SQUARE D

Thermal overload relay,TeSys Deca,0.25-0.4A,1NO+1NC,class 10A,lugs terminal,for unbalanced loads

BI-METALLIC OVERLOAD RELAY 600

SQDLR3D036 LR3D036 3389110377958
75.86 / EA
http://schema.org/OutOfStock
  • Country of Origin: France
  • Depth: 70 mm
  • Dielectric Strength: 1.89 kV, 50 Hz
  • Height: 66 mm
  • Net Weight: 0.124 kg
  • Warranty Length: 18 mth
  • Weight: 0.124 kg
  • Width: 45 mm
QTY
  • Features
  • Specifications
  • Prop 65
    • WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
  • Environment
    • Product Certifications : IEC || UL || CSA || CCC || EAC || BV || RINA || DNV-GL || LROS (Lloyds register of shipping) || ATEX INERIS || UKCA
    • Mechanical Robustness : vibrations6 Gn IEC 60068-2-6 || shocks15 Gn for 11 ms IEC 60068-2-7
    • Standards : EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-4-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4 || GB/T 14048.5 || EN 50495
    • Climatic Withstand : IACS E10
    • Ambient Air Temperature For Operation : -20-60 °C without derating IEC 60947-4-1
    • Dielectric Strength : 1.89 kV 50 Hz IEC 60947-1
    • Ip Degree Of Protection : IP20 conforming to IEC 60529
    • Flame Retardance : V1 conforming to UL 94
    • Ambient Air Temperature For Storage : -60-70 °C
  • Contractual warranty
    • Warranty : 18 months
  • Environmental data
    • Rohs Exemption Information : Yes
    • Packaging Made With Recycled Cardboard : Yes
    • Mercury Free : Yes
    • Environmental Disclosure : ENVPEP080206EN
    • Packaging Without Single Use Plastic : Yes
    • Toxic Heavy Metal Free : Yes
    • Scip Number : 224fb0ea-2bc1-482e-b6b4-c1bdd9779659
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Reach Free Of Svhc : Yes
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Circularity Profile : ENVEOLI0802006
    • Take-Back : No
    • Sustainable Packaging : Yes
    • Eu Rohs Directive : Compliant
    • Carbon Footprint (Kg Co2 Eq, Total Life Cycle) : 12.871496130184847
  • Complementary
    • Network Frequency : 0...400 Hz
    • Height : 66 mm
    • Auxiliary Contact Composition : 1 NO + 1 NC
    • [Ith] Conventional Free Air Thermal Current : 5 A signalling circuit
    • Connection Pitch : 14.5 mm
    • Connections - Terminals : control circuit screw clamp terminals 2 1-2.5 mm² flexible without cable end || control circuit screw clamp terminals 2 1-2.5 mm² flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm² solid without cable end || power circuit lugs-ring terminals
    • Phase Failure Sensitivity : tripping current 130 % of Ir on two phase, the last one at 0
    • [Ue] Rated Operational Voltage : 690 V AC 0...400 Hz power circuit IEC 60947-4-1
    • Associated Fuse Rating : 4 A gG for signalling circuit || 4 A BS for signalling circuit
    • Net Weight : 0.124 kg
    • [Uimp] Rated Impulse Withstand Voltage : 6 kV
    • Permissible Current : 3 A 120 V AC-15 signalling circuit || 0.22 A 125 V DC-13 signalling circuit
    • Tripping Threshold : 1.14 +/- 0.06 Ir IEC 60947-4-1
    • Tightening Torque : control circuit 1.7 N.m screw clamp terminals || power circuit 2.3 N.m lugs-ring terminals M4
    • Control Type : Red push-button stop || Blue push-button reset
    • Mounting Support : plate, with specific accessories || rail, with specific accessories || under contactor
    • Width : 45 mm
    • Depth : 70 mm
    • Temperature Compensation : -20-60 °C
  • Specifications
    • Country of Origin : France
    • Width : 45 mm
    • Height : 66 mm
    • Weight : 0.124 kg
    • Thermal Protection Adjustment Range : 0.25-0.4 A
    • Network Type : DC || AC
    • Relay Application : motor protection
    • Product Or Component Type : non differential thermal overload relay
    • Product Name : TeSys LRD || TeSys Deca
    • Thermal Overload Class : class 10A IEC 60947-4-1
    • Range : TeSys
    • [Ui] Rated Insulation Voltage : power circuit 600 V CSA || power circuit 600 V UL || power circuit 690 V IEC 60947-4-1
    • Product Compatibility : LC1D32 || LC1D25 || LC1D18 || LC1D09 || LC1D38 || LC1D12
    • Device Short Name : LR3D