TELEMECANIQUE

analogue IO extension module, Zelio Logic SR2 SR3, 4 IO, 24V DC

ZELIO SR3 ANALOG OUTPUT 24VDC

SQDSR3XT43BD SR3XT43BD 3389119203968
268.46 / EA
http://schema.org/OutOfStock
  • Load Type: Resistive Analogue Output
  • Warranty Length: 18 mth
This Schneider Electric Zelio Logic SR3 Analog I/O Extension Module Smart Relays uses a supply voltage of 24 volts direct current, has 4 inputs / outputs contact with screw-clamp terminals. This Analog I/O Extension Module Smart Relays provides Zelio Logic relays with additional inputs and outputs. It has a compact form-factor, allowing installation on DIN rail. Simple ladder programming, adapted for non-specialists. Discovery package, coming with Zelio Soft programming software, the simplest way to learn and use this relay. Built-in EEPROM flash memory for data backup up to 10 years, easy-to-recover after a power shortage or incident. More I/O than SR2 model, for larger applications. This product meets EN/IEC 61000-4-12, EN/IEC 61000-4-5, EN/IEC 61000-4-3, EN/IEC 61000-4-4 level 3, EN/IEC 61000-4-6 level 3, EN/IEC 61000-4-2 level 3, EN/IEC 60068-2-6 Fc, EN/IEC 61000-4-11 and EN/IEC 60068-2-27 Ea standards. Simple to select, install and program, Zelio Logic is suitable for all your applications. Flexible, it offers you the choice of 2 ranges, compact or modular, extendable and 2 programming languages (FBD or LADDER). Easy to use, Zelio Logic provides a real alternative to solutions based on cabled logic or specific cards.
QTY
  • Features
  • Specifications
  • Prop 65
    • WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
  • Complementary Attributes
    • Maximum Altitude Transport : 3048 m
    • Maximum Load Current : 10 mA analogue output
    • Maximum Permissible Voltage : 30 V analogue input circuit
    • Imp Maximum Permanent Current : 30 mA analogue input circuit
  • Important Information Attributes
    • Persona Type Ids : EU, OM, OM8
    • Persona Type Names : End User, Original Equipment Manufacturer, OEM - Control Panelbuilder
    • Conversion Error : +/- 1 % of the full scale value 0...10 V 25 °C)analogue output, +/- 1 % of the full scale value 0...10 V 25 °C)analogue output, +/- 1 % of the full scale value 0...10 V 25 °C)analogue output, +/- 1 % of the full scale value 0...10 V 25 °C)analogue output, +/- 1 % of the full scale value 0...10 V 55 °C)analogue output, +/- 1 % of the full scale value 0...10 V 55 °C)analogue output, +/- 1 % of the full scale value 0...10 V 55 °C)analogue output, +/- 1 % of the full scale value 0...10 V 55 °C)analogue output, +/- 1 % 0...10 V 25 °C)analogue input circuit, +/- 1 % 0...10 V 25 °C)analogue input circuit, +/- 1 % 0...10 V 25 °C)analogue input circuit, +/- 1 % 0...10 V 25 °C)analogue input circuit, +/- 1 % 0...10 V 55 °C)analogue input circuit, +/- 1 % 0...10 V 55 °C)analogue input circuit, +/- 1 % 0...10 V 55 °C)analogue input circuit, +/- 1 % 0...10 V 55 °C)analogue input circuit, +/- 1 % 0...20 mA 25 °C)analogue input circuit, +/- 1 % 0...20 mA 25 °C)analogue input circuit, +/- 1 % 0...20 mA 25 °C)analogue input circuit, +/- 1 % 0...20 mA 25 °C)analogue input circuit, +/- 1 % 0...20 mA 55 °C)analogue input circuit, +/- 1 % 0...20 mA 55 °C)analogue input circuit, +/- 1 % 0...20 mA 55 °C)analogue input circuit, +/- 1 % 0...20 mA 55 °C)analogue input circuit, +/- 1.5 °C - 25...125 °C 25 °C)analogue input circuit, +/- 1.5 °C - 25...125 °C 25 °C)analogue input circuit, +/- 1.5 °C - 25...125 °C 25 °C)analogue input circuit, +/- 1.5 °C - 25...125 °C 25 °C)analogue input circuit, +/- 1.5 °C - 25...125 °C 55 °C)analogue input circuit, +/- 1.5 °C - 25...125 °C 55 °C)analogue input circuit, +/- 1.5 °C - 25...125 °C 55 °C)analogue input circuit, +/- 1.5 °C - 25...125 °C 55 °C)analogue input circuit, +/- 1 % of the full scale value 0...10 V 25 °C)analogue output, +/- 1 % of the full scale value 0...10 V 25 °C)analogue output, +/- 1 % of the full scale value 0...10 V 25 °C)analogue output, +/- 1 % of the full scale value 0...10 V 25 °C)analogue output, +/- 1 % of the full scale value 0...10 V 55 °C)analogue output, +/- 1 % 0...10 V 25 °C)analogue input circuit, +/- 1 % 0...10 V 25 °C)analogue input circuit, +/- 1 % 0...20 mA 25 °C)analogue input circuit, +/- 1.5 °C - 25...125 °C 25 °C)analogue input circuit, +/- 1.5 °C - 25...125 °C 25 °C)analogue input circuit
    • Conversion Time : smart relay cycle time analogue input circuit, smart relay cycle time analogue output
    • Environmental Characteristic : EMC directive conforming to IEC 61000-6-2, EMC directive conforming to IEC 61000-6-3, EMC directive conforming to IEC 61000-6-4, EMC directive conforming to IEC 61131-2 zone B, low voltage directive conforming to IEC 61131-2
    • Lsb Value : 0.15 °C, - 25...125 °C analogue input circuit, 20 µA, 0...20 mA analogue input circuit, 9.8 mV, 0...10 V analogue input circuit, 9.8 mV, 0...10 V analogue output
    • Operating Distance : 10 m with screened cable analogue input circuit, 10 m with screened cable analogue output
    • Repeat Accuracy : < +/- 0.3 °C - 25...125 °C 25 °C analogue input circuit, < +/- 0.3 °C - 25...125 °C 25 °C analogue input circuit, < +/- 0.3 °C - 25...125 °C 25 °C analogue input circuit, < +/- 0.3 °C - 25...125 °C 25 °C analogue input circuit, <= +/- 1 % 0...10 V 25 °C analogue input circuit, <= +/- 1 % 0...10 V 25 °C analogue input circuit, <= +/- 1 % 0...10 V 25 °C analogue input circuit, <= +/- 1 % 0...10 V 25 °C analogue input circuit, <= +/- 1 % 0...10 V 55 °C analogue output, <= +/- 1 % 0...10 V 55 °C analogue output, <= +/- 1 % 0...10 V 55 °C analogue output, <= +/- 1 % 0...10 V 55 °C analogue output, <= +/- 1 % 0...20 mA 25 °C analogue input circuit, <= +/- 1 % 0...20 mA 25 °C analogue input circuit, <= +/- 1 % 0...20 mA 25 °C analogue input circuit, <= +/- 1 % 0...20 mA 25 °C analogue input circuit, < +/- 0.3 °C - 25...125 °C 25 °C analogue input circuit, < +/- 0.3 °C - 25...125 °C 25 °C analogue input circuit, < +/- 0.3 °C - 25...125 °C 25 °C analogue input circuit, < +/- 0.3 °C - 25...125 °C 25 °C analogue input circuit, <= +/- 1 % 0...10 V 25 °C analogue input circuit, <= +/- 1 % 0...10 V 25 °C analogue input circuit, <= +/- 1 % 0...10 V 55 °C analogue output, <= +/- 1 % 0...10 V 55 °C analogue output, <= +/- 1 % 0...20 mA 25 °C analogue input circuit
    • Connections Terminals : screw terminals, 1 x 0.25...1 x 2.5 mm² AWG 24...AWG 14) semi-solid, screw terminals, 1 x 0.25...1 x 2.5 mm² AWG 24...AWG 14) solid, screw terminals, 2 x 0.25...2 x 1.5 mm² AWG 23...AWG 16) solid, screw terminals, 1 x 0.25...1 x 2.5 mm² AWG 24...AWG 14) flexible with cable end, screw terminals, 2 x 0.25...2 x 0.75 mm² AWG 24...AWG 18) flexible with cable end
    • Carbon Footprint Of The Distribution Phase A4 : 0.0135474706, 0 kg CO2 eq.
    • Carbon Footprint Of The End Of Life Phase C1 To C4 : 0.1 kg CO2 eq., 0.0829222059
    • Carbon Footprint Of The Installation Phase A5 : 0.0007746529, 0 kg CO2 eq.
    • Carbon Footprint Of The Manufacturing Phase A1 To A3 : 13 kg CO2 eq., 13.4396911765
    • Carbon Footprint Of The Use Phase B2 B3 B4 B6 : 103 kg CO2 eq., 103.008
    • Certificate Agency : GOST, UL, C-tick, CSA
    • Local Data Status : Publishable
    • Local Publishable Date : 2026-01-12
    • Return Indicator : Y
    • Stocking Flag : N
    • Stock Policy : 2
    • Device Type : PLC System - PLC Component
    • Serviceability : No
    • Traceability : Yes
    • Field Service Division : IDIBS
    • Use Carbon Footprint : 103.008
    • Weee Scope : In
    • Weee Product Category : 5
    • Scope Perimeter : At least in Europe
    • Eoli Availability Display : Yes
    • End Of Life Doc Ref : ENVEOLI2011013EN
    • Reach Full Compliance Status : Reference contains Substances of Very High Concern above the threshold
    • Reach Full Compliance Status Id : CONTAINS_SVHC
    • Reach Compliance Directive : Reference contains Substances of Very High Concern above the threshold
    • Rohs Eur In Scope : No
    • Rohs Eur Status : Compliant By Exemption
    • Rohs Eur Conformity Date : 1846
    • Rohs Eur Full Compliance Status : Compliant By Exemption
    • China Rohs In Scope : Yes
    • China Rohs Label : 5
    • With Recycled Cardboard : Yes
    • Without Single Use Plastic : Yes
    • Product Contributes To Saved And Avoided Emissions : No
    • Tier Id : 1
    • Tier : 1
    • Function Option Id : STANDARD
    • Function Option : Standard
    • Market Segmentation Id : INDUSTRIAL
    • Market Segmentation : Industrial
    • Product Kit Identifier : N
    • Disturbance Radiated Conducted : class B IEC 55022-11 Group 1
    • Load Type : resistive analogue output
    • Product Availability : Stock - Normally stocked in distribution facility
    • Product Or Component Type : analogue I/O extension module
    • Range Of Product : Zelio Logic
    • Returnability : Yes
    • Reverse Polarity Protection : analogue input circuit with
    • Short Circuit Protection : with analogue output
    • Software Version : EIME v5.6.0.1
    • Sustainable Packaging : Yes
    • Temperature Probe Type : Pt 100, 3-wire IEC 751
    • Tightening Torque : 0.5 N.m
    • Total Lifecycle Carbon Footprint : 117 kg CO2 eq.
    • Weee Label : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Imp Maximum Permanent Current : 30 mA analogue input circuit
    • Warranty In Months : 18
    • Pep Code : ENVPEP2011013EN
    • Database Version : 2016-11
    • Pep Verification Date : 2020-11-01
    • Pcr Version : PCR-ed3-EN-2015 04 02
    • Type Of Verification For The Pep : Independent internal review
    • Data Source : extrapolated product
    • Functional Unit Description : To provide automated control of simple systems from 10 to 40 I/O for 10 years 100% of the time.
    • Functional Unit Quantity : 1
    • Functional Unit Unit : unité (unit)
    • Reference Lifetime In Y2 : 10
    • Energy Consumption On Product Lifetime In Kwh : 210.24
    • Energy Model Manufacturing A1 A3 2 : Energy model used: France
    • Energy Model Installation A5 2 : Electricity mix; AC; < 1kV; EU-27
    • Energy Model Use B6 2 : Electricity mix; AC; < 1kV; EU-27
    • Energy Model End Of Life C1 C4 2 : Electricity mix; AC; < 1kV; EU-27
    • Offer Owner Code : 190786
    • Pn : 1
    • Depletion Of Abiotic Resources Fossil Fuels Mj Operational Energy Use B6 2 : 1169.2
    • Hazardous Waste Disposed Of Kg Operational Energy Use B6 2 : 0.0537
    • Net Use Of Fresh Water M3 Operational Energy Use B6 2 : 373.484
    • Non Hazardous Waste Disposed Of Kg Operational Energy Use B6 2 : 384.052
    • Total Use Of Non Renewable Primary Energy Resources Primary Energy And Primary Energy Resources Used As Raw Materials Mj Operational Energy Use B6 2 : 1795.64
    • Total Use Of Primary Energy During The Life Cycle Mj Operational Energy Use B6 2 : 2057.24
    • Total Use Of Renewable Primary Energy Resources Primary Energy And Primary Energy Resources Used As Raw Materials Mj Operational Energy Use B6 2 : 261.6
    • Use Of Non Renewable Primary Energy Excluding Non Renewable Primary Energy Resources Used As Raw Materials Mj Operational Energy Use B6 2 : 1795.64
    • Use Of Renewable Primary Energy Excluding Renewable Primary Energy Resources Used As Raw Materials Mj Operational Energy Use B6 2 : 261.6
    • Air Pollution M3 Operational Energy Use B6 2 : 4433.2
    • Water Pollution M3 Operational Energy Use B6 2 : 4250.4
    • Global Warming Kg Equivalent Co2 Operational Energy Use B6 2 : 103.008
  • Environment Attributes Main
    • Ambient Air Temperature For Operation : -20-40 °C IEC 60068-2-1 and IEC 60068-2-2, -20-40 °C IEC 60068-2-1 and IEC 60068-2-2, -20-55 °C IEC 60068-2-1 and IEC 60068-2-2, -20-55 °C IEC 60068-2-1 and IEC 60068-2-2, -20-40 °C IEC 60068-2-1 and IEC 60068-2-2, -20-40 °C IEC 60068-2-1 and IEC 60068-2-2
    • Ip Degree Of Protection : IP20 IEC 60529 terminal block), IP40 IEC 60529 front panel)
    • Take Back : No
    • Recycled Metal Content At Cr Level : 0 %
    • China Rohs Regulation : X
    • Mercury Free : Yes
    • Carbon Footprint : 116.5449355059
    • Ambient Air Temperature For Storage : -40-70 °C
    • Circularity Profile : ENVEOLI2011013EN
    • Environmental Disclosure : ENVPEP2011013EN
    • Eu Rohs Directive : Compliant By Exemption
    • Operating Altitude : 6561.68 ft (2000 m)
    • Packaging Made With Recycled Cardboard : Yes
    • Packaging Without Single Use Plastic : Yes
    • Reach Regulation : Reference contains Substances of Very High Concern above the threshold
    • Relative Humidity : 95-95 % without condensation or dripping water
    • Pep Code : ENVPEP2011013EN
    • Pep Verification Date : 2020-11-01
    • Pcr Version : PCR-ed3-EN-2015 04 02
    • Type Of Verification For The Pep : Independent internal review
  • General Attributes
    • Product Or Component Type : analogue I/O extension module
    • Range Of Product : Zelio Logic
  • ETIM
    • ETIM 8 : EC001417
    • ETIM 9 : EC001417
  • Output Attributes
    • Analogue Output Number : 2
    • Analogue Output Range : 0...10 V
    • Analogue Output Resolution : 10 bits on the output range
  • Contractual Warranty Attributes
    • Warranty Period : 18 months
    • Warranty : 18 months
  • Input Attributes
    • Analogue Input Range : 0...10 V, 0...20 mA, -25...125 °C
    • Input Impedance : 18 kOhm 0...10 V analogue input circuit, 247 Ohm 0...20 mA analogue input circuit
    • Analogue Input Number : 2
    • Analogue Input Resolution : 10 bits on the input range
    • Analogue Input Type : common mode
  • Specifications
    • Country of Origin : France, United States