TeSys F - contactor coil - LX1FL - 110...120 V AC 40...400 Hz

CONTACTOR COIL 120VAC IEC

SQDLX1FL110 LX1FL110 3389110082401
570.12 / EA
http://schema.org/OutOfStock
  • Country of Origin: Czechia
  • Net Weight: 1.5 kg
  • Warranty Length: 18 mth
  • Weight: 1.5 kg
TeSys F AC coil 110/115V 40-400Hz (voltage code F7/FE7), low sealed consumption, for TeSys F 3-pole and 4-pole contactors LC1F630, LC1F1250. It operates in the voltage limits 0.85-1.1 Uc and environments until 55°C. It provides to the contactor high operating rates until 1200 cycles/hour.
QTY
  • Product Description
  • Specifications
TeSys F AC coil 110/115V 40-400Hz (voltage code F7/FE7), low sealed consumption, for TeSys F 3-pole and 4-pole contactors LC1F630, LC1F1250. It operates in the voltage limits 0.85-1.1 Uc and environments until 55°C. It provides to the contactor high operating rates until 1200 cycles/hour.
  • Environment
    • Ambient Air Temperature For Operation : -5-55 °C
    • Net Weight : 1.5 kg
  • Contractual warranty
    • Warranty : 18 months
  • Environmental data
    • Packaging Made With Recycled Cardboard : No
    • Environmental Disclosure : ENVPEP1505009EN
    • Packaging Without Single Use Plastic : No
    • Circularity Profile : ENVEOLI1505009EN
    • Take-Back : No
  • Complementary
    • Control Circuit Voltage Limits : operational 0.85...1.1 Uc 40...400 Hz 55 °C) || drop-out 0.25...0.5 Uc 40...400 Hz 55 °C)
    • Inrush Power In Va : 1650-1650 VA 40...400 Hz cos phi 0.9 (at 20 °C)
    • Coil Technology : without built-in suppressor module
    • Hold-In Power Consumption In Va : 22-22 VA 40...400 Hz cos phi 0.3 (at 20 °C)
    • Heat Dissipation : 20-20 W 40...400 Hz
  • Specifications
    • Country of Origin : Czechia
    • Weight : 1.5 kg
    • Average Resistance : 6.45 Ohm inrush 20 °C || 165 Ohm holding 20 °C
    • [Uc] Control Circuit Voltage : 110...120 V AC 40...400 Hz
    • Control Circuit Type : AC 40...400 Hz
    • Range Compatibility : TeSys TeSys F LC1F contactor
    • Product Or Component Type : contactor coil
    • Range : TeSys
    • Inductance Of Closed Circuit : 1.85 H
    • Maximum Operating Rate : 1200 cyc/h 55 °C
    • Operating Time : 100...200 ms opening || 40...80 ms closing
    • Product Compatibility : LC1F1250 || LC1F630
    • Device Short Name : LX1FL
    • Mechanical Durability : 5 Mcycles