-2 Annex M, EN/IEC 60755, UL 1053, CAN/CSA C22.2 No. 144
  • Complementary Attributes
    • Network Rated Voltage : 1000-1000 V - AC 50/60 Hz maximum), 1000-1000 V - AC 400 Hz maximum)
    • Minimum Load : 10 mA 12 V
    • Uimp Rated Impulse Withstand Voltage : 8 kV
    • Us Rated Supply Voltage : 220...240 V AC 50/60 Hz 55...110 %
  • Important Information Attributes
    • Persona Type Ids : LC, PB
    • Persona Type Names : Contractor, Panel Builder
    • Market Segmentation Id : COMMERCIAL, INDUSTRIAL
    • Market Segmentation : Commercial, Industrial
    • Earthing System : TN-S, TT, IT
    • Electromagnetic Compatibility : conducted and radiated emissionsB CISPR 11, conducted radio-frequency immunity test3 IEC 61000-4-6, electrostatic discharge immunity test4 IEC 61000-4-2, high-energy conducted susceptibility4 IEC 61000-4-5, low-energy conducted susceptibility4 IEC 61000-4-4, radiated susceptibility3 IEC 61000-4-3
    • Mechanical Robustness : fire resistance IEC 60695-2-1, IK protection 2 joulesIK07 EN 50102, vibrations 13.2...100 Hz0.7 g, vibrations 2...13.2 Hz+/- 1 mm
    • Monitoring : electronics continuous), power supply continuous), relay/sensor link continuous)
    • Test Function : remote test, local
    • Tightening Torque : auxiliary power supply: 0.6-0.6 N.m, fault: 0.6-0.6 N.m, relay test and fault reset: 0.6-0.6 N.m, sensor: 0.6-0.6 N.m, voltage presence: 0.6-0.6 N.m
    • Connections Terminals : fault terminal block 0.2-2.5 mm² rigid AWG 24...AWG 12, fault terminal block 0.25-2.5 mm² flexible AWG 24...AWG 12, relay test and fault reset terminal block 0.2-2.5 mm² rigid AWG 24...AWG 12, relay test and fault reset terminal block 0.25-2.5 mm² flexible AWG 24...AWG 12, sensor terminal block 0.2-2.5 mm² rigid AWG 24...AWG 12, sensor terminal block 0.25-2.5 mm² flexible AWG 24...AWG 12, voltage presence terminal block 0.2-2.5 mm² rigid AWG 24...AWG 12, voltage presence terminal block 0.25-2.5 mm² flexible AWG 24...AWG 12, auxiliary power supply terminal block 0.2-2.5 mm² flexible AWG 24...AWG 12, auxiliary power supply terminal block 0.2-2.5 mm² rigid AWG 24...AWG 12, auxiliary power supply terminal block 0.25-2.5 mm² flexible AWG 24...AWG 12, fault terminal block 0.2-2.5 mm² flexible AWG 24...AWG 12, relay test and fault reset terminal block 0.2-2.5 mm² flexible AWG 24...AWG 12, sensor terminal block 0.2-2.5 mm² flexible AWG 24...AWG 12, voltage presence terminal block 0.2-2.5 mm² flexible AWG 24...AWG 12
    • Carbon Footprint Of The Distribution Phase A4 : 0.0425004718576786, 0 kg CO2 eq.
    • Carbon Footprint Of The End Of Life Phase C1 To C4 : 0.7932315093336639, 0.8 kg CO2 eq.
    • Carbon Footprint Of The Installation Phase A5 : 0.1 kg CO2 eq., 0.07089832583983828
    • Carbon Footprint Of The Manufacturing Phase A1 To A3 : 3 kg CO2 eq., 2.7233847194703524
    • Carbon Footprint Of The Use Phase B2 B3 B4 B6 : 46 kg CO2 eq., 46.31700000000001
    • Medium Desc : Residual current protection relay, VigiPacT RH10P, 30mA, 220/240VAC 50/60Hz, front panel mounting
    • Local Data Status : Publishable
    • Local Publishable Date : 2025-07-10
    • Global Commercial Status : Commercialised
    • Return Indicator : N
    • Stocking Flag : Y
    • Device Type : Relay, Control & Measurement - Protection relay
    • Serviceability : Yes
    • Traceability : Yes
    • Field Service Division : PPIBS
    • Average Life Duration : 15 year(s)
    • Weee Applicability : Finished product
    • Weee Scope : In
    • Legacy Weee Scope : In
    • Scope Perimeter : At least in Europe
    • Eoli Availability Display : Yes
    • End Of Life Doc Ref : ENVEOLI2310023EN
    • Reach Full Compliance Status : Reference contains Substances of Very High Concern above the threshold
    • Reach Full Compliance Status Id : CONTAINS_SVHC
    • Reach Compliance Directive : Reference contains Substances of Very High Concern above the threshold
    • Rohs Eur In Scope : Yes
    • Rohs Eur Status : Compliant By Exemption
    • Rohs Eur Full Compliance Status : Compliant By Exemption
    • China Rohs In Scope : No
    • With Recycled Cardboard : Yes
    • Without Single Use Plastic : No
    • Product Contributes To Saved And Avoided Emissions : No
    • Function Option Id : STANDARD
    • Function Option : Standard
    • Product Kit Identifier : N
    • Compatibility Code : RH10P
    • Cut Out Dimensions : 68 x 68 mm
    • Device Short Name : RH10P
    • Earth Leakage Current : 0.03-0.03 A
    • Earth Leakage Protection Class : type A
    • Electrical Shock Protection Class : class II
    • Energy Efficiency Optimized : False
    • Halogen Free Status : Product contains halogen above thresholds
    • Mounting Support : front panel
    • Overvoltage Category : IV
    • Power Consumption In Va : 4 VA
    • Product Availability : Non-Stock - Not normally stocked in distribution facility
    • Product Or Component Type : residual current protection relay
    • Range : VigiPacT
    • Relay Application : protection relay
    • Reset : manual reset
    • Residual Earth Leakage Sensitity Adjustment Type : fixed
    • Residual Earth Leakage Time Delay Adjustment Type : instantaneous
    • Returnability : No
    • Software Version : v5.9.4
    • Sustainable Packaging : No
    • Tamperproof Of Settings : protected by sealable cover
    • Total Lifecycle Carbon Footprint : 50 kg CO2 eq.
    • Type Of Measurement : earth fault current internal measurement 80...100 %
    • Type Of Setting : none
    • Weee Label : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Ithe Conventional Enclosed Thermal Current : 8 A
    • Supply Voltage Num 7 Network Type : AC
    • Supply Voltage Num 7 Supply Voltage Num : 220...240 V
    • R Earth Leakage Current 1 R Earth Leakage Current : 0.03-0.03 A
    • Pep Code : ENVPEP2310023EN
    • Database Version : 2022-01
    • Pep Verification Date : 2023-12-05
    • Pcr Version : PEP-PCR-ed4-2021 09 06
    • Psr Version : PSR-0005-ed2-2016 03 29
    • Type Of Verification For The Pep : Independent external review
    • Data Source : extrapolated product
    • Functional Unit Description : Protect during 10 years people and premises at risk of fire or explosion with assigned voltage 220-240V by detecting and measuring the earth leakage current sensitivity is selectable with 9 thresholds from 30 mA to 30 A.
    • Functional Unit Unit : Unit
    • Energy Model Manufacturing A1 A3 2 : Electricity Mix; Production mix; Low voltage; FR
    • Energy Model Installation A5 2 : Electricity Mix; Production mix; Low voltage; UE-27
    • Energy Model Use B6 2 : Electricity Mix; Production mix; Low voltage; UE-27
    • Energy Model End Of Life C1 C4 2 : Electricity Mix; Production mix; Low voltage; UE-27
    • Height Nominal : 72 mm
    • Width Nominal : 72 mm
  • Environment Attributes Main
    • China Rohs Regulation : Product out of China RoHS scope , Product out of China RoHS scope. Substance declaration for your information.
    • Ip Degree Of Protection : IP40 on front face: conforming to EN/IEC 60529, IP30 on side parts: conforming to EN/IEC 60529, IP20 on connection terminals: conforming to EN/IEC 60529
    • Take Back : Nej
    • Halogene Performance : Product contains halogen above thresholds
    • Recycled Metal Content At Cr Level : 0 %
    • Mercury Free : Yes
    • Carbon Footprint : 49.94701502650154
    • Ambient Air Temperature For Operation : -35-70 °C
    • Ambient Air Temperature For Storage : -55-85 °C
    • Circularity Profile : ENVEOLI2310023EN
    • Environmental Disclosure : ENVPEP2310023EN
    • Eu Rohs Directive : Compliant By Exemption
    • Halogen Content Performance : Product contains halogen above thresholds
    • Packaging Made With Recycled Cardboard : Yes
    • Packaging Without Single Use Plastic : No
    • Reach Regulation : Reference contains Substances of Very High Concern above the threshold
    • Relative Humidity : 95-95 % 55-55 °C
    • Pep Code : ENVPEP2310023EN
    • Pep Verification Date : 2023-12-05
    • Pcr Version : PEP-PCR-ed4-2021 09 06
    • Psr Version : PSR-0005-ed2-2016 03 29
    • Type Of Verification For The Pep : Independent external review
  • General Attributes
    • Product Or Component Type : residual current protection relay
  • ETIM
    • ETIM 8 : EC001445
    • ETIM 9 : EC001445
  • Contractual Warranty Attributes
    • Warranty Period : 18 months
    • Warranty : 18 months
  • Specifications
    • Depth : 78 mm