SQUARE D

Motor Management, TeSys T, motor controller, Ethernet/IP, Modbus/TCP, 6 inputs, 3 outputs, 1.35 to 27A, 100 to 240 VAC

Motor Management, TeSys T, motor controller, Ethernet/IP, Modbus/TCP, 6 inputs, 3 outputs, 1.35 to 27A, 100 to 240 VAC

SQDLTMR27EFM LTMR27EFM 3389119404891
1014.69 / EA
http://schema.org/OutOfStock
  • Certifications: ABS, ATEX, BV, CCC, CSA, C-tick, DNV, EAC, GL, KERI, LROS (Lloyds Register Of Shipping), NOM, RINA, RMRoS, UL
  • Current: 8-62.8 mA
  • Depth: 122.5 mm
  • Height: 61 mm
  • Net Weight: 0.53 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, IACS E10, IEC 60947-4-1, UL 508
  • Storage Temperature: -40-80 °C
  • Warranty Length: 18 mth
  • Width: 91 mm
TeSys T is a motor management system that provides full motor monitoring, control, and protection when used with short circuit protection and a contactor. TeSys T manages most critical processes while reducing downtime and increasing productivity. TeSys T is a flexible system that integrates seamlessly into your automation system through five major communication protocols. TeSys T predicts what will happen in the process, as it accurately monitors current, voltage, and power over a wide range. This controller is the central component in the motor management system. The module manages the basic functions of the motor management system. It manages the measurement of 3 phase current via integral current transformers from 0.4 to 100 A or up to 810 A by external current transformers. It also measures ground current with internal or external ground sensors, motor temperature and the inputs and outputs for the various motor control modes, detected fault management and other functions. Ethernet/IP and Modbus/TCP protocol is used by this controller. Ethernet TCP/IP communication is used. This module has 6 discrete logic inputs, 3 relay logic outputs and a relay output for detected fault signaling overload relay. The current range of this controller is 1.35 to 27 amperes. 120 to 240 VAC is used to power this controller. Controller has the following certifications: UL, CSA NOM, ATEX, BV, EAC, RINA, LROS, DNV, ABS, GL, KERI, RMRoS, C-Tick and CCC.
QTY
  • Product Description
  • Specifications
TeSys T is a motor management system that provides full motor monitoring, control, and protection when used with short circuit protection and a contactor. TeSys T manages most critical processes while reducing downtime and increasing productivity. TeSys T is a flexible system that integrates seamlessly into your automation system through five major communication protocols. TeSys T predicts what will happen in the process, as it accurately monitors current, voltage, and power over a wide range. This controller is the central component in the motor management system. The module manages the basic functions of the motor management system. It manages the measurement of 3 phase current via integral current transformers from 0.4 to 100 A or up to 810 A by external current transformers. It also measures ground current with internal or external ground sensors, motor temperature and the inputs and outputs for the various motor control modes, detected fault management and other functions. Ethernet/IP and Modbus/TCP protocol is used by this controller. Ethernet TCP/IP communication is used. This module has 6 discrete logic inputs, 3 relay logic outputs and a relay output for detected fault signaling overload relay. The current range of this controller is 1.35 to 27 amperes. 120 to 240 VAC is used to power this controller. Controller has the following certifications: UL, CSA NOM, ATEX, BV, EAC, RINA, LROS, DNV, ABS, GL, KERI, RMRoS, C-Tick and CCC.
  • Environment
    • Product Certifications : EAC || DNV || BV || C-tick || CCC || ABS || RINA || RMRoS || CSA || NOM || LROS (Lloyds register of shipping) || UL || KERI || GL || ATEX
    • Mechanical Robustness : vibrations mounted on symmetrical rail1 Gn, 5...300 Hz EN/IEC 60068-2-6 || vibrations plate mounted4 Gn, 5...300 Hz EN/IEC 60068-2-6 || shocks half sine wave acceleration15 Gn for 11 ms EN/IEC 60068-2-27
    • Ambient Air Temperature For Operation : -20-60 °C
    • Standards : IACS E10 || UL 508 || IEC 60947-4-1 || EN 60947-4-1 || CSA C22.2 No 14
    • Ambient Air Temperature For Storage : -40-80 °C
    • Protective Treatment : 12 x 24 hour cycles EN/IEC 60068-2-30 || 48 h EN/IEC 60070-2-11 || TH EN/IEC 60068
    • Operating Altitude : <= 6561.68 ft (2000 m) without derating
    • Fire Resistance : 650 °C EN/IEC 60695-2-12 || 960 °C UL 94
    • Ip Degree Of Protection : IP20
  • Contractual warranty
    • Warranty : 18 months
  • Offer Sustainability
    • Rohs Exemption Information : Yes
    • Mercury Free : Yes
    • Environmental Disclosure : ENVPEP060308EN_V2
    • Sustainable Offer Status : Green Premium product
    • Pvc Free : Yes
    • Reach Regulation : Reference contains Substances of Very High Concern above the threshold
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • China Rohs Regulation : Product out of China RoHS scope. Substance declaration for your information.
    • Circularity Profile : ENVEOLI100411EN_V2
    • Eu Rohs Directive : Compliant with Exemptions
    • Halogen Content Performance : Halogen free plastic parts product
  • Complementary
    • Contacts Type And Composition : 1 NO + 1 NC fault signal || 3 NO
    • Height : 61 mm
    • Connection Pitch : 5.08 mm
    • Permissible Power : 480 VA AC-15), Ie = 2 A, 500000 cycles output) || 30 W DC-13), Ie = 1.25 A, 500000 cycles output)
    • Network And Machine Diagnosis Type : event recording || trip context information || phase fault and earth fault trip counters || trip history information || waiting time after overload tripping || fault recording || remaining operating time before overload tripping || starting current and time || motor control command recording || running hours counter/operating time
    • Pollution Degree : 3
    • Logic Input Number : 6
    • Maximum Operating Rate : 1800 cyc/h
    • Connections - Terminals : control circuit connector 1 0.25-2.5 mm² AWG 24...AWG 14)flexible with cable end || control circuit connector 1 0.2-2.5 mm² AWG 24...AWG 14)flexible without cable end || control circuit connector 1 0.25-2.5 mm² AWG 24...AWG 14)flexible without cable end || control circuit connector 1 0.2-2.5 mm² AWG 24...AWG 14)solid without cable end || control circuit connector 2 0.2-1 mm² AWG 24...AWG 14)flexible with cable end || control circuit connector 2 0.2-1.5 mm² AWG 24...AWG 14)flexible without cable end || control circuit connector 2 0.5-1.5 mm² AWG 24...AWG 14)flexible without cable end || control circuit connector 2 0.2-1 mm² AWG 24...AWG 14)solid without cable end
    • Input Current : 3.1 mA 100 V || 7.5 mA 240 V
    • Current State 1 Guaranteed : logic input 79...264 V >= 2 mA 25 ms
    • Net Weight : 0.53 kg
    • [Uimp] Rated Impulse Withstand Voltage : 4 kV supply, inputs and outputs EN/IEC 60947-4-1 || 6 kV current or voltage measurement circuit EN/IEC 60947-4-1 || 0.8 kV communication circuit EN/IEC 60947-4-1
    • Associated Fuse Rating : 4 A gG output || 0.5 A gG control circuit
    • Electromagnetic Compatibility : electrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 || communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 || relay outputs and supply: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5 || relay outputs and supply: surges (common mode), 4 kV, conforming to EN/IEC 61000-4-5 || control circuit: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 || radiated RF fields, 3, 10 V/m, conforming to EN/IEC 61000-4-3 || fast transients immunity test (other circuits), level 3, 2 kV, conforming to EN/IEC 61000-4-4 || fast transients immunity test (on supply and relay outputs), level 4, 4 kV, conforming to EN/IEC 61000-4-4 || voltage dips and interruptions immunity test, 70 %, 500 ms, conforming to EN/IEC 61000-4-11 || conducted RF disturbances, 10 V, conforming to EN/IEC 61000-4-6 || temperature sensor: surges (serial mode), 0.5 kV, conforming to EN/IEC 61000-4-5 || temperature sensor: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5 || control circuit: surges (serial mode), 1 kV, conforming to EN/IEC 61000-4-5
    • Measurement Accuracy : 5...15 % earth fault current internal measurement || 1 % voltage 100...830 V) || 3 % power factor || 5 % earth fault current external measurement || +/- 30 min/year internal clock || 0,02 Temperature || 1 % current || 5 % active and reactive power
    • Current State 0 Guaranteed : logic input 0...40 V <= 15 mA 25 ms
    • [Ui] Rated Insulation Voltage : 690 V EN/IEC 60947-1 || 690 V CSA C22.2 No 14 || 690 V UL 508
    • Short-Circuit Withstand : 100 kA conforming to EN/IEC 60947-4-1
    • Compatibility Code : LTMR
    • Protection Type : phase unbalance || earth-leakage protection || thermal protection || reverse polarity protection || power factor variation || overload || load fluctuation || locked rotor || thermal overload protection || phase failure || overload (long time)
    • Web Services : web server
    • Width : 91 mm
    • Load Current : 5 A 250 V AC logic output || 5 A 30 V DC logic output
    • Tightening Torque : control circuit 0.5-0.6 N.m flat 3 mm
    • Overvoltage Category : III
    • Depth : 122.5 mm
    • Maximum Operating Frequency : 2 Hz
    • Metering Type : average current Iavg || phase current I1, I2, I3 RMS || imbalance current || earth-fault current || temperature
  • Specifications
    • Product Or Component Type : motor controller
    • Product Name : TeSys T
    • Measurement Current : 1.35-27 A
    • Range : TeSys
    • Current Consumption : 8...62.8 mA
    • [Us] Rated Supply Voltage : 100...240 V AC 50/60 Hz
    • Communication Port Protocol : Modbus TCP/EtherNet/IP
    • Bus Type : Ethernet IEEE 802.3 0...159 10...100 Mbit/s, RJ45 2 shielded twisted pairs
    • Supply Voltage Limits : 93.5-264 V AC
    • Device Application : equipment monitoring and control
    • Device Short Name : LTMR