Electromechanical vacuum switch, 9016G, 9016 g, adjustable scale, 2 thresholds, Set 0 to 28.7 InHg

VACUUM SWITCH 480VAC 10 AMP G

SQD9016GAW1Z 9016GAW1Z 785901446248
365.59 / EA
http://schema.org/OutOfStock
  • Certifications: CSA File LR25490, UL Listed File E12158 CCN NKPZ And CCN NTHT
  • Depth: 4.56 in
  • Enclosure Material: Die Cast Aluminum
  • Height: 6.45 in
  • Line Rated Current: 0.22 A, 0.27 A, 120 V, 125 V, 240 V, 250 V, 3 A, 6 A
  • Net Weight: 4.6 lb
  • Standard: UL 508
  • Storage Temperature: 10-185 °F
  • Warranty Length: 18 mth
  • Width: 4.56 in
QTY
  • Specifications
  • Specifications
    • Range Of Product : 9016G
    • Product Or Component Type : electromechanical vacuum switch
    • Electrical Circuit Type : control circuit
    • Device Application : sensitive control application
    • Device Short Name : 9016G
  • Contractual warranty
    • Warranty : 18 months
  • Complementary
    • Repeat Accuracy : 0.4 %
    • Vacuum Sensor Size : 28.7 inHg
    • Height : 6.45 in
    • Pressure Actuator : diaphragm nitrile (Buna-N)
    • Terminal Block Type : 4 screw terminals
    • Short-Circuit Protection : 10 A cartridge overload and short-circuit protection gL
    • Maximum Pressure : 100 psi
    • Line Rated Current : 3 A 240 V AC A600 NEMA rating designation || 6 A 120 V AC A600 NEMA rating designation || 0.27 A 250 V DC R300 NEMA rating designation || 0.22 A 125 V DC R300 NEMA rating designation
    • Electrical Connection : screw-clamp terminals AWG 22...AWG 12
    • Contacts Type And Composition : NC-NO, SPDT, Form Z, snap action, silver nickel contacts
    • Materials In Contact With Fluid : 3M Scotch-Grip 847 rubber and gasket adhesive || nitrile (Buna-N) || zinc plated steel
    • Local Display : without
    • Net Weight : 4.6 lb(US)
    • Local Signalling : without
    • Maximum Permissible Pressure - Per Cycle : 100 psi
    • Fluid Connection Type : 0.25 inch 18 NPT UL 508
    • Vacuum Switch Type Of Operation : regulation between two thresholds
    • Maximum Operating Rate : 120 cyc/mn
    • Controlled Fluid : air -40-250 °F) || water -40-250 °F) || hydraulic oil -40-250 °F) || gas -40-250 °F)
    • Range On Decreasing Vacuum : 0-28.7 inHg
    • Approx Adjustable Differential At Mid Range : 1.3-7.4 inHg
    • Setting : internal
    • Scale Type : adjustable differential
    • Mechanical Durability : 5000000 cycles
    • Cable Entry : 0.5 inch NPT conduit entrance
    • Operating Position : any position
    • Enclosure Material : die cast aluminium alloy 380
    • Width : 4.56 in
    • Depth : 4.56 in
  • Offer Sustainability
    • Environmental Disclosure : ENVPEP111211EN
    • Reach Regulation : Reference contains Substances of Very High Concern above the threshold
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Diisononyl phthalate (DINP), which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
    • Circularity Profile : ENVEOLI111210EN
    • Eu Rohs Directive : Not applicable, out of EU RoHS legal scope
  • Environment
    • Product Certifications : CSA file LR25490 || UL listed file E12158 CCN NKPZ and CCN NTHT
    • Ambient Air Temperature For Operation : 10-185 °F
    • Standards : UL 508
    • Vibration Resistance : 2 gn 40-150 Hz)IEC 68-2-6
    • Shock Resistance : 50 gn IEC 58-2-27
    • Ambient Air Temperature For Storage : 10-185 °F
    • Nema Degree Of Protection : NEMA 4/4X/13 UL 698
    • Protective Treatment : none