current control relay, Harmony Control Relays, 5A, 1CO, overcurrent function, 250V AC DC

CURRENT RELAY 250V 5AMP RM17

SQDRM17JC00MW RM17JC00MW 3389119405034
133.98 / EA
http://schema.org/OutOfStock
  • Certifications: CSA, C-tick, GL, GOST, UL
  • Housing Material: Plastic
  • Net Weight: 0.13 kg
  • Operating Cycles: 360
  • Standard: IEC 60255-6
  • Storage Temperature: -40-70 °C
  • Warranty Length: 18 mth
  • Width: 17.5 mm
This Harmony RM17-J control relay allows monitoring of current control in 3-phase networks. This modular 3-phase control relay is ideal for monitoring of electrical values and current variation in industrial and building control panels. It applies to a wide type of industrial automation applications such as hoisting, packaging, lifts, textile, water. It has one of market slimmest form-factors with 17.5mm width, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 1-pole DIN device. It also offers a selectable memory function, integral LED for indicating control status, sealable cover, with simple and precise settings with screw trimmers. It provides automatic shutdown management and fault information to user for a quick fault identification and troubleshooting. Multi function controller for wide choice selected in hard-wired logic automated systems, ideal for refurbishment of old installations without using a PLC. 0 0 0 0 0 0 0 0 0 0 0 0
QTY
  • Product Description
  • Specifications
This Harmony RM17-J control relay allows monitoring of current control in 3-phase networks. This modular 3-phase control relay is ideal for monitoring of electrical values and current variation in industrial and building control panels. It applies to a wide type of industrial automation applications such as hoisting, packaging, lifts, textile, water. It has one of market slimmest form-factors with 17.5mm width, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 1-pole DIN device. It also offers a selectable memory function, integral LED for indicating control status, sealable cover, with simple and precise settings with screw trimmers. It provides automatic shutdown management and fault information to user for a quick fault identification and troubleshooting. Multi function controller for wide choice selected in hard-wired logic automated systems, ideal for refurbishment of old installations without using a PLC. 0 0 0 0 0 0 0 0 0 0 0 0
  • Environment
    • Product Certifications : GL || C-tick || GOST || UL || CSA
    • Standards : IEC 60255-6
    • Immunity To Microbreaks : 10 ms
    • Non-Dissipating Shock Wave : 4 kV
    • Dielectric Test Voltage : 2 kV AC 50 Hz
    • Electromagnetic Compatibility : emission standard for industrial environments conforming to IEC 61000-6-4 || emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3 || immunity for industrial environments conforming to NF EN/IEC 61000-6-2
    • Shock Resistance : 15 gn 11 ms IEC 60255-21-1
    • Ambient Air Temperature For Operation : -20-50 °C
    • Vibration Resistance : 0.35 mm 5-57.6 Hz)IEC 60068-2-6 || 1 gn 57.6-150 Hz)IEC 60255-21-1
    • Ip Degree Of Protection : IP20 IEC 60529 terminals) || IP30 IEC 60529 casing)
    • Pollution Degree : 3 IEC 60664-1
    • Ambient Air Temperature For Storage : -40-70 °C
    • Relative Humidity : 95-95 % 55-55 °C IEC 60068-2-30
  • Contractual warranty
    • Warranty : 18 months
  • Offer Sustainability
    • Rohs Exemption Information : Yes
    • Mercury Free : Yes
    • Environmental Disclosure : ENVPEP1504008EN
    • Sustainable Offer Status : Green Premium product
    • Reach Regulation : Reference contains Substances of Very High Concern above the threshold
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • China Rohs Regulation : X
    • Circularity Profile : ENVEOLI1504008EN
    • Eu Rohs Directive : Pro-active compliance (Product out of EU RoHS legal scope)
  • Complementary
    • [Us] Rated Supply Voltage : AC/DC
    • Polarity : yes DC
    • Maximum Measuring Cycle : 30 ms measurement cycle as true rms value
    • Control Circuit Voltage Limits : 15 % + 10 % Un
    • Hysteresis : 15-15 % fixed threshold setting
    • Insulation Resistance : > 500 MOhm 500 V DC IEC 60255-5 || > 500 MOhm 500 V DC IEC 60664-1
    • Measurement Error : +/- 0.05 %/°C with temperature variation || < 1 % over the whole range with voltage variation
    • [Us] Rated Supply Voltage : AC/DC non self-powered
    • Operating Rate : <= 360 operations/hour full load
    • Output Contacts : 1 C/O
    • Contacts Material : cadmium free
    • Marking : CE : 73/23/EEC || CE : EMC 89/336/EEC
    • Response Time : < 200 ms (in the event of a fault)
    • Operating Position : any position without derating
    • Input Current : 100000 mA permanent at 25 °C || 300000 mA non repetitive < 3 s at 25 °C
    • Net Weight : 0.13 kg
    • Threshold Setting : 10...100 %
    • Maximum Switching Voltage : 250 V AC/DC
    • Control Type : without test button
    • Connections - Terminals : screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end || screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end || screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 12) flexible with cable end || screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end
    • [Ui] Rated Insulation Voltage : 400 V IEC 60664-1
    • Overvoltage Category : III IEC 60664-1
    • Insulation : between supply and measurement
    • Supply Voltage Limits : 20.4-264 V AC/DC
    • Mounting Support : 35 mm symmetrical DIN rail conforming to IEC 60715
    • Nominal Output Current : 5 A
    • Local Signalling : for power ON LED (green) || for relay ON LED (yellow)
    • Mechanical Durability : 30000000 cycles
    • Housing Material : self-extinguishing plastic
    • Control Circuit Frequency : 40...70 Hz sinusoidal
    • Measurement Accuracy : +/- 10 % of the full scale value
    • Width : 17.5 mm
    • Tightening Torque : 0.6-1 N.m IEC 60947-1
    • Maximum Power Consumption In W : 1 W
    • Electrical Durability : 100000 cycles
    • Run-Up Delay At Power-Up : 0.5 s
    • Repeat Accuracy : +/- 0.5 % input and measurement circuit
  • Specifications
    • Minimum Switching Current : 10 mA 5 V DC
    • Range Of Product : Harmony Control Relays
    • Measurement Range : 2...20 A AC
    • Switching Capacity In Va : 1250 VA
    • Product Or Component Type : current control relay
    • Utilisation Category : AC-12 IEC 60947-5-1 || AC-13 IEC 60947-5-1 || AC-14 IEC 60947-5-1 || AC-15 IEC 60947-5-1 || DC-12 IEC 60947-5-1 || DC-13 IEC 60947-5-1 || DC-14 IEC 60947-5-1
    • Relay Name : RM17JC
    • Contacts Type And Composition : 1 C/O
    • Relay Type : current control relay
    • Time Delay Type : without
    • Relay Monitored Parameters : overcurrent detection
    • Maximum Power Consumption In Va : 3 VA