SQUARE D

Soft starter, Altistart 480, 480A, 208 to 690V AC, control supply 110 to 230V AC

SOFTSTARTER ATS480 208 - 690V

SQDATS480C48Y ATS480C48Y 3606481089144
7723.28 / EA
http://schema.org/OutOfStock
  • Connection Type: 1 RJ45
  • Depth: 314.0 mm
  • IsSustainable: Yes
  • Operating Position: Vertical +/- 10 Degree
Altivar Soft Starter ATS480 is intended to start and stop asynchronous motors supplied from 208V to 690V. It meets the requirements of the most demanding applications in normal and heavy duty. With an operational rated current of 480A in normal duty, it supplies motor from 132kW to 500kW according to mains voltage. Designed for digitization, connected, optimized to meet cybersecurity standard, it simplifies project execution and maximizes the availability of applications. Its torque control (TCS) masters acceleration and deceleration. It efficiently stops high inertia application thanks to the dynamic braking and DC injection. It could be connected in-line or inside the delta to reduce its operational current. The embedded test routine simplifies the commissioning inside the delta. Its dimensions are 400mm (width) x 314mm (depth) x 670mm (height) and it weighs 51,4kg. Altivar Soft Starter ATS480 is designed to address process, infrastructures and industrial machines. It conforms to IEC/EN60947-4-1. It is certified CE, cULus, UKCA, CCC, RCM, EAC, and Marine certified DNV, ABS, BV and CCS. Display terminals, remote mounting kit, communication modules are common with Altivar Drives. Line chokes, DNV kits are common with ATS48. ATS480 is compatible with ATS48, it has same footprint, fixing, torque control algorithm, I/O, menus… The integration of Altivar Soft Starter ATS480 in EcoStruxure drastically simplifies architecture selection, detailed design and execution in automation and electrical systems.
QTY
  • Product Description
  • Features
  • Specifications
Altivar Soft Starter ATS480 is intended to start and stop asynchronous motors supplied from 208V to 690V. It meets the requirements of the most demanding applications in normal and heavy duty. With an operational rated current of 480A in normal duty, it supplies motor from 132kW to 500kW according to mains voltage. Designed for digitization, connected, optimized to meet cybersecurity standard, it simplifies project execution and maximizes the availability of applications. Its torque control (TCS) masters acceleration and deceleration. It efficiently stops high inertia application thanks to the dynamic braking and DC injection. It could be connected in-line or inside the delta to reduce its operational current. The embedded test routine simplifies the commissioning inside the delta. Its dimensions are 400mm (width) x 314mm (depth) x 670mm (height) and it weighs 51,4kg. Altivar Soft Starter ATS480 is designed to address process, infrastructures and industrial machines. It conforms to IEC/EN60947-4-1. It is certified CE, cULus, UKCA, CCC, RCM, EAC, and Marine certified DNV, ABS, BV and CCS. Display terminals, remote mounting kit, communication modules are common with Altivar Drives. Line chokes, DNV kits are common with ATS48. ATS480 is compatible with ATS48, it has same footprint, fixing, torque control algorithm, I/O, menus… The integration of Altivar Soft Starter ATS480 in EcoStruxure drastically simplifies architecture selection, detailed design and execution in automation and electrical systems.
  • Prop 65
    • WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
  • Communications & Management Attributes
    • Communication Data Link : serial
    • Communication Port Protocol : Modbus serial
  • Complementary Attributes
    • Maximum Horse Power Rating : 350.0 hp 575 V heavy duty150.0 hp 208 V normal duty125.0 hp 208 V heavy duty, 150.0 hp 230 V heavy duty350.0 hp 460 V normal duty, 300.0 hp 460 V heavy duty400.0 hp 575 V normal duty
    • Maximum Switching Current : relay outputs, relay outputs 2 A 250 V ACrelay outputs 2 A 30 V DC
    • Integrated Motor Overload Protection : true
    • Maximum Permanent Current : 410.0 A at 40 °C heavy duty
    • Minimum Switching Current : 100 mA 12 V DC relay outputs
  • Important Information Attributes
    • Persona Type Ids : EU, OM, OM8
    • Persona Type Names : End User, Original Equipment Manufacturer, OEM - Control Panelbuilder
    • Device Connection : in the motor supply line, to the motor delta terminals
    • Electromagnetic Compatibility : conducted and radiated emissions level A conforming to IEC 60947-4-2conducted and radiated emissions with bypass level B conforming to IEC 60947-4-2, damped oscillating waves level 3 conforming to IEC 61000-4-12electrostatic discharge level 3 conforming to IEC 61000-4-11, immunity to electrical transients level 4 conforming to IEC 61000-4-4immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3voltage/current impulse level 3 conforming to IEC 61000-4-5
    • Function Available : external bypass control, pre-heating, smoke extraction, multi-motor cascade, second motor set, user management, ports and services hardening, security event logging, cybersecure firmware update, single direction
    • Marking : CE, CCC, UKCA, EAC, RCM, cULus
    • Motor Power Kw : 220.0 kW 440 V in the motor supply line heavy duty250.0 kW 500 V in the motor supply line heavy duty250.0 kW 525 V in the motor supply line heavy duty400.0 kW 690 V in the motor supply line heavy duty220.0 kW 230 V to the motor delta terminals heavy duty355.0 kW 400 V to the motor delta terminals normal duty315.0 kW 400 V to the motor delta terminals heavy duty, 132.0 kW 230 V in the motor supply line normal duty110.0 kW 230 V in the motor supply line heavy duty250.0 kW 400 V in the motor supply line normal duty, 220.0 kW 400 V in the motor supply line heavy duty, 250.0 kW 440 V in the motor supply line normal duty315.0 kW 500 V in the motor supply line normal duty, 315.0 kW 525 V in the motor supply line normal duty400.0 kW 660 V in the motor supply line normal duty, 355.0 kW 660 V in the motor supply line heavy duty500.0 kW 690 V in the motor supply line normal duty, 250.0 kW 230 V to the motor delta terminals normal duty
    • Option Card : communication module Profibus DP V1, communication module Modbus TCP/EtherNet/IP, communication module CANopen daisy chain, communication module CANopen Sub-D, communication module CANopen open style, communication module PROFINET
    • Protection Type : line supply phase loss motorthermal protection motor, phase failure lineintegrated thermal protection motorthermal protection starter, current overload motor, underload motor, excessive starting time, locked rotor motor, motor phase loss motor, line supply phase loss line
    • Utilisation Category : AC-3A, AC-53A
    • Certificate Agency : CE, cULus, CCC, UKCA, RCM, EAC, DNV, ABS, BV, CCS
    • [Ue] Rated Operational Voltage : 440 V 220.0 kW in the motor supply line heavy duty500 V 250.0 kW in the motor supply line heavy duty525 V 250.0 kW in the motor supply line heavy duty690 V 400.0 kW in the motor supply line heavy duty, 230 V 150.0 hp heavy duty575 V 350.0 hp heavy duty, 230 V 132.0 kW in the motor supply line normal duty230 V 110.0 kW in the motor supply line heavy duty400 V 250.0 kW in the motor supply line normal duty, 400 V 220.0 kW in the motor supply line heavy duty, 440 V 250.0 kW in the motor supply line normal duty500 V 315.0 kW in the motor supply line normal duty, 525 V 315.0 kW in the motor supply line normal duty660 V 400.0 kW in the motor supply line normal duty, 660 V 355.0 kW in the motor supply line heavy duty690 V 500.0 kW in the motor supply line normal duty208 V 150.0 hp normal duty, 208 V 125.0 hp heavy duty460 V 350.0 hp normal duty, 460 V 300.0 hp heavy duty575 V 400.0 hp normal duty
    • Environmental Class (During Operation) : class 3C3 according to IEC 60721-3-3, class 3S2 according to IEC 60721-3-3
    • Maximum Acceleration Under Vibratory Load (During Storage) : 15 m/s² at 200...500 Hz, 10 m/s² at 9...200 Hz
    • Maximum Acceleration Under Vibratory Load (During Transport) : 15 m/s² at 200...500 Hz, 10 m/s² at 9...200 Hz
    • Carbon Footprint Of The Distribution Phase [A4] : 7.5606696667, 8 kg CO2 eq.
    • Carbon Footprint Of The End-of-life Phase [C1 To C4] : 6.6158423333, 7 kg CO2 eq.
    • Carbon Footprint Of The Installation Phase [A5] : 8 kg CO2 eq., 7.6999423333
    • Carbon Footprint Of The Manufacturing Phase [A1 To A3] : 484 kg CO2 eq., 484.1629666667
    • Carbon Footprint Of The Use Phase [B2 B3 B4 B6] : 32 956 kg CO2 eq., 32956.1891348089
    • Local Data Status : Publishable
    • Local Publishable Date : 2026-03-26
    • Pre Comm Date : 2021-12-20
    • Return Indicator : Y
    • Stocking Flag : N
    • Stock Policy : 2
    • Device Type : Soft starter - Soft starter
    • Serviceability : Yes
    • Traceability : Yes
    • Field Service Division : IDIBS
    • Average Life Duration : 10 year(s)
    • Weee Applicability : Finished product
    • Weee Scope : In
    • Weee Product Category : 4
    • Scope Perimeter : At least in Europe
    • Eoli Availability Display : Yes
    • End Of Life Doc Ref : ENVEOLI2102013EN
    • Reach Full Compliance Status : Reference contains Substances of Very High Concern above the threshold
    • Reach Full Compliance Status Id : CONTAINS_SVHC
    • Reach Compliance Directive : Reference contains Substances of Very High Concern above the threshold
    • Rohs Eur In Scope : No
    • Rohs Eur Status : Compliant By Exemption
    • Rohs Eur Conformity Date : 2149
    • Rohs Eur Full Compliance Status : Compliant By Exemption
    • China Rohs In Scope : Yes
    • China Rohs Label : 5
    • With Recycled Cardboard : Yes
    • Without Single Use Plastic : No
    • Product Contributes To Saved And Avoided Emissions : No
    • Dangerous Goods Code : LITHIUM METAL BATTERIES IN EQUIP. BUTTON CELL-BAT EXEMPT
    • Tier Id : 1
    • Tier : 1
    • Function Option Id : STANDARD
    • Function Option : Standard
    • Market Segmentation Id : INDUSTRIAL
    • Market Segmentation : Industrial
    • Product Kit Identifier : N
    • Apparent Power : 0.125 kVA
    • Connector Type : 1 RJ45
    • Data Format : 8 bits, configurable odd, even or no parity
    • Device Short Name : ATS480
    • Display Screen Available : true
    • Method Of Access : slave Modbus serial
    • Network Frequency : 50/60 Hz
    • Noise Level : 55.0 dB
    • Number Of Addresses : 0-227 Modbus serial
    • Operating Position : vertical +/- 10 degree
    • Phase : 3 phase
    • Power Loss Per Device Current Dependent : 1366.0 W
    • Power Loss Static Current Independent : 25.0 W
    • Product Availability : Stock - Normally stocked in distribution facility
    • Product Destination : asynchronous motors
    • Product Or Component Type : soft starter
    • Product Specific Application : process and infrastructures
    • Range Of Product : Altivar Soft Starter ATS480
    • Returnability : Yes
    • Software Version : EIME v5.9.1
    • Supply Frequency : 50...60 Hz - 20...20 %
    • Sustainable Packaging : No
    • Total Lifecycle Carbon Footprint : 33 462 kg CO2 eq.
    • Transmission Frame : RTU
    • Transmission Rate : 1200...256000 bit/s
    • Type Of Polarization : no impedance Modbus serial
    • Updatability : Upgradeable through digital modules
    • Volume Of Cooling Air : 600.0 m3/h
    • Weee Label : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • With Safety Function Safe Programmable Logic : false
    • Torque Control : true
    • Pep Code : ENVPEP2102013EN
    • Database Version : 2020-12
    • Pep Verification Date : 2021-11-01
    • Pcr Version : PCR-ed3-EN-2015 04 02
    • Type Of Verification For The Pep : Independent external review
    • Data Source : extrapolated product
    • Functional-unit Description : The aim of soft starter is to drive an asynchronous motor (squirrel cage) by limitation of the current during acceleration and deceleration phase with a torque control. It’s based on three phases dimmer with Silicon controlled rectifier (thyristor). The rating of softstarter is given by nominal current 660 A in the case study which lead to drive several power motor depending of power network ie 230V power motor of 110kW and 690V power motor of 355kW. Calculation of the environmental impacts is based on 10 years of product service lifetime. The usage profile taken into account is 45% uptime in use phase, 45% uptime in stand by phase and 10% uptime in off phase.
    • Functional-unit Quantity : 1
    • Functional-unit Unit : unit
    • Reference Lifetime In Y : 10
    • Energy Consumption On Product Lifetime In Kwh : 55818.72
    • Energy Model - Manufacturing [A1-a3] : Energy model used: China
    • Energy Model - Installation [A5] : Electricity Mix; AC; < 1kV; EU-27
    • Energy Model - Use [B6] : Electricity Mix; AC; < 1kV; EU-27
    • Energy Model - End Of Life [C1-c4] : Electricity Mix; AC; < 1kV; EU-27
    • Height Nominal : 670.0 mm
    • Width Nominal : 400.0 mm
    • [Ie] Rated Operational Current : normal duty 480.0 A 40 °C)
    • [Uc] Control Circuit Voltage : 24 V DC110...230 V AC 50/60 Hz - 15...10 %
    • [Ui] Rated Insulation Voltage : 690 V
    • [Uimp] Rated Impulse Withstand Voltage : 6 kV
    • [Us] Rated Supply Voltage : 208...690 V - 15...10 %
    • Maximum Acceleration Under Shock Impact (During Operation) : 150 m/s² at 11 ms
    • Maximum Acceleration Under Shock Load (During Storage) : 100 m/s² at 11 ms
    • Maximum Acceleration Under Shock Load (During Transport) : 100 m/s² at 11 ms
    • Maximum Acceleration Under Vibrational Stress (During Operation) : 10 m/s² at 13...200 Hz
    • Maximum Deflection Under Vibratory Load (During Operation) : 1.5 mm at 2...13 Hz
    • Maximum Deflection Under Vibratory Load (During Storage) : 1.75 mm at 2...9 Hz
    • Maximum Deflection Under Vibratory Load (During Transport) : 1.75 mm at 2...9 Hz
    • With Safety Function Safe Brake Management (Sbc/Sbt) : false
    • With Safety Function Safe Direction (Sdi) : false
    • With Safety Function Safe Operating Stop (Sos) : false
    • With Safety Function Safe Position (Sp) : false
    • With Safety Function Safe Speed Monitor (Ssm) : false
    • With Safety Function Safe Stop 1 (Ss1) : false
    • With Safety Function Safe Torque Off (Sto) : false
    • With Safety Function Safely Limited Position (Slp) : false
    • With Safety Function Safely Limited Speed (Sls) : false
    • With Sft Fct Safe Stop 2 (Ss2) : false
    • Nbr. Of Units In Pkg. : 1
    • Package Weight(Lbs) : 61.000 kg
    • Take-back : No
    • Warranty (In Months) : 18
    • Air Pollution (M3) Distribution [A4] : 321.6261
    • Hazardous Waste Disposed Of (Kg) Manufacturing [A1-a3] : 1599.194
    • Non-hazardous Waste Disposed Of (Kg) Manufacturing [A1-a3] : 276.4455
    • Total Use Of Non-renewable Primary Energy Resources (Primary Energy And Primary Energy Resources Used As Raw Materials) (Mj) Manufacturing [A1-a3] : 9431.67
    • Use Of Non-renewable Primary Energy Resources Used As Raw Materials (Mj) Total Life Cycle : 156.4913
    • Use Of Non-renewable Primary Energy Resources Used As Raw Materials (Mj) Manufacturing [A1-a3] : 156.4913
    • Use Of Non-renewable Primary Energy Excluding Non-renewable Primary Energy Resources Used As Raw Materials (Mj) Manufacturing [A1-a3] : 9275.208
    • Use Of Renewable Primary Energy Excluding Renewable Primary Energy Resources Used As Raw Materials (Mj) Manufacturing [A1-a3] : 164.6953
    • [In] Rated Current Pwr Loss Specifctn2 : 480.0 A
    • Customs Code : 8537109170
  • Environment Attributes Main
    • Ambient Air Temperature For Operation : -15-40 °C (without derating), -15-40 °C (without derating), 40-60 °C (with current derating of 2 % per °C), -15-40 °C (without derating), -15-40 °C (without derating)
    • Ambient Air Temperature For Storage : -25-70 °C, -25-70 °C
    • Operating Altitude : <= 3280.84 ft (1000 m) without derating, <= 3280.84 ft (1000 m) without derating, > 3280.84...13123.36 ft (> 1000...4000 m) with current derating 1 % per 100 m, > 3280.84...13123.36 ft (> 1000...4000 m) with current derating 1 % per 100 m<= 3280.84 ft (1000 m) without derating, <= 3280.84 ft (1000 m) without derating, > 3280.84...13123.36 ft (> 1000...4000 m) with current derating 1 % per 100 m, > 3280.84...13123.36 ft (> 1000...4000 m) with current derating 1 % per 100 m
    • Take Back : No
    • Recycled Metal Content At Cr Level : 0 %
    • China Rohs Regulation : X
    • Mercury Free : Yes
    • Carbon Footprint : 33462.2285558089
    • Circularity Profile : ENVEOLI2102013EN
    • Environmental Disclosure : ENVPEP2102013EN
    • Eu Rohs Directive : Compliant By Exemption
    • Ip Degree Of Protection : IP00
    • Packaging Made With Recycled Cardboard : Yes
    • Packaging Without Single Use Plastic : No
    • Reach Regulation : Reference contains Substances of Very High Concern above the threshold
    • Relative Humidity : 0-95 % without condensation or dripping water IEC 60068-2-3
    • Pep Code : ENVPEP2102013EN
    • Pep Verification Date : 2021-11-01
    • Pcr Version : PCR-ed3-EN-2015 04 02
    • Type Of Verification For The Pep : Independent external review
  • General Attributes
    • Phase : 3 phase
    • Product Or Component Type : soft starter
    • Range Of Product : Altivar Soft Starter ATS480
  • ETIM
    • ETIM 8 : EC000640
    • ETIM 9 : EC000640
  • Output Attributes
    • Discrete Output Type : DQ1) programmable digital output <= 30 V, DQ2) programmable digital output <= 30 V
    • Relay Output Type : relay outputs R1A 1 NO, relay outputs R1B 1 NOrelay outputs RIC NO/NC programmable
    • Analogue Output Number : 1
    • Analogue Output Type : current output AQ1 0...20 mA or 0...10 V 500 Ohm
    • Discrete Output Number : 2
    • Output Compatibility : open collector level 1 PLC IEC 65A-68
    • Output Current Drift : 150-700 %
    • Relay Output Number : 3
  • Input Attributes
    • Analogue Input Type : AI1/PTC PTC/Pt 100 temperature probe, PTC2 PTC/Pt 100 temperature probe, PTC3 PTC/Pt 100 temperature probe
    • Discrete Input Type : STOP) logic inputs, 3500 Ohm, RUN) logic inputs, 3500 OhmDI3) programmable as logic input, 3500 Ohm, DI4) programmable as logic input, 3500 Ohm
    • Input Compatibility : STOP discrete input level 1 PLC IEC 61131-2, RUN discrete input level 1 PLC IEC 61131-2, DI3 discrete input level 1 PLC IEC 61131-2, DI4 discrete input level 1 PLC IEC 61131-2
    • Analogue Input Number : 1
    • Discrete Input Logic : programmable digital input < 5 V
    • Discrete Input Number : 4
  • Specifications
    • Country of Origin : Brazil, China, France, Indonesia, Singapore, United States
    • Depth : 314.0 mm
  • Batteries & Runtime Attributes
    • Removable Battery : Yes