Soft starter, Altivar Soft Starter ATS490, 660A, 208 to 690V AC, control supply 110 to 230V AC

Soft starter, Altivar Soft Sta

SQDATS490C66Y ATS490C66Y 3606486948927
17080.11 / EA
http://schema.org/OutOfStock
  • Connection Type: 1 RJ45 For Connecting Modbus Serial, 1 RJ45 For Connecting Modbus TCP/EtherNet/IP
  • Depth: 300 mm
  • IsSustainable: Yes
  • Operating Position: Vertical +/- 10 Degree
QTY
  • Features
  • Specifications
  • Prop 65
    • WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
  • Communications & Management Attributes
    • Communication Port Protocol : Modbus serialModbus serial, Modbus TCP/EtherNet/IP
  • Complementary Attributes
    • Maximum Horse Power Rating : 500 hp 575 V heavy duty200 hp 208 V normal duty250 hp 230 V normal duty500 hp 460 V normal duty600 hp 575 V normal duty, 200 hp 230 V heavy duty, 400 hp 460 V heavy duty
    • Integrated Motor Overload Protection : true
    • Maximum Permanent Current : 590 A at 40 °C heavy duty
    • Maximum Switching Current : relay outputs 2 A / 250 V AC for AC-15 100000 cycles following IEC 60947-5-1relay outputs 2 A / 30 V DC for DC-13 150000 cycles following IEC 60947-5-1
    • Minimum Switching Current : 100 mA 12 V DC relay outputs
  • Important Information Attributes
    • Connector Type : 1 RJ45 for connecting Modbus serial, 1 RJ45 for connecting Modbus TCP/EtherNet/IP
    • Device Connection : in the motor supply line, inside delta
    • Display Type : 1 LED green and yellow)status1 LED Red)Warning/Error1 LED Yellow)ASF, 1 LED Yellow)COM, 1 LED green and yellow)NET11 LED green and red)NET2, 1 LED green and red)NET3, 1 LED green and yellow)NET4, 1 LED green and red)RUN/ERR (Module Status), 1 LED green and yellow)Ethernet link, 1 LED green and red)ETH MS (Ethernet port configuration status), 1 LED green and red)Eth NS (Ethernet network status)
    • Electromagnetic Compatibility : conducted and radiated emissions level A conforming to IEC 60947-4-2, damped oscillating waves level 3 conforming to IEC 61000-4-18electrostatic discharge level 3 conforming to IEC 61000-4-2, immunity to electrical transients level 4 conforming to IEC 61000-4-4immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3voltage/current impulse level 3 conforming to IEC 61000-4-5immunity to conducted interference caused by radio-electrical fields level 3 conforming to EN/IEC 61000-4-6
    • Function Available : pre-heating, smoke extraction, second motor set, Deceleration with torque control, Braking, boost, Line contactor control, reverse contactor control, anti-jam, jog, borehole pump starting, condition monitoring, power monitoring, cybersecure firmware update
    • Marking : CE, cULus, UKCA, RCM, CCC, ATEX, EAC, KC
    • Motor Power Kw : 355 kW 440 V in the motor supply line heavy duty560 kW 690 V in the motor supply line heavy duty400 kW 400 V to the motor delta terminals heavy duty, 355 kW 400 V in the motor supply line normal duty400 kW 440 V in the motor supply line normal duty630 kW 660 V in the motor supply line normal duty, 630 kW 690 V in the motor supply line normal duty, 160 kW 230 V in the motor supply line heavy duty, 315 kW 400 V in the motor supply line heavy duty, 400 kW 500 V in the motor supply line heavy duty, 400 kW 525 V in the motor supply line heavy duty, 560 kW 660 V in the motor supply line heavy duty, 315 kW 230 V to the motor delta terminals normal duty, 500 kW 400 V to the motor delta terminals normal duty
    • Option Card : communication module CANopen daisy chain, communication module CANopen Sub-D, communication module CANopen open style, communication module Profibus DP V1, communication module PROFINET
    • Protection Type : phase failure mainsthermal protection starter, thermal protection motor, current overload motor, motor underload motor, excessive acceleration time motor, motor phase loss detection motor, protection against line phase inversion mains, external thermal protection motor, protection delta inside wiring starter, short-circuit between motor phase and earth motor
    • Transmission Frame : RTU, TCP/UDP
    • Transmission Rate : 4.8…38.4 kbps, 100 BASE TX
    • Utilisation Category : AC-3A, AC-53A
    • Certificate Agency : CE, cULus, UKCA, RCM, CCC, DNV, ATEX, EAC, KC
    • [Ue] Rated Operational Voltage : 440 V 355 kW in the motor supply line heavy duty690 V 560 kW in the motor supply line heavy duty, 230 V 200 hp heavy duty575 V 500 hp heavy duty, 400 V 355 kW in the motor supply line normal duty440 V 400 kW in the motor supply line normal duty660 V 630 kW in the motor supply line normal duty, 690 V 630 kW in the motor supply line normal duty, 230 V 160 kW in the motor supply line heavy duty, 400 V 315 kW in the motor supply line heavy duty, 500 V 400 kW in the motor supply line heavy duty, 525 V 400 kW in the motor supply line heavy duty, 660 V 560 kW in the motor supply line heavy duty208 V 200 hp normal duty, 230 V 250 hp normal duty460 V 500 hp normal duty575 V 600 hp normal duty, 460 V 400 hp heavy duty, 208...690 V AC - 15...10 %)
    • Environmental Class (During Operation) : class 3C3 according to IEC 60721-3-3, class 3S3 according to IEC 60721-3-3
    • Maximum Acceleration Under Vibratory Load (During Storage) : 1 gn at 9…200 Hz, 1.5 gn at 200…500 Hz
    • Maximum Acceleration Under Vibratory Load (During Transport) : 1 gn at 9…200 Hz, 1.5 gn at 200…500 Hz
    • Carbon Footprint Of The Distribution Phase [A4] : 7.397142502879543, 7 kg CO2 eq.
    • Carbon Footprint Of The End-of-life Phase [C1 To C4] : 65.88132628918824, 66 kg CO2 eq.
    • Carbon Footprint Of The Installation Phase [A5] : 10 kg CO2 eq., 9.746973643254218
    • Carbon Footprint Of The Manufacturing Phase [A1 To A3] : 516 kg CO2 eq., 515.6116659383605
    • Carbon Footprint Of The Use Phase [B2 B3 B4 B6] : 6 318 kg CO2 eq., 6317.504064147673
    • Local Data Status : Publishable
    • Local Publishable Date : 2026-01-12
    • Return Indicator : Y
    • Stocking Flag : Y
    • Stock Policy : 1
    • Device Type : Soft starter - Soft starter
    • Serviceability : Yes
    • Traceability : Yes
    • Field Service Division : IDIBS
    • Average Life Duration : 10 year(s)
    • Weee Applicability : Finished product
    • Weee Scope : In
    • Weee Product Category : 5
    • Scope Perimeter : At least in Europe
    • Eoli Availability Display : Yes
    • End Of Life Doc Ref : ENVEOLI2311028EN
    • Reach Full Compliance Status : Reference contains Substances of Very High Concern above the threshold
    • Reach Full Compliance Status Id : CONTAINS_SVHC
    • Reach Compliance Directive : Reference contains Substances of Very High Concern above the threshold
    • Rohs Eur In Scope : Yes
    • Rohs Eur Status : Compliant By Exemption
    • Rohs Eur Conformity Date : 2421
    • Rohs Eur Full Compliance Status : Compliant By Exemption
    • China Rohs In Scope : Yes
    • China Rohs Label : 5
    • With Recycled Cardboard : Yes
    • Without Single Use Plastic : No
    • Product Contributes To Saved And Avoided Emissions : No
    • Dangerous Goods Code : LITHIUM METAL BATTERIES IN EQUIP. BUTTON CELL-BAT EXEMPT
    • Product Kit Identifier : N
    • Apparent Power : 280 VA
    • Data Format : 8 bits, configurable odd, even or no parity 1or 2 stop
    • Device Short Name : ATS490
    • Display Screen Available : true
    • Internal Bypass : true
    • Material Declaration : true
    • Method Of Access : slave Modbus serial
    • Number Of Addresses : 0-247 Modbus serial
    • Operating Position : vertical +/- 10 degree
    • Operating Rate : 10 cyc/h
    • Overload Current : 400 % Ie for 13 s
    • Phase : 3 phase
    • Power Loss Per Device Current Dependent : 205 W
    • Power Loss Static Current Independent : 19 W
    • Power Losses : 9247 W during starting at 40 °C at 400% Ie
    • Product Availability : Stock - Normally stocked in distribution facility
    • Product Destination : asynchronous motors
    • Product Or Component Type : soft starter
    • Product Specific Application : process and infrastructures
    • Range Of Product : Altivar Soft Starter ATS490
    • Returnability : Yes
    • Safety Function : STO (safe torque off): SIL 1 conforming to IEC 61508STO (safe torque off): PL c/category 2 conforming to ISO 13849
    • Safety Level : security level (SL) 1 IEC 62443-4-2
    • Service Factor : 100
    • Software Version : v6.1
    • Supply Frequency : 50...60 Hz - 20...20 %
    • Sustainable Packaging : No
    • Total Lifecycle Carbon Footprint : 6 916 kg CO2 eq.
    • Type Of Polarization : no impedance Modbus serial
    • Updatability : Upgradeable through digital modules
    • Volume Of Cooling Air : 238 m3/h
    • Weee Label : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • With Safety Function Cybersecurity : true
    • With Safety Function Safe Programmable Logic : false
    • Torque Control : true
    • Pep Code : ENVPEP2311028EN
    • Database Version : 2023-02
    • Pep Verification Date : 2024-08-01
    • Pcr Version : PCR-4-ed4-EN-2021 09 06
    • Psr Version : PSR-0005-ed3-EN-2023 06 06
    • Type Of Verification For The Pep : Independent external review
    • Data Source : referent product
    • Functional-unit Description : The aim of soft starter is to drive an asynchronous motor (squirrel cage) by limitation of the current during acceleration and deceleration phase with a torque control. It’s based on three phases dimmer with Silicon controlled rectifier (thyristor). The rating of softstarter is given by nominal current 660A in the case study which lead to drive several power motor depending of power network voltage ie 230V power motor of 200kW and 690V power motor of 630kW. Calculation of the environmental impacts is based on 10 years of product service lifetime. The usage profile taken into account is 2,16% uptime in active phase, 47,84% uptime in stand by phase and 50% in control phase.
    • Functional-unit Quantity : 1
    • Functional-unit Unit : Unit
    • Reference Lifetime In Y : 10
    • Energy Model - Manufacturing [A1-a3] : Indonesia, ID
    • Energy Model - Installation [A5] : Electricity Mix; Low voltage; 2018; Europe, EU-27
    • Energy Model - Use [B6] : Electricity Mix; Low voltage; 2018; Europe, EU-27
    • Energy Model - End Of Life [C1-c4] : Electricity Mix; Low voltage; 2018; Europe, EU-27
    • Recyclability Potential In % : 85
    • Height Nominal : 455 mm
    • Width Nominal : 304 mm
    • [Ie] Rated Operational Current : normal duty 660 A in line 40 °C)
    • [Uc] Control Circuit Voltage : 24 V DC110...230 V AC 50-60 Hz - 15...10 %
    • [Ui] Rated Insulation Voltage : 690 V
    • [Uimp] Rated Impulse Withstand Voltage : 6 kV
    • Maximum Acceleration Under Shock Impact (During Operation) : 15 gn at 11 ms
    • Maximum Acceleration Under Shock Load (During Storage) : 10 gn at 11 ms
    • Maximum Acceleration Under Shock Load (During Transport) : 10 gn at 11 ms
    • Maximum Acceleration Under Vibrational Stress (During Operation) : 1 gn at 13…200 Hz
    • Maximum Deflection Under Vibratory Load (During Operation) : 1.5 mm at 2...13 Hz
    • Maximum Deflection Under Vibratory Load (During Storage) : 1.75 mm at 2...9 Hz
    • Maximum Deflection Under Vibratory Load (During Transport) : 1.75 mm at 2...9 Hz
    • On-load Factor : 50 %
    • With Safety Function Safe Brake Management (Sbc/Sbt) : false
    • With Safety Function Safe Direction (Sdi) : false
    • With Safety Function Safe Operating Stop (Sos) : false
    • With Safety Function Safe Position (Sp) : false
    • With Safety Function Safe Speed Monitor (Ssm) : false
    • With Safety Function Safe Stop 1 (Ss1) : false
    • With Safety Function Safe Torque Off (Sto) : true
    • With Safety Function Safely Limited Position (Slp) : false
    • With Safety Function Safely Limited Speed (Sls) : false
    • With Sft Fct Safe Stop 2 (Ss2) : false
    • Nbr. Of Units In Pkg. : 1
    • Package Weight(Lbs) : 39.500 kg
    • Take-back : No
    • Warranty (In Months) : 18
    • [In] Rated Current Pwr Loss Specifctn2 : 660 A
    • Customs Code : 8537109170
  • Environment Attributes Main
    • Ambient Air Temperature For Operation : -25-40 °C (without derating), -25-40 °C (without derating)-25-40 °C (without derating), -25-40 °C (without derating)40-60 °C (with current derating of 1 % per °C above 40 °C)
    • Ambient Air Temperature For Storage : -40-70 °C, -40-70 °C
    • Ambient Air Transport Temperature : -40-70 °C, -40-70 °C
    • Operating Altitude : <= 6561.68 ft (2000 m) without derating, <= 6561.68 ft (2000 m) without derating, > 2000...4800 m with current derating 1 % per 100 m above 2000 m, > 2000...4800 m with current derating 1 % per 100 m above 2000 m<= 6561.68 ft (2000 m) without derating, <= 6561.68 ft (2000 m) without derating, > 2000...4800 m with current derating 1 % per 100 m above 2000 m, > 2000...4800 m with current derating 1 % per 100 m above 2000 m
    • Take Back : No
    • Recycled Metal Content At Cr Level : 0 %
    • China Rohs Regulation : X
    • Mercury Free : Yes
    • Carbon Footprint : 6916.141172521355
    • Circularity Profile : ENVEOLI2311028EN
    • Environmental Disclosure : ENVPEP2311028EN
    • Eu Rohs Directive : Compliant By Exemption
    • Ip Degree Of Protection : IP00
    • Packaging Made With Recycled Cardboard : Yes
    • Packaging Without Single Use Plastic : No
    • Reach Regulation : Reference contains Substances of Very High Concern above the threshold
    • Relative Humidity : 5-95 % without condensation or dripping water EN/IEC 60068-2-3
    • Pep Code : ENVPEP2311028EN
    • Pep Verification Date : 2024-08-01
    • Pcr Version : PCR-4-ed4-EN-2021 09 06
    • Psr Version : PSR-0005-ed3-EN-2023 06 06
    • Type Of Verification For The Pep : Independent external review
  • General Attributes
    • Phase : 3 phase
    • Product Or Component Type : soft starter
    • Range Of Product : Altivar Soft Starter ATS490
  • ETIM
    • ETIM 8 : EC000640
    • ETIM 9 : EC000640
  • Output Attributes
    • Analogue Output Type : current output AQ1 : 0...20 mA/4...20 mA , impedance< 500 Ohm, voltage output AQ1 : 0...10 V , impedance> 470 Ohm
    • Discrete Output Type : programmable digital output DQ1 <= 30 V 100 mA, programmable digital output DQ2 <= 30 V 100 mA
    • Relay Output Type : relay outputs R1A, R1C NO, relay outputs R2A, R2C NO, relay outputs R3A, R3C NO
    • Analogue Output Number : 1
    • Discrete Output Number : 2
    • Output Compatibility : open collector level 1 PLC IEC 65A-68
    • Output Current Drift : 150-700 %
    • Relay Output Number : 3
  • Input Attributes
    • Analogue Input Type : AI1/PTC1 : PTC/PT 100/PT 1000/KTY84 temperature probe, PTC2 : PTC/PT 100/PT 1000/KTY84 temperature probe, PTC3 : PTC/PT 100/PT 1000/KTY84 temperature probe
    • Discrete Input Logic : digital input DI1 0...< 5 V <= 2 mA > 11 V, >= 5 mA, digital input DI2 0...< 5 V <= 2 mA > 11 V, >= 5 mA, digital input DI3 0...< 5 V <= 2 mA > 11 V, >= 5 mA, digital input DI4 0...< 5 V <= 2 mA > 11 V, >= 5 mA, digital input STO 0...< 5 V <= 2 mA > 11 V, >= 5 mA
    • Discrete Input Type : DI1) digital input, 4.4 kOhm, DI2) digital input, 4.4 kOhm, DI3) digital input, 4.4 kOhm, DI4) digital input, 4.4 kOhmSTO) digital input, > 1 kOhm
    • Input Compatibility : DI1 discrete input level 1 PLC EN/IEC 61131-2, DI2 discrete input level 1 PLC EN/IEC 61131-2, DI3 discrete input level 1 PLC EN/IEC 61131-2, DI4 discrete input level 1 PLC EN/IEC 61131-2, STO discrete input level 1 PLC EN/IEC 61131-2
    • Analogue Input Number : 1
    • Discrete Input Number : 5
  • Specifications
    • Country of Origin : China, France, Indonesia, Philippines, Singapore, United States
    • Depth : 300 mm
  • Batteries & Runtime Attributes
    • Removable Battery : Yes