  • Depth: 100 mm, 3.937 in
  • Height: 125 mm, 4.921 in
  • IP Rating: IP20
  • Max. Operating Temperature: 70 °C
  • Min. Operating Temperature: -25 °C
  • Net Weight: 675 g
  • Operating Temperature: -25 °C...70 °C
  • Storage Temperature: -40 °C...85 °C
  • Width: 1.575 in, 40 mm
Power supply, switch-mode power supply unit, 24 V
QTY
  • Product Description
  • Specifications
Power supply, switch-mode power supply unit, 24 V
  • General Data
    • AC failure bridging time @ I : > 80 ms @ 230 V AC / > 20 ms @ 115 V AC
    • Degree of efficiency : 87 %
    • Earth leakage current, max. : 3.5 mA
    • Housing version : Metal, corrosion resistant
    • Indication : Green LED (Uoutput > 21.6 V DC), Yellow LED (loutput > 90 % IRated typ. ), red LED (overload, overtemperature, short-circuit, Uoutput < 20.4 V DC)
    • MTBF : > 500,000 h in accordance with IEC 61709 (SN29500)
    • Max. perm. air humidity (operational) : 5 %…95 % RH
    • Mounting position, installation notice : on terminal rail TS 35
    • Operating temperature : -25 °C...70 °C
    • Power factor (approx.) : > 0.5…230 V AC / > 0.53…115 V AC
    • Power loss, idling : 4 W
    • Power loss, nominal load : 15 W
    • Protection against over-heating : Yes
    • Protection against reverse voltages from the load : 30…35 V DC
    • Protection degree : IP20
    • Short-circuit protection : Yes
  • Signalling
    • Contact load (NO contact) : max. 30 V DC / 1 A
    • Floating contact : Yes
    • Relay on/off : Output voltage >21.6 V DC/ <20.4 V DC, overload
  • Connection Data (Input)
    • Conductor cross-section, AWG/kcmil , max. : 12
    • Conductor cross-section, AWG/kcmil , min. : 26
    • Conductor cross-section, flexible , min. : 0.5 mm²
    • Conductor cross-section, rigid , max. : 6 mm²
    • Conductor cross-section, rigid , min. : 0.5 mm²
    • Connection system : Screw connection
    • Number of terminals : 3 for L/N/PE
    • Tightening torque, max. : 0.6 Nm
    • Tightening torque, min. : 0.5 Nm
    • Wire connection cross section, flexible (input), max. : 2.5 mm²
  • Approvals
    • Approvals : CE, CULUS, EAC, TUEV
    • ROHS : Conform
    • UL File Number Search : E258476
  • Dimensions And Weights
    • Width : 40 mm
    • Width (inches) : 1.575 inch
    • Height : 125 mm
    • Height (inches) : 4.921 inch
    • Depth : 100 mm
    • Depth (inches) : 3.937 inch
    • Net weight : 675 g
  • Electrical Safety (Applied Standards)
    • Electrical machine equipment : Acc. to EN60204
    • For use with electronic equipment : Acc. to EN50178 / VDE0160
    • Protection against dangerous shock currents : Acc. to VDE0106-101
    • Protective separation / protection against electrical shock : VDE0100-410 / acc. to DIN57100-410
    • Safety extra-low voltage : SELV according to EN 60950, PELV according to EN 60204
    • Safety transformers for switch-mode power supplies : According to EN 61558-2-16
  • Emc / Shock / Vibration
    • Limiting of mains voltage harmonic currents : According to EN 61000-3-2
    • Noise emission in accordance with EN55032 : Class B
    • Vibration resistance IEC 60068-2-6 : 1 g according to EN 50178
    • Interference immunity test acc. to : EN 61000-4-2 (ESD), EN 61000-4-3 (RS), EN 61000-4-4 (burst), EN 61000-4-5 (surge), EN 61000-4-6 (conducted), EN61000-4-8 (Fields), EN61000-4-11 (Dips)
    • Shock resistance IEC 60068-2-27 : 15 g In all directions
  • Input
    • AC current consumption : 1,26 A @ 230 V AC / 2,24 A @ 110 V AC
    • AC input voltage range : 85...264 V AC (derating at 100 V AC)
    • Connection system : Screw connection
    • DC current consumption : 0,39 A @ 370 V DC / 1,16 A @ 120 V DC
    • DC input voltage range : 80...370 V DC (Derating @ 120 V DC)
    • Frequency range AC : 47...63 Hz
    • Input frequency : 47...63 Hz
    • Input fuse (internal) : Yes
    • Inrush current : max. 40 A
    • Rated input voltage : 100...240 V AC (wide-range input)
    • Recommended back-up fuse : 4 A / DI, safety fuse6 A, Char. B, circuit breaker3...5 A, Char. C, circuit breaker
    • Surge protection : Varistor
  • Classifications
    • ETIM 6.0 : EC002540
    • ETIM 7.0 : EC002540
    • eClass 9.0 : 27-04-07-01
    • eClass 9.1 : 27-04-07-01
    • eClass 10.0 : 27-04-07-01
  • Output
    • Capacitive load : unrestricted
    • Connection system : Screw connection
    • Continous output current @ U : 5 A @ 55 °C, 3,75 A @ 70 °C
    • Nominal output current for U : 5 A at 55 °C
    • Output power : 120 W
    • Output voltage : 22...28 V (adjustable via potentiometer)
    • Overload protection : Yes
    • Parallel connection option : yes, max. 5
    • Protection against inverse voltage : Yes
    • Ramp-up time : ≤ 100 ms
    • Rated output voltage : 24 V DC ± 1 %
    • Residual ripple, breaking spikes : < 50 mVPP @ 24 V DC, IN
  • Environmental Product Compliance
    • REACH SVHC : Lead 7439-92-1
  • Insulation Coordination
    • Insulation voltage input / earth : 2 kV
    • Insulation voltage output / earth : 0.5 kV
    • Insulation voltage, input/output : 3 kV
    • Pollution severity : 2
    • Protection class : I, with PE connection
  • Connection Data (Output)
    • Conductor cross-section, AWG/kcmil , max. : 12
    • Conductor cross-section, AWG/kcmil , min. : 26
    • Conductor cross-section, flexible , max. : 2.5 mm²
    • Conductor cross-section, flexible , min. : 0.5 mm²
    • Conductor cross-section, rigid , max. : 6 mm²
    • Conductor cross-section, rigid , min. : 0.5 mm²
    • Connection system : Screw connection
    • Number of terminals : 6 (++,--,13,14)
    • Tightening torque, max. : 0.6 Nm
    • Tightening torque, min. : 0.5 Nm
  • Temperatures
    • Operating temperature, max. : 70 °C
    • Operating temperature, min. : -25 °C
    • Storage temperature, max. : 85 °C
    • Storage temperature, min. : -40 °C
    • Operating temperature : -25 °C...70 °C
    • Storage temperature : -40 °C...85 °C
  • Ratings Iecex/Atex/Cul
    • Certificate no. (cULus) : E258476