SQUARE D

EM4000 multi-circuit energy meter, 24 x 333 mV inputs, 277V control power 60 Hz

EM4000 MULTI-CIRCUIT ENERGY ME

SQDMETSEEM403336 METSEEM403336 SQDMETSEEM403336
0.00 / EA
http://schema.org/OutOfStock
  • Certifications: UL
  • Depth: 5.5 cm
  • Height: 33.5 cm
  • Mounting Type: Wall Mounted, Wall-Mounted
  • Net Weight: 4 kg
  • Standard: ANSI/TIA-968-A : 2002, CSA C22.2 No 61010-1, CSA C22.2 No 61010-1-4, EN 55022, FCC Part 15 Class B, ICES-003, IEC 6100-4-5
  • Storage Temperature: -40-70 °C
  • Width: 30.5 cm
This multi-circuit power meter is part of the PowerLogic EM4000 Series. This compact multi-circuit energy meter enables reliable metering of building electrical loads with a low installation cost-per-point. It combine revenue-accurate electricity sub-metering with advanced communications technology. It is ideal for departmental metering applications and M&V within office, condominiums, malls and other multi-user environments. This version monitor up to 24 tenants with a single device, combined with 0.333 volt split or solid core current transducer. Designed for 120 (phase neutral) or 208 volts (phase phase) networks, working at 60 Hz. Measurement accuracy is plus or minus 0.5 %, compliant with ANSI C12.1 and C12.20 Class 0.5 ; IEC 62053-22 Class 0.5S. The printed board is installed in a Type 1 black enclosure, with an integrated backlit LCD display, 2 lines, on the door. Mechanical dimensions are 335 mm in width, 305 mm in height and 55 mm in depth ; for 4 kg.
QTY
  • Product Description
  • Specifications
This multi-circuit power meter is part of the PowerLogic EM4000 Series. This compact multi-circuit energy meter enables reliable metering of building electrical loads with a low installation cost-per-point. It combine revenue-accurate electricity sub-metering with advanced communications technology. It is ideal for departmental metering applications and M&V within office, condominiums, malls and other multi-user environments. This version monitor up to 24 tenants with a single device, combined with 0.333 volt split or solid core current transducer. Designed for 120 (phase neutral) or 208 volts (phase phase) networks, working at 60 Hz. Measurement accuracy is plus or minus 0.5 %, compliant with ANSI C12.1 and C12.20 Class 0.5 ; IEC 62053-22 Class 0.5S. The printed board is installed in a Type 1 black enclosure, with an integrated backlit LCD display, 2 lines, on the door. Mechanical dimensions are 335 mm in width, 305 mm in height and 55 mm in depth ; for 4 kg.
  • Environment
    • Ambient Air Temperature For Operation : -40-70 °C
    • Height : 33.5 cm
    • Pollution Degree : 2
    • Mounting Mode : wall mount
    • Ambient Air Temperature For Storage : -40-70 °C
    • Relative Humidity : 90-90 % 40-40 °C
    • Standards : FCC Part 15 class B || ICES-003 || IEC 6100-4-5 || CSA C22.2 No 61010-1-4 || ANSI/TIA-968-A : 2002 || CSA C22.2 No 61010-1 || EN 55022
    • Device Mounting : wall mounted
    • Product Certifications : UL
    • Width : 30.5 cm
    • Enclosure Type : NEMA type 1
    • Depth : 5.5 cm
    • Net Weight : 4 kg
    • Type Of Installation : indoor installation || enclosed outdoor
    • Operating Altitude : <= 9842.52 ft (3000 m)
  • Specifications
    • Width : 30.5 cm
    • Height : 33.5 cm
    • Weight : 4 kg
    • Network Frequency : 60 Hz
    • Energy Management : billing analysis || sub billing and cost allocation
    • [Us] Rated Supply Voltage : 277 V AC 60 Hz
    • Power Quality Analysis : compliance monitoring
    • Type Of Measurement : current per phase, rms || negative active energy || voltage per phase, rms || negative reactive energy || apparent energy || pulse count || active and reactive power || apparent power || positive active energy || positive reactive energy
    • Power Monitoring : basic instrumentation
    • Product Or Component Type : multi-circuit energy meter
    • Product Name : PowerLogic EM4000
    • Device Application : sub billing
    • Device Short Name : EM4033
    • Range : PowerLogic
  • Offer Sustainability
    • Eu Rohs Directive : Under investigation
    • California Proposition 65 : WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
  • Complementary
    • Communication Port Support : RJ45 ETHERNET || RS485
    • Measurement Accuracy : +/- 0.5 % of the measuring range
    • Measurement Voltage : 80-480 V without PTs || 480-999000 V with external PTs
    • Sampling Rate : 256 samples/cycle
    • Communication Port Protocol : BACnet IP || FTP || HTTP || Modbus TCP/IP || SNTP
    • Analogue Input Type : solid core CT 0.333 V24 x single pole || solid core CT 0.333 V12 x single phase || solid core CT 0.333 V8 x three phase || split core CT 0.333 V24 x single pole || split core CT 0.333 V12 x single phase || split core CT 0.333 V8 x three phase
    • Display Type : Backlit LCD
    • Communication Of Data : voltage || negative active energy || positive active energy || positive reactive energy || negative reactive energy || apparent energy
    • Number Of Inputs : 2 pulse
    • Messages Display Capacity : 2 lines of 16 characters