Motor circuit breaker, TeSys GV4, 3P, 50A, Icu 50kA, thermal magnetic, Everlink terminals

Motor circuit breaker, TeSys G

SQDGV4P50N GV4P50N 3606481310361
969.31 / EA
http://schema.org/OutOfStock
  • Country of Origin: Poland
  • Depth: 165 mm
  • Height: 155 mm
  • Net Weight: 1.6 kg
  • Operating Position: Any Position
  • Warranty Length: 18 mth
  • Weight: 1.6 kg
  • Width: 81 mm
TeSys GV motor circuit breaker, 3 poles (3P), 50A/690V, for protection of 3-phase motors 11-22kW@400V. It provides thermal magnetic protection and additional motor protection functions, breaking capacity Icu 50kA@400V, start-stop control by rotary handle, connection by Everlink BTR screw terminals. Thermal protection adjustable by dials with a setting current Ir in range 20-50A and a selectable tripping class 10 or 20, magnetic protection at 17 In. Additional protections have fixed pick-up and include short time delay protection Isd at 13 Ir, phase unbalance and loss protection, ground fault protection. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX).
QTY
  • Product Description
  • Specifications
TeSys GV motor circuit breaker, 3 poles (3P), 50A/690V, for protection of 3-phase motors 11-22kW@400V. It provides thermal magnetic protection and additional motor protection functions, breaking capacity Icu 50kA@400V, start-stop control by rotary handle, connection by Everlink BTR screw terminals. Thermal protection adjustable by dials with a setting current Ir in range 20-50A and a selectable tripping class 10 or 20, magnetic protection at 17 In. Additional protections have fixed pick-up and include short time delay protection Isd at 13 Ir, phase unbalance and loss protection, ground fault protection. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX).
  • Environment
    • Product Certifications : IEC || UL || CSA || CCC || EAC || ATEX || EU-RO MR
    • Ik Degree Of Protection : IK07 IEC 62262
    • Ambient Air Temperature For Operation : -25-70 °C
    • Standards : CSA C22.2 No 60947-4-1 || UL 60947-4-1 || EN/IEC 60947-4-1 || EN/IEC 60947-2
    • Climatic Withstand : IACS E10
    • Pollution Degree : 3
    • Ambient Air Temperature For Storage : -50-85 °C
    • Ip Degree Of Protection : IP40 IEC 60529
    • Operating Altitude : 5000 m
    • Fire Resistance : 960 °C IEC 60695-2-11
  • Contractual warranty
    • Warranty : 18 months
  • Environmental data
    • Rohs Exemption Information : Yes
    • Packaging Made With Recycled Cardboard : Yes
    • Mercury Free : Yes
    • Environmental Disclosure : ENVPEP1704004EN
    • Halogen Content Performance : Halogen free plastic parts product
    • Packaging Without Single Use Plastic : Yes
    • Weee Label : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Scip Number : 1b259a2c-3a3c-401a-acdd-f0837efd4018
    • Reach Regulation : Reference contains Substances of Very High Concern above the threshold
    • Circularity Profile : ENVEOLI1704004EN
    • Take-Back : No
    • Carbon Footprint Of The Use Phase [B2, B3, B4, B6] : 74.322
    • Carbon Footprint Of The Manufacturing Phase [A1 To A3] : 12.045295696724102
    • Carbon Footprint Of The Distribution Phase [A4] : 0.5 kg CO2 eq.
    • Pvc Free : Yes
    • Carbon Footprint Of The Installation Phase [A5] : 0.5 kg CO2 eq.
    • Sustainable Packaging : Yes
    • Total Lifecycle Carbon Footprint : 91 kg CO2 eq.
    • Eu Rohs Directive : Not compliant
    • Carbon Footprint Of The End-Of-Life Phase [C1 To C4] : 4.104600403965412
    • Carbon Footprint (Kg Co2 Eq, Total Life Cycle) : 91.43519324757494
  • Complementary
    • Mechanical Robustness : vibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 || vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 || shocks 15 gn 11 ms IEC 60068-2-27
    • Line Rated Current : 50 A
    • [Ue] Rated Operational Voltage : 690 V AC 50/60 Hz IEC 60947-2
    • Height : 155 mm
    • Phase Failure Sensitivity : yes IEC 60947-4-1
    • Rated Duty : continuous IEC 60947-4-1
    • Magnetic Tripping Current : 850-850 A
    • [Ith] Conventional Free Air Thermal Current : 115 A IEC 60947-4-1
    • Motor Power Kw : 11-11 kW 400...415 V AC 50/60 Hz || 15-15 kW 500 V AC 50/60 Hz || 18.5-18.5 kW 660...690 V AC 50/60 Hz || 15-15 kW 400...415 V AC 50/60 Hz || 18.5-18.5 kW 400...415 V AC 50/60 Hz || 22-22 kW 400...415 V AC 50/60 Hz || 18.5-18.5 kW 500 V AC 50/60 Hz || 22-22 kW 500 V AC 50/60 Hz || 30-30 kW 500 V AC 50/60 Hz || 22-22 kW 660...690 V AC 50/60 Hz || 30-30 kW 660...690 V AC 50/60 Hz || 37-37 kW 660...690 V AC 50/60 Hz || 45-45 kW 660...690 V AC 50/60 Hz
    • Maximum Operating Rate : 25 cyc/h
    • Operating Position : any position
    • Connections - Terminals : EverLink BTR screw connectors top) 1 1.5-70 mm² - solid || EverLink BTR screw connectors top) 1 1.5-50 mm² - flexible || EverLink BTR screw connectors bottom) 1 2.5-95 mm² - solid || EverLink BTR screw connectors bottom) 1 2.5-70 mm² - flexible
    • Utilisation Category : category A IEC 60947-2 || AC-3 IEC 60947-4-1
    • Net Weight : 1.6 kg
    • [Uimp] Rated Impulse Withstand Voltage : 8 kV IEC 60947-2
    • Control Type : rotary handle
    • Power Dissipation Per Pole : 4.6 W
    • Electrical Durability : 20000 cycles AC-3 440 V In/2 || 10000 cycles AC-3 440 V In
    • Breaking Capacity : 100 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 || 50 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 || 50 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 15 kA Icu 525 V AC 50/60 Hz IEC 60947-2 || 65 kA 208Y/120 V AC 50/60 Hz UL 60947 || 65 kA 240 V AC 50/60 Hz UL 60947 || 35 kA 480Y/277 V AC 50/60 Hz UL 60947 || 8 kA Icu 660...690 V AC 50/60 Hz IEC 60947-2 || 25 kA Icu 500 V AC 50/60 Hz IEC 60947-2 || 18 kA 600Y/347 V AC 50/60 Hz UL 60947
    • Suitability For Isolation : yes IEC 60947-1
    • [Ui] Rated Insulation Voltage : 800 V AC 50/60 Hz IEC 60947-2
    • Tightening Torque : 9 N.m 16-95 mm² || 5 N.m 1.5-10 mm²
    • Mechanical Durability : 40000 cycles
    • Poles Description : 3P
    • Color : Gray RAL 7016)
    • Width : 81 mm
    • Depth : 165 mm
  • Specifications
    • Country of Origin : Poland
    • Width : 81 mm
    • Height : 155 mm
    • Weight : 1.6 kg
    • Range Of Product : TeSys GV4
    • Product Or Component Type : motor circuit breaker
    • Product Name : TeSys GV4
    • Range : TeSys Deca
    • Device Application : motor protection
    • Device Short Name : GV4P
    • Trip Unit Technology : electronic || thermal-magnetic