Safety controller with embedded communication, Modicon MCM, 8 inputs 4 outputs, monitors expansion modules, spring

Safety controller with embedded communication, Modicon MCM, 8 inputs 4 outputs, monitors expansion modules, spring

SQDXPSMCMC10804BEG XPSMCMC10804BEG 3606487042211
1831.29 / EA
http://schema.org/OutOfStock
  • Country of Origin: Italy
  • Depth: 114.5 mm
  • Number of Outputs: 4 Safety Outputs OSSD Contactor/drive Connection, 4 Test Line Control Outputs, 4 Configurable Diagnostic Connection, 4
QTY
  • Specifications
  • Complementary Attributes
    • Integrated Connection Type : backplane expansion bus, USB 2.0 port
    • Maximum Number Of I O Expansion Module : 14 128 input, 14 32.0 output
    • Uimp Rated Impulse Withstand Voltage : 4 kV IEC 61800-5-1
    • Us Rated Supply Voltage : 24 V - 20...20 % DC
  • Important Information Attributes
    • Cable Cross Section : 0.2-2.5 mm² - AWG 24...AWG 14 solid without cable end0.2-1.5 mm² - AWG 24...AWG 16 flexible without cable end, 0.2-2.5 mm² - AWG 24...AWG 14 flexible without cable end, 0.25-1 mm² - AWG 23...AWG 18 flexible with cable end, without bezel, 0.25-2.5 mm² - AWG 23...AWG 14 flexible with cable end, with bezel, 0.25-1.5 mm² - AWG 23...AWG 16 flexible with cable end, without bezel, 0.5-1.5 mm² - AWG 20...AWG 16 flexible with cable end, with double bezel, 0.2-1 mm² - AWG 24...AWG 18 solid without cable end
    • Electromagnetic Compatibility : electrostatic discharge immunity test - test level: 6 kV (on contact) conforming to IEC 61000-4-2, electrostatic discharge immunity test - test level: 20 kV (on air) conforming to IEC 61000-4-2, susceptibility to electromagnetic fields - test level: 10 V/m (80...1000 MHz) conforming to IEC 61000-4-3, susceptibility to electromagnetic fields - test level: 30 V/m (1.4 GHz...2 GHz) conforming to IEC 61000-4-3
    • Function Of Module : light curtain monitoring EN/ISO 14119emergency stop ISO 13850, guard monitoring EN/ISO 14119, enabling switch monitoring IEC 60947-5-1, light curtain monitoring IEC 61496-1, foot switch monitoring IEC 60947-5-1, switch monitoring EN 574, two-hand control EN/ISO 14119, safety mat monitoring IEC 61326-1, switch monitoring IEC 61800-5-2, muting function of light curtains IEC 61800-5-2, safety time delays, counter functions
    • Local Signalling : 1 LED green PWR power ON, 1 LED green RUN RUN (status), 1 LED red E IN internal error, 1 LED red E EX external error, 1 LED orange COM communication, 1 LED blue EN master enable, 8 LEDs yellow IN input status, 2 LEDs yellow RST restart signal, 2 LEDs yellow STATUS output channel, 1 LED green/red MS module status, 1 LED green/red NS network status
    • Safety Level : can reach category 4 ISO 13849-1, can reach PL = e ISO 13849-1, type 4 IEC 61496-1, SILCL 3 IEC 62061
    • Safety Reliability Data : MTTFd = 125 years high, DC > 99 %, PFHd = 2.89E-8 1/h
    • Vibration Resistance : +/-0.35 mm (f= 10-55 Hz) conforming to IEC 61496-1, +/-0.35 mm (f= 10-55 Hz) conforming to IEC 61496-1, +/-0.35 mm (f= 10-55 Hz) conforming to IEC 61496-1+/-0.35 mm (f= 10-55 Hz) conforming to IEC 61496-1, +/-0.35 mm (f= 10-55 Hz) conforming to IEC 61496-1, +/-0.35 mm (f= 10-55 Hz) conforming to IEC 61496-1
    • Carbon Footprint Of The Distribution Phase A4 : 0.030075801749271134, 0 kg CO2 eq.
    • Carbon Footprint Of The End Of Life Phase C1 To C4 : 0.2567735665694849, 0.3 kg CO2 eq.
    • Carbon Footprint Of The Installation Phase A5 : 0.2 kg CO2 eq., 0.1886977648202138
    • Carbon Footprint Of The Manufacturing Phase A1 To A3 : 6 kg CO2 eq., 6.484450923226433
    • Carbon Footprint Of The Use Phase B2 B3 B4 B6 : 108 kg CO2 eq., 107.71
    • Certificate Agency : TÜV, RCM, cULus
    • Local Data Status : Publishable
    • Local Publishable Date : 2026-01-12
    • Pre Comm Date : 2024-06-27
    • Return Indicator : Y
    • Stocking Flag : Y
    • Stock Policy : 2
    • Device Type : PLC System - PLC CPU
    • Serviceability : Yes
    • Traceability : Yes
    • Field Service Division : IDIBS
    • Average Life Duration : 20 year(s)
    • Use Carbon Footprint : 107.71
    • Weee Scope : In
    • Weee Product Category : 5
    • Scope Perimeter : At least in Europe
    • Eoli Availability Display : Yes
    • End Of Life Doc Ref : ENVEOLI2403017EN
    • Reach Full Compliance Status : Free of Substances of Very High Concern above the threshold
    • Reach Full Compliance Status Id : NOT_CONTAINING_SVHC
    • Reach Compliance Directive : Free of Substances of Very High Concern above the threshold
    • Rohs Eur In Scope : No
    • Rohs Eur Status : Compliant By Exemption
    • Rohs Eur Conformity Date : 2411
    • Rohs Eur Full Compliance Status : Compliant By Exemption
    • China Rohs In Scope : Yes
    • China Rohs Label : 5
    • With Recycled Cardboard : No
    • Without Single Use Plastic : No
    • Product Contributes To Saved And Avoided Emissions : No
    • Product Kit Identifier : N
    • Data Storage Equipment : SD card optional)
    • Device Short Name : XPSMCM
    • Electrical Connection : spring terminal
    • Inductive Load : 2 mH
    • Insulation : 250 V AC between power supply and housing IEC 61800-5-1
    • Load Capacitance : 0.82 µF
    • Mounting Support : omega 35 mm DIN rail EN 50022
    • Overvoltage Category : II
    • Power Dissipation In W : 3 W
    • Product Availability : Non-Stock - Not normally stocked in distribution facility
    • Product Or Component Type : safety controller CPU
    • Quality Labels : CE
    • Range Of Product : Modicon MCM
    • Returnability : Yes
    • Service Life : 20 year(s)
    • Shock Resistance : 10 gn 16 ms) 1000 shocks on each axis IEC 61496-1
    • Software Version : v5.9.4
    • Sustainable Packaging : No
    • Total Lifecycle Carbon Footprint : 115 kg CO2 eq.
    • Weee Label : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Connections Terminals : 6 captive spring terminals, removable terminal block
    • Warranty In Months : 18
    • Pep Code : ENVPEP2403017EN
    • Database Version : 2022-01
    • Pep Verification Date : 2023-11-01
    • Pcr Version : PEP-PCR-ed4-2021 09 06
    • Type Of Verification For The Pep : Independent internal review
    • Data Source : extrapolated product
    • Functional-unit Description : To monitor safety sensor signals and provide data to a CPU at 3W during 10 years with a 100% use rate.
    • Functional-unit Quantity : 1
    • Functional-unit Unit : unit
    • Reference Lifetime, In Y : 10
    • Energy Consumption On Product Lifetime, In Kwh : 262.8
    • Energy Model - Manufacturing [A1-a3] : Electricity Mix; Production mix; Low voltage; IT
    • Energy Model - Installation [A5] : Electricity Mix; Production mix; Low voltage; UE-27
    • Energy Model - Use [B6] : Electricity Mix; Production mix; Low voltage; UE-27
    • Energy Model - End Of Life [C1-c4] : Electricity Mix; Production mix; Low voltage; UE-27
    • Height Nominal : 99 mm
    • Width Nominal : 45 mm
    • Climate Change - Fossil Fuels ( Kg Co2 Eq.) Operational Energy Use [B6] : 107.57
    • Climate Change - Total ( Kg Co2 Eq.) Operational Energy Use [B6] : 107.71
    • Depletion Of Abiotic Resources - Fossil Fuels (Mj) Operational Energy Use [B6] : 2744.2
    • Ecotoxicity (Fresh Water) (Ctue) Operational Energy Use [B6] : 1160
    • Impacts Related To Land Use/Soil Quality (-) Operational Energy Use [B6] : 2.1432
    • Ionizing Radiation, Human Health (Kbq Of U235 Equiv.) Operational Energy Use [B6] : 160.15
    • Non-hazardous Waste Disposed Of (Kg) Operational Energy Use [B6] : 15.498
    • Terrestrial Eutrophication (Mole Of N Equiv) Operational Energy Use [B6] : 1.0492
    • Total Use Of Primary Energy During The Life Cycle (Mj) Operational Energy Use [B6] : 3271.2
    • Total Use Of Renewable Primary Energy Resources (Primary Energy And Primary Energy Resources Used As Raw Materials) (Mj) Operational Energy Use [B6] : 526.96
    • Use Of Non-renewable Primary Energy, Excluding Non-renewable Primary Energy Resources Used As Raw Materials (Mj) Operational Energy Use [B6] : 2744.2
    • Use Of Renewable Primary Energy, Excluding Renewable Primary Energy Resources Used As Raw Materials (Mj) Operational Energy Use [B6] : 526.96
    • Water Use (M3 Eq) Operational Energy Use [B6] : 3.5823
  • Environment Attributes Main
    • Ambient Air Temperature For Operation : -10-55 °C, -10-55 °C
    • Ambient Air Temperature For Storage : -20-85 °C, -20-85 °C
    • Take Back : No
    • Reach Free Shvc : Yes
    • Recycled Metal Content At Cr Level : 0 %
    • China Rohs Regulation : X
    • Mercury Free : Yes
    • Carbon Footprint : 114.66999805636539
    • Circularity Profile : ENVEOLI2403017EN
    • Environmental Disclosure : ENVPEP2403017EN
    • Eu Rohs Directive : Compliant By Exemption
    • Ip Degree Of Protection : IP20
    • Packaging Made With Recycled Cardboard : No
    • Packaging Without Single Use Plastic : No
    • Reach Free Of Svhc : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Relative Humidity : 10-95 %
    • Pep Code : ENVPEP2403017EN
    • Pep Verification Date : 2023-11-01
    • Pcr Version : PEP-PCR-ed4-2021 09 06
    • Psr Version : 0
    • Type Of Verification For The Pep : Independent internal review
  • General Attributes
    • Product Or Component Type : safety controller CPU
    • Range Of Product : Modicon MCM
  • ETIM
    • ETIM 8 : EC001449
    • ETIM 9 : EC001449
  • Output Attributes
    • Discrete Output Type : PNP or NPN, safety relay
    • Number Of Outputs : 4 safety outputs OSSD contactor/drive connection, 4 test line control outputs, 4 configurable diagnostic connection, 4
    • Discrete Output Current : 400 mA
  • Input Attributes
    • Discrete Input Type : safety input, NPN or PNP
    • Number Of Inputs : 8 digital input connection, 4 digital interlock start/restart or external device monitoring
    • Synchronisation Time Between Inputs : < 0.5 ms, < 0.5 ms
    • Discrete Input Current : 400 mA
    • Discrete Input Voltage : 24 V
  • Specifications
    • Country of Origin : Italy
    • Depth : 114.5 mm