SQUARE D

TeSys Deca thermal overload relays - 16...24 A - class 10A

TeSys Deca thermal overload relays - 16...24 A - class 10A

SQDLRD226 LRD226 3389110822779
139.44 / EA
http://schema.org/OutOfStock
  • Depth: 70 mm
  • Dielectric Strength: 1.89 kV, 50 Hz
  • Warranty Length: 18 mth
TeSys LRD thermal overload relay, 24A/690V, thermal setting range 16-24A, tripping class 10A, for protection of 3-phase motors 11kW@400V. Differential device with phase failure and load unbalance detection. It provides a thermal adjustement dial, a manual-automatic reset selector, a test selector for simulation of a tripping, reset and stop buttons, a flag indicator and 2 auxiliary contacts 1NO+1NC for fault signalling. Settings are protected by a transparent cover lockable by sealing. Connection by screw clamp terminals, it connects directly to the bottom terminals of 3-pole contactors LC1D25-D38. Mounting on DIN rail or screw fixing, separated from the contactor, with use of a terminal block LAD7B106 (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, ATEX, Marine).
QTY
  • Product Description
  • Features
  • Specifications
TeSys LRD thermal overload relay, 24A/690V, thermal setting range 16-24A, tripping class 10A, for protection of 3-phase motors 11kW@400V. Differential device with phase failure and load unbalance detection. It provides a thermal adjustement dial, a manual-automatic reset selector, a test selector for simulation of a tripping, reset and stop buttons, a flag indicator and 2 auxiliary contacts 1NO+1NC for fault signalling. Settings are protected by a transparent cover lockable by sealing. Connection by screw clamp terminals, it connects directly to the bottom terminals of 3-pole contactors LC1D25-D38. Mounting on DIN rail or screw fixing, separated from the contactor, with use of a terminal block LAD7B106 (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, ATEX, Marine).
  • Prop 65
    • WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
  • Conformance Attributes
    • Product Certifications : IEC, UL, CSA, CCC, EAC, BV, RINA, DNV-GL, LROS (Lloyds register of shipping), ATEX INERIS, UKCA
    • Standards : EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, UL 60947-5-1, CSA C22.2 No 60947-4-1, CSA C22.2 No 60947-5-1, GB/T 14048.4, GB/T 14048.5, EN 50495
  • Complementary Attributes
    • Ui Rated Insulation Voltage : power circuit 600 V CSA, power circuit 600 V UL, power circuit 690 V IEC 60947-4-1
    • Ue Rated Operational Voltage : 690 V AC 0...400 Hz power circuit IEC 60947-4-1
    • Uimp Rated Impulse Withstand Voltage : 6 kV
  • Important Information Attributes
    • Associated Fuse Rating : 4 A gG for signalling circuit, 4 A BS for signalling circuit
    • Control Type : Red push-button stop, Blue push-button reset
    • Mechanical Robustness : vibrations6 Gn IEC 60068-2-6, shocks15 Gn for 11 ms IEC 60068-2-7
    • Mounting Support : plate, with specific accessories, rail, with specific accessories, under contactor
    • Network Type : DC, AC
    • Permissible Current : 1.5 A 240 V AC-15 signalling circuit, 0.1 A 250 V DC-13 signalling circuit
    • Product Name : TeSys LRD, TeSys Deca
    • Range : TeSys, TeSys Deca
    • Temperature Compensation : -20-60 °C, -20-60 °C
    • Tightening Torque : control circuit 1.7 N.m screw clamp terminals, power circuit 2.3 N.m lugs-ring terminals M4
    • Connections Terminals : control circuit screw clamp terminals 2 1-2.5 mm² flexible without cable end, control circuit screw clamp terminals 2 1-2.5 mm² flexible with cable end, control circuit screw clamp terminals 2 1-2.5 mm² solid without cable end, power circuit lugs-ring terminals
    • Carbon Footprint Of The Distribution Phase A4 : 0.223194662, 0.2 kg CO2 eq.
    • Carbon Footprint Of The End Of Life Phase C1 To C4 : 0.4 kg CO2 eq., 0.365021809
    • Carbon Footprint Of The Installation Phase A5 : 0.025536289, 0 kg CO2 eq.
    • Carbon Footprint Of The Manufacturing Phase A1 To A3 : 0.2 kg CO2 eq., 0.189450077
    • Carbon Footprint Of The Use Phase B2 B3 B4 B6 : 2 kg CO2 eq., 1.896335784
    • Local Data Status : Publishable
    • Local Publishable Date : 2025-05-31
    • Return Indicator : N
    • Stocking Flag : Y
    • Stock Policy : 2
    • Device Type : Relay, Control & Measurement - Protection relay
    • Serviceability : No
    • Traceability : No
    • Legacy Weee Scope : In
    • Weee Product Category : 5
    • Scope Perimeter : At least in Europe
    • Eoli Availability Display : Yes
    • End Of Life Doc Ref : ENVEOLI0804005
    • Reach Full Compliance Status : Free of Substances of Very High Concern above the threshold
    • Reach Full Compliance Status Id : NOT_CONTAINING_SVHC
    • Reach Compliance Directive : Free of Substances of Very High Concern above the threshold
    • Rohs Eur In Scope : Yes
    • Rohs Eur Status : Compliant By Exemption
    • Rohs Eur Conformity Date : 1851
    • Rohs Eur Full Compliance Status : Compliant By Exemption
    • China Rohs In Scope : No
    • With Recycled Cardboard : Yes
    • Without Single Use Plastic : Yes
    • Product Contributes To Saved And Avoided Emissions : No
    • Product Kit Identifier : N
    • Compatibility Code : LRD
    • Connection Pitch : 17.5 mm
    • Device Short Name : LRD
    • Dielectric Strength : 1.89 kV 50 Hz IEC 60947-1
    • Flame Retardance : V1 conforming to UL 94
    • Network Frequency : 0...400 Hz
    • Phase Failure Sensitivity : tripping current 130 % of Ir on two phase, the last one at 0
    • Product Availability : Non-Stock - Not normally stocked in distribution facility
    • Product Or Component Type : differential thermal overload relay
    • Relay Application : motor protection
    • Returnability : No
    • Software Version : v6.1
    • Sustainable Packaging : No
    • Thermal Overload Class : class 10A IEC 60947-4-1
    • Thermal Protection Adjustment Range : 16-24 A
    • Total Lifecycle Carbon Footprint : 3 kg CO2 eq.
    • Tripping Threshold : 1.14 +/- 0.06 Ir IEC 60947-4-1
    • Weee Label : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Ith Conventional Free Air Thermal Current : 5 A signalling circuit
    • Warranty In Months : 18
    • R Thermal Protection Adj Range : 16-24 A
    • Pep Code : ENVPEP0802006EN
    • Database Version : 2023-02
    • Pep Verification Date : 2024-06-01
    • Pcr Version : PCR-4-ed4-EN-2021 09 06
    • Psr Version : PSR-0005-ed3.1-EN-2023 12 08
    • Type Of Verification For The Pep : Independent internal review
    • Data Source : extrapolated product
    • Functional Unit Description : The functional unit of the LRD365 is to detect overload currents in order to protect the load for 20 years.
    • Functional Unit Quantity : 1
    • Functional Unit Unit : unit
    • Product Weight In G2 : 181
    • Reference Lifetime In Y2 : 20
    • Energy Consumption On Product Lifetime In Kwh : 28.3824
    • Energy Model Manufacturing A1 A3 2 : France, FR
    • Energy Model Installation A5 2 : Electricity Mix; Low voltage; 2018; France, FR
    • Energy Model Use B6 2 : Electricity Mix; Low voltage; 2018; France, FR
    • Energy Model End Of Life C1 C4 2 : Electricity Mix; Low voltage; 2018; France, FR
    • Recyclability Potential In 2 : 27
    • Offer Owner Code : 190788
    • Height Nominal : 66 mm
    • Width Nominal : 45 mm
  • Environment Attributes Main
    • China Rohs Regulation : Product out of China RoHS scope , Product out of China RoHS scope. Substance declaration for your information.
    • Ambient Air Temperature For Operation : -20-60 °C without derating IEC 60947-4-1, -20-60 °C without derating IEC 60947-4-1, -20-60 °C without derating IEC 60947-4-1, -20-60 °C without derating IEC 60947-4-1, -20-60 °C without derating IEC 60947-4-1, -20-60 °C without derating IEC 60947-4-1
    • Product Compatibility : LC1D32, LC1D25, LC1D38
    • Take Back : No
    • Reach Free Shvc : Yes
    • Recycled Metal Content At Cr Level : 0 %
    • Carbon Footprint : 2.699538621
    • Ambient Air Temperature For Storage : -60-70 °C
    • Circularity Profile : ENVEOLI0804005
    • Climatic Withstand : IACS E10
    • Environmental Disclosure : ENVPEP0802006EN
    • Eu Rohs Directive : Compliant By Exemption
    • Ip Degree Of Protection : IP20 conforming to IEC 60529
    • Packaging Made With Recycled Cardboard : Yes
    • Packaging Without Single Use Plastic : Yes
    • Reach Free Of Svhc : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Pep Code : ENVPEP0802006EN
    • Pep Verification Date : 2024-06-01
    • Pcr Version : PCR-4-ed4-EN-2021 09 06
    • Psr Version : PSR-0005-ed3.1-EN-2023 12 08
    • Type Of Verification For The Pep : Independent internal review
  • General Attributes
    • Product Or Component Type : differential thermal overload relay
  • ETIM
    • ETIM 8 : EC000106
    • ETIM 9 : EC000106
  • Contractual Warranty Attributes
    • Warranty Period : 18 months
    • Warranty : 18 months
  • Specifications
    • Country of Origin : Brazil, France
    • Depth : 70 mm