primary_image

Relay module; Nominal input voltage: 115 V AC/DC; 1 changeover contact; Limiting continuous current: 6 A; Yellow status indicator; Module width: 6 mm; 2,50 mm²; gray

120 V 6 AMP TERM. BLK RELAY

WGO857357 857357 WGO857357
14.01 / EA
http://schema.org/OutOfStock
  • At Rated Voltage: 300 V
  • Conductor Size: 14 AWG, 2.5 mm
  • Contact Material: AgSnO2
  • Country of Origin: China
  • Height: 3.701 in, 94 mm
  • Mounting Type: DIN-35 Rail
  • Package Type: Box
  • Strip Length: 0.39 in, 10 mm
  • Weight: 32.180 g
  • Width: 0.236 in, 6 mm
QTY
  • Features
  • Specifications
  • Approvals
    • Brjansker Zertifizierungsstelle, EAC, EAC Ex 857 RU_C_DE.AZ_58_B_02148_21 nA nC, TP TC 012/2011
    • DEKRA EXAM GmbH, ATEX, BVS_14_ATEX_E_091_XII 3G Ex ec nC IIC T4 Gc; II 3G Ex ec IIC T4 Gc, EN 60079-0
    • CNEX, CCC, 2020312304000757, CNCA-C23-01
    • Brjansker Zertifizierungsstelle, EAC, EAC RU C-DE.AM02.B.00122/19, TP TC 004/2011
    • Underwriters Laboratories Inc., UL, E198726, UL 121201
    • UL International Netherlands B.V., UL, E175199 Sec.4, UL 508
    • DEKRA EXAM GmbH, IECEx, IECEX_BVS_14.0079X_Issue_3 Ex ec nC IIC T4 Gc; Ex ec IIC T4 Gc, IEC 60079-0
    • WAGO GmbH & Co. KG, UKEx, UKCA_WAGO22UKEX002X_ec nC, EN 60079-0
  • Basic Relay
    • WAGO Basic Relay : 857-155
  • Safety And Protection
    • Rated voltage : 300 V
    • Rated surge voltage : 4 kV
    • Type of circuits : Mains circuits
    • Overvoltage category : III
    • Pollution degree : 2
    • Dielectric strength (control/load circuit) (AC, 1 min) : 3.51 kVrms
    • Dielectric strength (open contact) (AC, 1 min) : 1 kVrms
    • Insulation type (control/load circuit) : Reinforced insulation (safe isolation)
    • Insulation type (between adjacent devices of the same type) : Double insulation (safe isolation)
    • Insulation type (to adjacent devices of different types) : Basic insulation
    • Safety information : Adjacent devices are devices of the same design (series) that are arranged next to each other with the same orientation on the mounting rail. An end stop (249-116) must be fitted to devices of other types for compliance with the reinforced insulation requirements.
    • Protection type : IP20
  • Load Circuit
    • Number of changeover/switchover contacts : 1
    • Contact material (relay) : AgSnO2
    • Limiting continuous current : 6 A
    • Inrush current (resistive) max. : (AC) 20 A / 0.02 s
    • Switching voltage (max.) : AC 250 V
    • Switching power (resistive) max. : AC 1500 VA; DC (see load limit curve)
    • Switching capacity : AC-15: 3 A / AC 250 V; DC-13: 2 A / DC 24 V
    • Recommended minimum load : 10 V / 10 mA; 24 V / 1 mA
    • Pull-in time (typ.) : 15 ms
    • Drop-out time (typ.) : 25 ms
    • Bounce time (typ.) : 3.5 ms
    • Electrical life (NO; resistive load; 23 °C) : 50 x 10³ switching operations
    • Mechanical life : 5 x 10⁶ switching operations
    • Switching frequency with/without load (max.) : 6 min-1 / 180 min-1
  • Environmental Requirements
    • Ambient temperature (operation at UN) : -40 … +60 °C
    • Ambient temperature (storage) : -40 … +70 °C
    • Processing temperature : -25 … +50 °C
    • Temperature range of connection cable : ≥ (Tambient + 30 K)
    • Relative humidity : 5 … 85 % (no condensation permissible)
    • Operating altitude (max.) : 2000 m
  • Connection Data
    • Connection technology : Push-in CAGE CLAMP®
    • Solid conductor : 0.34 … 2.5 mm² / 22 … 14 AWG
    • Fine-stranded conductor : 0.34 … 2.5 mm² / 22 … 14 AWG
    • Fine-stranded conductor; with insulated ferrule : 0.34 … 1.5 mm² / 22 … 16 AWG
    • Strip length : 9 … 10 mm / 0.35 … 0.39 inches
  • Control Circuit
    • Nominal input voltage UN : AC/DC 115 V
    • Input voltage range : ±20 %
    • Nominal input current at UN : 4 mA
    • Nominal frequency range (input voltage) : 50 … 60 HzAC / 0 HzDC
  • Physical Data
    • Width : 6 mm / 0.236 inches
    • Height : 94 mm / 3.701 inches
    • Depth from upper-edge of DIN-rail : 81 mm / 3.189 inches
  • Material Data
    • Color : Gray
    • Fire load : 0.552 MJ
    • Weight : 32.180 g
  • Standards And Specifications
    • Standards/specifications : EN 61010-2-201 || EN 61810-1 || EN 61373 || UL 508 || ATEX || IEC Ex
  • Mechanical Data
    • Mounting type : DIN-35 rail
    • Mounting position : Horizontal (standing/lying); vertical
  • Specifications
    • Product Group Code : 0006
  • Commercial Data
    • Packaging type : Box
    • Country of origin : CN
    • GTIN : 4055143656467
    • Customs tariff number : 85364900990
  • Notes
    • Safety information : Adjacent devices are devices of the same design (series) that are arranged next to each other with the same orientation on the mounting rail. An end stop (249-116) must be fitted to devices of other types for compliance with the reinforced insulation requirements.
    • Note : To protect the relay coils and contacts, inductive loads must be dampened with an effective protection circuit.
  • Signaling
    • Status indicator : Yellow LED