TeSys Deca Manual Starter and Protector, thermal magnetic circuit protector, push buttons, 1.6 to 2.5 A, screw clamp

SQD GV2ME07 MANUAL STARTER 600

SQDGV2ME07 GV2ME07 3389110343076
221.25 / EA
http://schema.org/OutOfStock
  • Country of Origin: Thailand
  • Depth: 78.5 mm
  • Height: 89 mm
  • Net Weight: 0.26 kg
  • Warranty Length: 18 mth
  • Weight: 0.26 kg
  • Width: 45 mm
The GV2 manual starter and protector provides manual isolation, manual motor control, and thermal overcurrent protection in one compact unit. The basic motor starter GV2ME controls motors with full load currents up to 32 A. The manual starter is three pole with horsepower ratings. The manual starter is operated by push buttons. The Class 10 ambient compensated thermal over current is adjustable from 1.6 ampere to 2.5 ampere. This device has screw clamp terminals. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX).
QTY
  • Product Description
  • Features
  • Specifications
The GV2 manual starter and protector provides manual isolation, manual motor control, and thermal overcurrent protection in one compact unit. The basic motor starter GV2ME controls motors with full load currents up to 32 A. The manual starter is three pole with horsepower ratings. The manual starter is operated by push buttons. The Class 10 ambient compensated thermal over current is adjustable from 1.6 ampere to 2.5 ampere. This device has screw clamp terminals. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX).
  • Prop 65
    • WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
  • Environment
    • Product Certifications : CCC || UL || CSA || EAC || ATEX || LROS (Lloyds register of shipping) || BV || RINA || DNV-GL || UKCA
    • Operating Altitude : 6561.68 ft (2000 m)
    • Ik Degree Of Protection : IK04
    • Mechanical Robustness : shocks 30 Gn for 11 ms || vibrations 5 Gn, 5...150 Hz
    • Ambient Air Temperature For Operation : -20-60 °C
    • Standards : EN/IEC 60947-2 || EN/IEC 60947-4-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || IEC/EN 60335-2-40:Annex JJ || IEC/EN 60335-1:Clause 30.2
    • Climatic Withstand : IACS E10
    • Ambient Air Temperature For Storage : -40-80 °C
    • Ip Degree Of Protection : IP20 IEC 60529
    • Fire Resistance : 960 °C IEC 60695-2-11
  • Contractual warranty
    • Warranty : 18 months
  • Environmental data
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Take-Back : No
    • Carbon Footprint (Kg Co2 Eq, Total Life Cycle) : 42.650938629908836
    • Packaging Made With Recycled Cardboard : Yes
    • Environmental Disclosure : ENVPEP121004
    • Packaging Without Single Use Plastic : No
    • Scip Number : 04104e70-ba29-493c-b2cc-b5837d1f879b
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Circularity Profile : ENVEOLI121004
  • Complementary
    • Line Rated Current : 2.5 A
    • [Ue] Rated Operational Voltage : 690 V AC 50/60 Hz IEC 60947-2
    • Rated Duty : continuous IEC 60947-4-1
    • Network Type : AC
    • [Ith] Conventional Free Air Thermal Current : 2.5 A IEC 60947-4-1
    • Motor Power Kw : 0.75-0.75 kW 400/415 V AC 50/60 Hz || 1.1-1.1 kW 500 V AC 50/60 Hz || 1.5-1.5 kW 690 V AC 50/60 Hz
    • Utilisation Category : category A IEC 60947-2 || AC-3 IEC 60947-4-1 || AC-3e IEC 60947-4-1
    • Net Weight : 0.26 kg
    • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947-2
    • [Ui] Rated Insulation Voltage : 690 V AC 50/60 Hz IEC 60947-2
    • Thermal Protection Adjustment Range : 1.6-2.5 A IEC 60947-4-1
    • Poles Description : 3P
    • Mounting Position : horizontal || vertical
    • Width : 45 mm
    • Depth : 78.5 mm
    • Network Frequency : 50/60 Hz IEC 60947-4-1
    • Height : 89 mm
    • Phase Failure Sensitivity : yes IEC 60947-4-1
    • Magnetic Tripping Current : 39-39 A
    • Fixing Mode : 35 mm symmetrical DIN rail clipped || panel screwed with adaptor plate)
    • [Ics] Rated Service Short-Circuit Breaking Capacity : 100 % 230/240 V AC 50/60 Hz IEC 60947-2 || 100 % 400/415 V AC 50/60 Hz IEC 60947-2 || 100 % 440 V AC 50/60 Hz IEC 60947-2 || 100 % 500 V AC 50/60 Hz IEC 60947-2 || 75 % 690 V AC 50/60 Hz IEC 60947-2
    • Control Type : push-button
    • Power Dissipation Per Pole : 2.5 W
    • Electrical Durability : 100000 cycles AC-3 415 V In || 100000 cycles AC-3e 415 V In
    • Breaking Capacity : 100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 500 V AC 50/60 Hz IEC 60947-2 || 3 kA Icu 690 V AC 50/60 Hz IEC 60947-2
    • Suitability For Isolation : yes IEC 60947-1
    • Tightening Torque : 1.7 N.m screw clamp terminal
    • Mechanical Durability : 100000 cycles
    • Color : dark grey
  • Specifications
    • Country of Origin : Thailand
    • Width : 45 mm
    • Height : 89 mm
    • Weight : 0.26 kg
    • Product Or Component Type : motor circuit breaker
    • Product Name : TeSys GV2
    • Trip Unit Technology : thermal-magnetic
    • Range : TeSys Deca
    • Device Application : motor protection
    • Device Short Name : GV2ME