safety module, Harmony XPS, estop or guard, connected to supply terminals 48 to 240V AC or DC , no inputs, screw

ESTOP OR GUARD ,HARMONY XPS, C

SQDXPSBAC34AP XPSBAC34AP 3606482034020
214.23 / EA
http://schema.org/OutOfStock
  • Certifications: CULus, TÜV
  • Contact Configuration: 4 NO + 1 NC
  • Depth: 120 mm
  • Height: 100 mm
  • Net Weight: 0.200 kg
  • Number of Outputs: 0
  • Operating Temperature: -25-55 °C
  • Standard: IEC 60947-5-1, IEC 61508-1 Functional Safety Standard, IEC 61508-2 Functional Safety Standard, IEC 61508-3 Functional Safety Standard, IEC 61508-4 Functional Safety Standard, IEC 61508-5 Functional Safety Standard, IEC 61508-6 Functional Safety Standard, IEC 61508-7 Functional Safety Standard, IEC 62061 Functional Safety Standard, ISO 13849-1 Functional Safety Standard
  • Width: 22.5 mm
This safety relay is designed for monitoring Emergency stop and Guard switch. The safety relay is powered with 48-240V AC/DC, and equipped with a screw removable terminal block. This basic safety modules embeds pre-defined safety functions. This safety relay embeds 1 control output, 4 NO safety outputs, and 2 NC diagnostic outputs. The maximum safety level achieved by this safety relay is PLe/Category 4 conforming to ISO 13849-1, SILCL 3 conforming to IEC 62061, SIL 3 conforming to IEC 61508. This safety relay weighs 0,200kg. Its dimensions are 22,5mm (Width) x 120mm (Depth) x 100mm (Height). This safety relays is suitable for applications such as Food and Beverage, Hoisting, Material Handling, Material Working, Packaging. This safe relay conforms to IEC 60947-5-1, IEC 61508-1, IEC 61508-2/-3, ISO 13849-1, IEC 62061 functional safety standards, is certified by cULus, TÜV. Harmony safety relays are compatible with Modicon logic controllers. This relay is mounted on a 35mm symmetrical DIN rail. Harmony XPS Basic and Universal safety relays are the first choice for managing single safety functions easily, typically in machines of simple to medium complexity. Harmony XPS Basic offers the most optimised solution for applications with hardwired safety modules.
QTY
  • Product Description
  • Specifications
This safety relay is designed for monitoring Emergency stop and Guard switch. The safety relay is powered with 48-240V AC/DC, and equipped with a screw removable terminal block. This basic safety modules embeds pre-defined safety functions. This safety relay embeds 1 control output, 4 NO safety outputs, and 2 NC diagnostic outputs. The maximum safety level achieved by this safety relay is PLe/Category 4 conforming to ISO 13849-1, SILCL 3 conforming to IEC 62061, SIL 3 conforming to IEC 61508. This safety relay weighs 0,200kg. Its dimensions are 22,5mm (Width) x 120mm (Depth) x 100mm (Height). This safety relays is suitable for applications such as Food and Beverage, Hoisting, Material Handling, Material Working, Packaging. This safe relay conforms to IEC 60947-5-1, IEC 61508-1, IEC 61508-2/-3, ISO 13849-1, IEC 62061 functional safety standards, is certified by cULus, TÜV. Harmony safety relays are compatible with Modicon logic controllers. This relay is mounted on a 35mm symmetrical DIN rail. Harmony XPS Basic and Universal safety relays are the first choice for managing single safety functions easily, typically in machines of simple to medium complexity. Harmony XPS Basic offers the most optimised solution for applications with hardwired safety modules.
  • Complementary
    • Terminal Identifier : power supply
    • Number Of Outputs : 0
    • Height : 100 mm
    • Mounting Support : 35 mm symmetrical DIN rail
    • Minimum Output Voltage : 5 V relay output
    • Response Time : 60 ms at 48...240 V AC/DC
    • Minimum Output Current : 10 mA relay output
    • [Ith] Conventional Free Air Thermal Current : 6 A
    • Associated Fuse Rating : 10 A gG NO relay output circuit IEC 60947-1
    • Local Signalling : LED green power power ON || LED red error error || LED yellow state status || LED yellow start1 start input || LED yellow start2 start input
    • [Uimp] Rated Impulse Withstand Voltage : 4 kV II IEC 60947-1
    • Net Weight : 0.200 kg
    • Type Of Start : automatic/manual/monitored
    • Number Of Inputs : 0
    • Input Compatibility : normally closed circuit ISO 14119 || XC limit switch ISO 14119 || mechanical contact ISO 14119 || normally closed circuit ISO 13850
    • Power Consumption In Va : 6.0 VA 48...240 V AC 50/60 Hz
    • [Ie] Rated Operational Current : 5 A AC-1 for normally open relay contact || 3 A AC-15 for normally open relay contact || 5 A DC-1 for normally open relay contact || 3 A DC-13 for normally open relay contact || 3 A AC-1 for normally closed relay contact || 1 A AC-15 for normally closed relay contact || 3 A DC-1 for normally closed relay contact || 1 A DC-13 for normally closed relay contact
    • Auxiliary Contact Composition : 4 NO + 1 NC
    • [Ui] Rated Insulation Voltage : 300 V 2)IEC 60947-1
    • Power Consumption In W : 2.0 W 48...240 V DC
    • Input Protection Type : internal, electronic
    • Width : 22.5 mm
    • Depth : 120 mm
    • Synchronisation Time Between Inputs : unlimited
  • Specifications
    • [Us] Rated Supply Voltage : 48...240 V AC - 15...10 % || 48...240 V DC - 20...20 %
    • Range Of Product : Harmony Safety Automation
    • Product Or Component Type : safety module
    • Safety Module Name : XPSBAC
    • Connections - Terminals : removable screw terminal block, 0.2...2.5 mm² solid or flexible || removable screw terminal block, 0.25...2.5 mm² flexible with ferrule single conductor || removable screw terminal block, 0.2...1.5 mm² solid or flexible twin conductor || removable screw terminal block, 2 x 0.25...1 mm² flexible with ferrule without cable end, with bezel || removable screw terminal block, 2 x 0.5...1.5 mm² flexible with ferrule with cable end, with bezel
    • Safety Module Application : for emergency stop and protective guard applications
    • Safety Reliability Data : MTTFd > 30 years for normally open relay contact ISO 13849-1 || Dcavg >= 99 % for normally open relay contact ISO 13849-1 || PFHd = 1.01E-09 for normally open relay contact ISO 13849-1 || HFT = 1 for normally open relay contact IEC 62061 || PFHd = 1.01E-09 for normally open relay contact IEC 62061 || SFF > 99% for normally open relay contact IEC 62061 || HFT = 1 for normally open relay contact IEC 61508-1 || PFHd = 1.01E-09 for normally open relay contact IEC 61508-1 || SFF > 99% for normally open relay contact IEC 61508-1 || type = B for normally open relay contact IEC 61508-1 || MTTFd > 30 years for normally closed relay contact ISO 13849-1 || DC > 60 % for normally closed relay contact ISO 13849-1 || PFHd = 1.01E-09 for normally closed relay contact ISO 13849-1 || HFT=0 for normally closed relay contact IEC 62061 || PFHd = 1.01E-09 for normally closed relay contact IEC 62061 || SFF > 60% for normally closed relay contact IEC 62061 || HFT=0 for normally closed relay contact IEC 61508-1 || PFHd = 1.01E-09 for normally closed relay contact IEC 61508-1 || SFF > 60% for normally closed relay contact IEC 61508-1 || type = B for normally closed relay contact IEC 61508-1
    • Electrical Circuit Type : NC pair
    • Function Of Module : emergency stop button with 2 NC contacts || guard monitoring with 1 or 2 limit switches
    • Safety Level : can reach PL e/category 4 for normally open relay contact ISO 13849-1 || can reach SILCL 3 for normally open relay contact IEC 62061 || can reach SIL 3 for normally open relay contact IEC 61508 || can reach PL c/category 1 for normally closed relay contact ISO 13849-1 || can reach SILCL 1 for normally closed relay contact IEC 62061 || can reach SIL 1 for normally closed relay contact IEC 61508
  • Environment
    • Product Certifications : TÜV || cULus
    • Ambient Air Temperature For Operation : -25-55 °C
    • Ip Degree Of Protection : IP20 terminals)IEC 60529 || IP40 housing)IEC 60529 || IP54 mounting area)IEC 60529
    • Standards : IEC 60947-5-1 || IEC 61508-1 functional safety standard || IEC 61508-2 functional safety standard || IEC 61508-3 functional safety standard || IEC 61508-4 functional safety standard || IEC 61508-5 functional safety standard || IEC 61508-6 functional safety standard || IEC 61508-7 functional safety standard || ISO 13849-1 functional safety standard || IEC 62061 functional safety standard
    • Relative Humidity : 5-95 % non-condensing
  • Offer Sustainability
    • Rohs Exemption Information : Yes
    • Mercury Free : Yes
    • Environmental Disclosure : ENVPEP1811003EN
    • Sustainable Offer Status : Green Premium product
    • Reach Regulation : Reference contains Substances of Very High Concern above the threshold
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • China Rohs Regulation : X
    • Circularity Profile : ENVEOLI1811003EN
    • Eu Rohs Directive : Pro-active compliance (Product out of EU RoHS legal scope)