Time delay auxiliary contact block, TeSys Deca, 1NO + 1NC, off delay 0.3-3s, front, lugs-ring terminals

Time delay auxiliary contact b

SQDLADR06 LADR06 3389110821673
173.75 / EA
http://schema.org/OutOfStock
  • Country of Origin: France
  • Depth: 61 mm
  • Height: 48 mm
  • Warranty Length: 18 mth
  • Width: 44 mm
TeSys Deca time delay auxiliary contact block, for contactors LC1D and control relays CAD. It provides 1NO+1NC contacts rated up to 10A 690V AC, Off-delay setting range 0.3-3s, connection by lugs-ring terminals. Clip-on front mounting, it procures high reliability and durability. Multi standards certified (IEC, UL, CSA, CCC, EAC).
QTY
  • Product Description
  • Features
  • Specifications
TeSys Deca time delay auxiliary contact block, for contactors LC1D and control relays CAD. It provides 1NO+1NC contacts rated up to 10A 690V AC, Off-delay setting range 0.3-3s, connection by lugs-ring terminals. Clip-on front mounting, it procures high reliability and durability. Multi standards certified (IEC, UL, CSA, CCC, EAC).
  • Prop 65
    • WARNING: Cancer - www.P65Warnings.ca.gov
  • Environment
    • Ambient Air Temperature For Operation : -40-70 °C
    • Ip Degree Of Protection : IP20 conforming to IEC 60529
    • Ambient Air Temperature For Storage : -60-80 °C
    • Environmental Characteristic : normal environment
    • Protective Treatment : TH IEC 60068
    • Operating Altitude : 9842.52 ft (3000 m)
  • Contractual warranty
    • Warranty : 18 months
  • Environmental data
    • Packaging Made With Recycled Cardboard : Yes
    • Environmental Disclosure : ENVPEP110702EN_V01
    • Packaging Without Single Use Plastic : Yes
    • Scip Number : 116c8fe4-0538-43fb-9c58-cfc8259b5fbc
    • California Proposition 65 : WARNING: Cancer - www.P65Warnings.ca.gov
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Circularity Profile : N/A
    • Take-Back : No
    • Pvc Free : Yes
    • Carbon Footprint (Kg Co2 Eq, Total Life Cycle) : 3.8592674729932326
  • Complementary
    • Non-Overlap Time : 1.5 ms on de-energisation no overlap between NC and NO contact || 1.5 ms on energisation no overlap between NC and NO contact
    • Permissible Short-Time Rating : 100 A 60 °C 1 s || 120 A 60 °C 500 ms || 140 A 60 °C 100 ms
    • Minimum Switching Current : 5 mA
    • Height : 48 mm
    • Protection Type : gG fuse 10 A
    • Insulation Resistance : > 10 MOhm
    • Irms Rated Making Capacity : 140 A AC || 250 A DC
    • Connections - Terminals : lugs-ring terminals 8 mm)
    • Minimum Switching Voltage : 17 V
    • Tightening Torque : 1.7 N.m flat Ø 6 mm || 1.7 N.m Philips No 2 || 1.7 N.m pozidriv No 2
    • Mechanical Durability : 5 Mcycles
    • Color : dark grey
    • Width : 44 mm
    • Depth : 61 mm
  • Specifications
    • Country of Origin : France
    • Width : 44 mm
    • Height : 48 mm
    • Product Certifications : IECEE CB Scheme || UL || CSA || CCC || EAC || UKCA
    • [Ith] Conventional Free Air Thermal Current : 10 A (at 60 °C)
    • Timer Type : off delay
    • [Ue] Rated Operational Voltage : 690 V AC 25...400 Hz
    • Standards : EN/IEC 60947-5-1 || UL 60947-5-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.5 || EN 50012 || IEC 60335-1:Clause 30.2 || IEC 60335-2-40:Annex JJ || UL 60335-2-40:Annex JJ
    • Range Compatibility : TeSys D CAD || TeSys D LC1D || TeSys F LC1F || TeSys F CR1F || TeSys Deca CAD || TeSys Deca LC1D
    • Product Or Component Type : time delay auxiliary contact block
    • Product Name : TeSys Deca
    • Range : TeSys || TeSys Deca
    • Mounting Location : front
    • Pole Contact Composition : 1 NO + 1 NC
    • [Ui] Rated Insulation Voltage : 690 V IEC 60947-5-1 || 600 V UL 60947-5-1 || 600 V CSA C22.2 No 60947-5-1
    • [Ie] Rated Operational Current : 6 A at 120 V AC-15 || 1.04 A at 690 V AC-15 || 0.55 A at 125 V DC-13 || 0.1 A at 600 V DC-13
    • Time Delay Range : 0.3...3 s
    • Auxiliary Contacts Operation : time delay