TeSys Deca thermal overload relays , 110...140A , class 10A

BIMETALLIC OVERLOAD RELAY 600V

SQDLRD33696 LRD33696 3389110522563
716.62 / EA
http://schema.org/OutOfStock
  • Country of Origin: France
  • Dielectric Strength: 2.2 kV, 50 Hz
  • Height: 123 mm
  • Net Weight: 1 kg
  • Warranty Length: 18 mth
  • Weight: 1 kg
QTY
  • Features
  • Specifications
  • Prop 65
    • WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
  • Environment
    • Product Certifications : IEC || UL || CSA || CCC || EAC || ATEX INERIS || UKCA
    • Mechanical Robustness : vibrations6 Gn IEC 60068-2-6 || shocks15 Gn for 11 ms IEC 60068-2-7
    • Standards : EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-4-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4 || GB/T 14048.5 || EN 50495
    • Climatic Withstand : IACS E10
    • Ambient Air Temperature For Operation : -20-60 °C without derating IEC 60947-4-1
    • Dielectric Strength : 2.2 kV 50 Hz IEC 60947-1
    • Ip Degree Of Protection : IP20 conforming to IEC 60529
    • Flame Retardance : V1 conforming to UL 94
    • Ambient Air Temperature For Storage : -60-70 °C
  • Contractual warranty
    • Warranty : 18 months
  • Environmental data
    • Packaging Made With Recycled Cardboard : Yes
    • Environmental Disclosure : ENVPEP110101EN
    • Packaging Without Single Use Plastic : No
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Circularity Profile : ENVEOLI1101001
    • Take-Back : No
    • Carbon Footprint (Kg Co2 Eq, Total Life Cycle) : 7.9404414349
  • Complementary
    • Network Frequency : 0...400 Hz
    • Height : 123 mm
    • [Ith] Conventional Free Air Thermal Current : 5 A signalling circuit
    • Auxiliary Contact Composition : 1 NO + 1 NC
    • Connections - Terminals : power circuit screw clamp terminals 1 4-35 mm² flexible without cable end || power circuit screw clamp terminals 1 4-35 mm² flexible with cable end || power circuit screw clamp terminals 1 4-35 mm² solid without cable end || control circuit screw clamp terminals 2 1-2.5 mm² flexible without cable end || control circuit screw clamp terminals 2 1-2.5 mm² flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm² solid without cable end
    • Phase Failure Sensitivity : tripping current 130 % of Ir on two phase, the last one at 0
    • [Ue] Rated Operational Voltage : 1000 V AC 0...400 Hz power circuit IEC 60947-4-1
    • Associated Fuse Rating : 4 A gG for signalling circuit || 4 A BS for signalling circuit
    • Net Weight : 1 kg
    • [Uimp] Rated Impulse Withstand Voltage : 6 kV
    • Permissible Current : 0.72 A 500 V AC-15 signalling circuit || 0.06 A 440 V DC-13 signalling circuit
    • Tripping Threshold : 1.14 +/- 0.06 Ir IEC 60947-4-1
    • Tightening Torque : control circuit 1.7 N.m screw clamp terminals || power circuit 9 N.m screw clamp terminals
    • Control Type : Red push-button stop || Blue push-button reset
    • Mounting Support : plate || rail
    • Temperature Compensation : -20-60 °C
  • Specifications
    • Country of Origin : France
    • Height : 123 mm
    • Weight : 1 kg
    • Network Type : AC || DC
    • Thermal Protection Adjustment Range : 110-140 A
    • Relay Application : motor protection
    • Product Or Component Type : differential thermal overload relay
    • Product Name : TeSys LRD || TeSys Deca
    • Thermal Overload Class : class 10A IEC 60947-4-1
    • Range : TeSys
    • [Ui] Rated Insulation Voltage : power circuit 750 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL
    • Product Compatibility : LC1D150
    • Device Short Name : LRD