TeSys D, replacement coil, for LC1D80 and LC1D95 contactors, 120 VAC 50/60 Hz coil

RELAY COIL 120V 50/60 HZ

SQDLX1D6G7 LX1D6G7 3389110208511
243.17 / EA
http://schema.org/OutOfStock
  • Net Weight: 0.28 kg
  • Warranty Length: 18 mth
TeSys D replacement coils are for replacing the operating coil in old TeSys D contactors with 40 amperes to 95 ampere ratings. This coil has an operating voltage of 120 Vac 50/60 Hz. This coil has an inrush consumption rating of 220 VA and a sealed consumpation rating ofd 22 VA. The 60Hz operating range is 85 to 110% of nomial voltage at 55 degrees C.
QTY
  • Product Description
  • Specifications
TeSys D replacement coils are for replacing the operating coil in old TeSys D contactors with 40 amperes to 95 ampere ratings. This coil has an operating voltage of 120 Vac 50/60 Hz. This coil has an inrush consumption rating of 220 VA and a sealed consumpation rating ofd 22 VA. The 60Hz operating range is 85 to 110% of nomial voltage at 55 degrees C.
  • Environment
    • Ambient Air Temperature For Operation : -5-60 °C
    • Net Weight : 0.28 kg
  • Contractual warranty
    • Warranty : 18 months
  • Offer Sustainability
    • Rohs Exemption Information : Yes
    • Mercury Free : Yes
    • Environmental Disclosure : ENVPEP110205EN
    • Sustainable Offer Status : Green Premium product
    • Reach Regulation : Reference contains Substances of Very High Concern above the threshold
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Reach Free Of Svhc : Yes
    • China Rohs Regulation : Product out of China RoHS scope. Substance declaration for your information.
    • Circularity Profile : N/A
    • Eu Rohs Directive : Pro-active compliance (Product out of EU RoHS legal scope)
  • Complementary
    • Control Circuit Voltage Limits : drop-out: 0.3...0.6 Uc at 50/60 Hz (at <55 °C) || operational: 0.8...1.1 Uc at 50 Hz (at <55 °C) || operational: 0.85...1.1 Uc at 60 Hz (at <55 °C)
    • Inrush Power In Va : 245-245 VA 60 Hz cos phi 0.75 (at 20 °C) || 245-245 VA 50 Hz cos phi 0.75 (at 20 °C)
    • Coil Technology : without built-in suppressor module
    • Hold-In Power Consumption In Va : 26-26 VA 60 Hz cos phi 0.3 (at 20 °C) || 26-26 VA 50 Hz cos phi 0.3 (at 20 °C)
    • Heat Dissipation : 6-10 W 50/60 Hz
  • Specifications
    • Average Resistance : 32 Ohm 20 °C
    • [Uc] Control Circuit Voltage : 120 V AC 50/60 Hz
    • Control Circuit Type : AC 50/60 Hz
    • Product Or Component Type : contactor coil
    • Range : TeSys
    • Inductance Of Closed Circuit : 2 H
    • Maximum Operating Rate : 3600 cyc/h 60 °C
    • Mechanical Durability : 4 Mcycles
    • Product Compatibility : LC1D40 || LC1D50 || LC1D65...D95
    • Device Short Name : LX1D6