Country of Origin:
Czechia
-
Depth:
66 mm
-
Height:
89 mm
-
Net Weight:
0.105 kg
-
Warranty Length:
18 mth
-
Weight:
0.105 kg
-
Width:
18 mm
TeSys GV electrical trip, MX shunt release, 220-240V AC 60Hz, for motor circuit breakers GV2, GV3. It trips the circuit breaker when the control voltage is applied in limits 0.7-1.1 Uc with an impulse duration greater than 20ms or a maintained signal. To be mounted on right-hand side of the circuit breaker, connection by screw clamp terminals. Multi standards certified (IEC, UL, CSA, CCC, EAC).